ThinkSystem DE6400F and DE6400H Product Guide
Lenovo
Lenovo's DE6400F/DE6400H guide gives the 2U24 NVMe controller enclosure (1150 W maximum, 25.07 kg) and the DE120S, DE240S and DE600S expansion enclosures (300, 382 and 1446 W) separate power and size tables.
On this page
Overview
ThinkSystem DE6400F (all-flash) and DE6400H (hybrid) are end-to-end NVMe storage arrays for midrange to high-end block storage. The guide covers the 2U form factor with 24 small form-factor 2.5-inch NVMe drives, two controllers with 16 GB system memory each (32 GB total), and host connections of 10/25Gb iSCSI, 16/32Gb FC/NVMe-FC and 100Gb IB/NVMe-RoCE with 12Gb SAS expansion. A single array reaches 367 TB raw NVMe capacity, expandable to 1.798 PiB all-SSD or 4.577 PiB hybrid.
For facility planning, the physical and electrical sections separate the controller enclosure from the expansion enclosures. The DE6400F and DE6400H 2U24 SFF enclosure is 87 mm high, 447 mm wide, 543 mm deep and 25.07 kg fully configured. Expansion enclosures: DE120S 2U12 LFF 27.12 kg, DE240S 2U24 SFF 24.59 kg and DE600S 4U60 LFF 112.2 kg (175 x 449 x 922 mm).
The electrical table gives maximum power load, inlet current and heat output by source voltage: DE6400F and DE6400H 1150 W, 5.48 A per inlet and 4030 BTU/hour at 200-220 V AC; DE240S 382 W; DE120S 300 W; DE600S 1446 W (7.62 A). Controller enclosures run on 200-240 V, and each enclosure has two redundant hot-swap power supplies (1181 W AC at 220 V for the controller). Operating environment is 5-45 °C for the DE240S and 10-40 °C for the DE120S, 8-90% non-condensing humidity and 3050 m altitude. The document is a manufacturer product guide. Enclosure types (DE6400, DE240S, DE120S and DE600S) have different dimensions and power values, and each must be read from its own row.
Key points
- DE6400F and DE6400H 2U24 SFF controller enclosure: 87 x 447 x 543 mm, 25.07 kg fully configured.
- Maximum controller enclosure load is 1150 W at 200-220 V AC, 5.48 A per inlet, 4030 BTU/hour heat output.
- Expansion enclosure maximum loads: DE240S 382 W, DE120S 300 W, DE600S 1446 W (7.62 A, 4934 BTU/hour).
- Expansion enclosure weights: DE120S 27.12 kg, DE240S 24.59 kg, DE600S 112.2 kg.
- The DE600S 4U60 measures 175 x 449 x 922 mm.
- Power: 200-240 V AC nominal, 50/60 Hz; two redundant hot-swap power supplies per enclosure.
- Operating environment: DE240S 5-45 °C, DE120S 10-40 °C; humidity 8-90% non-condensing; altitude 3050 m.
- Acoustic noise: DE600S 7.2 bels, DE240S and DE120S 6.6 bels.
- A single array scales from 367 TB raw NVMe to 1.798 PiB (all-flash) and 4.577 PiB (hybrid).
Using it in design
- In the storage rack power budget, add the controller enclosure (1150 W at 200-220 V) and each expansion enclosure (300, 382 or 1446 W) as separate rows.
- Take heat load from the BTU/hour values (4030, 1304, 1024 and 4934) into the cooling calculation.
- In weight planning, check the 112.2 kg DE600S and its 922 mm depth against rack depth and load capacity.
- Plan a 200-240 V AC circuit and two power supplies fed from independent sources.
- Compare the allowed ambient temperature by expansion enclosure type (5-45 °C or 10-40 °C) with the hall design.
Who should read it
Electrical, mechanical and facility engineers planning racks, power and cooling for storage arrays.
Document contents
- Introduction
- Did you know?
- Parts and specifications
- Standard components and models
- Power supplies and cables
- Physical specifications
- Operating environment
- Electrical power and heat output
- Warranty and support
Publication details
- Authors
- Lenovo
- Publisher
- Lenovo
- Year
- 2026
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Lenovo (2026). ThinkSystem DE6400F and DE6400H Product Guide. Lenovo. https://lenovopress.lenovo.com/lp1642.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.