Liqid UltraStack AMD MI350P Datasheet: October 2026
LIQID
The Liqid UltraStack datasheet describes 4-30 AMD MI350P GPUs on one EPYC server; 1-20 GPU results are measured, and about 22 kW total system power at 30 GPUs under typical inference load is a projection.
On this page
Overview
Liqid UltraStack is an inference system that attaches 4 to 30 AMD Instinct MI350P GPUs to one dual-socket AMD EPYC 9005 server over PCIe Gen 5, running one model per GPU. GPU pooling uses the Liqid PCIe Gen 5 fabric and 10-slot EX-Series expansion chassis, one chassis per 10 GPUs (1, 2 or 3 chassis). The system is air-cooled and needs no liquid cooling or facility redesign.
Each MI350P offers 144 GB HBM3E, about 4 TB/s memory bandwidth per GPU and about 2.3 PFLOPS FP8, at 600 W per GPU (configurable to 450 W). The configuration table gives aggregate HBM3E of 576 GB, 1.44 TB, 2.88 TB and 4.32 TB for 4, 10, 20 and 30 GPUs; FP8 performance of 9.2, 23, 46 and 69 PF; and GPU power of 2.4, 6, 12 and 18 kW.
The key distinction is between measurement and projection. Performance data rests on AMD published specifications and Liqid Phase-3 testing on 1 to 20 GPUs; 7B-class throughput reaches a measured 4,653 tok/s (1 GPU), 18,526 (4), 44,383 (10) and about 89,000 (20 GPUs). The roughly 133,000 tok/s and about 22 kW total system power at 30 GPUs are projected from measured 20-GPU scaling.
The power row reflects typical AI inference load and varies by configuration and workload; GPU power (18 kW at 30 GPUs) is separate from total system power (about 22 kW). The efficiency claims (up to 75% fewer servers, up to 2.1x tokens per dollar) are Liqid internal targets, not measurements.
Key points
- 4 to 30 MI350P GPUs attach to one dual-socket AMD EPYC 9005 server over PCIe Gen 5, one model per GPU.
- Each MI350P has 144 GB HBM3E, about 4 TB/s, about 2.3 PFLOPS FP8 and 600 W (configurable to 450 W).
- GPU power for 4, 10, 20 and 30 GPUs is 2.4, 6, 12 and 18 kW; aggregate HBM3E ranges from 576 GB to 4.32 TB.
- Total system power at 30 GPUs is about 22 kW; the value is for typical inference load and is not a maximum input rating.
- 1-20 GPU results are measured; 30-GPU results are projected from 20-GPU scaling.
- 7B-class throughput: 4,653 tok/s on 1 GPU, 18,526 on 4, 44,383 on 10, about 89,000 on 20 (measured); about 133,000 on 30 (projected).
- The system is air-cooled and needs no liquid cooling or facility redesign.
- One Liqid 10-slot chassis per 10 GPUs, plus one Liqid Director 1U management appliance.
- Claims of up to 75% fewer servers, 2.1x tokens per dollar, 1.8x tokens per watt and 50% lower power are Liqid internal targets, not measurements.
Using it in design
- For the 30-GPU configuration, build the rack power budget with the difference between the about-22 kW projection and the maximum input rating in mind, and confirm maximum input power with the manufacturer.
- Add the chassis count (1 per 10 GPUs) and the 1U Director appliance to the rack layout and cabling plan.
- Keep GPU power as a separate calculation row at 600 W or 450 W and add CPU, network and storage for total system power.
- Since 30-GPU results are projections, validate capacity targets against the measured 20-GPU values.
Who should read it
Electrical, cooling and rack engineers and IT architects planning GPU pools for multi-model inference.
Document contents
- The growth dilemma
- One model per GPU, one host
- Configurations: 4 to 30 GPUs on one server
- What you can run as you grow
- What UltraStack adds
- Technical specifications
- Per-GPU building block
Publication details
- Authors
- LIQID
- Publisher
- LIQID
- Year
- 2026
- Document number
- 10.13.26
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
LIQID (2026). Liqid UltraStack AMD MI350P Datasheet: October 2026. LIQID. 10.13.26. https://cdi.liqid.com/hubfs/UltraStack-AMD_MI350P_Datasheet_Oct2026.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.