Technical guideFree to read2026

NVIDIA Spectrum-6 SN6000 Hardware User Manual: Specifications

NVIDIA

NVIDIA's Spectrum-6 SN6000 specification page separates the air-cooled SN6600 (200-240 VAC, 3.94 kW typical) from the liquid-cooled SN6600-LD, SN6810-LD and SN6800-LD (48 VDC) on power, size and ambient limits.

On this page

Overview

The page gives hardware planning tables for the Spectrum-6 based SN6000 Ethernet switch family: SN6600-LD, SN6600, SN6810-LD and SN6800-LD. The tables cover mechanical size and weight, mounting, speed and port form factor, environment, cooling, power input, power consumption and main components. The page was last updated on 4 November 2026.

Air and liquid cooled models are clearly separated. The SN6600 is air-cooled (5 fans, N+1 redundant, port-side intake), runs on 200-240 VAC and is 5.25 in (133.35 mm) high and 52 kg. The liquid-cooled -LD models take 48 VDC (40-60 VDC), mount in a 19-inch MGX v1.2 rack, and their depth value includes the UQD fittings and front levers (900 mm).

Power values depend on the optic type. SN6600-LD typical power is 3.3 kW with fully retimed optics (FRO) and 2.79 kW with transmit retimed optics (TRO); for the air-cooled SN6600 the values are 3.94 kW and 3.2 kW. SN6810-LD lists 1.96 kW typical and 2.2 kW maximum; SN6800-LD lists 8.3 kW typical and 10.5 kW maximum. Operating ambient is 5-40 °C for the -LD models and 0-35 °C for the SN6600 (ASHRAE A3). The document is a manufacturer specification table; liquid cooling requirements sit in a separate section and have no values on this page. Rack placement, power distribution type and optic selection should follow the rows of these tables.

Key points

  1. SN6600-LD: 88 x 438 x 900 mm (including UQD and front levers), 33 kg, 128 x 800 Gb/s, 48 VDC (40-60 VDC), typical 3.3 kW (FRO) or 2.79 kW (TRO).
  2. SN6600 (air-cooled): 133.35 x 438 x 767 mm, 52 kg, 200-240 VAC, 5 fans N+1, typical 3.94 kW (FRO) or 3.2 kW (TRO).
  3. SN6810-LD: 87 x 438 x 900 mm, 32.5 kg, 48 VDC, typical 1.96 kW, maximum 2.2 kW.
  4. SN6800-LD: 220 x 438 x 900 mm, 95 kg, 4 x Spectrum-6 ASIC, 2048 x 200 Gb/s, 409.6 Tbps, typical 8.3 kW, maximum 10.5 kW.
  5. Operating ambient is 5-40 °C for liquid-cooled models and 0-35 °C (ASHRAE A3) for the air-cooled SN6600; humidity 10-85% non-condensing; altitude 3,050 m.
  6. Liquid-cooled models mount in a 19-inch MGX v1.2 rack and the air-cooled model in a 19-inch EIA rack.
  7. Power on the SN6600 family depends on optic type (FRO versus TRO).
  8. The SN6600 and SN6600-LD offer 102.4 Tbps throughput and 256 MB packet buffer.

Using it in design

  • In the rack power budget, use each model's own row: liquid-cooled models need 48 VDC while the air-cooled SN6600 needs 200-240 VAC, so separate the supply type up front.
  • In power calculation, choose the optic type (FRO or TRO); on the SN6600 the difference is 3.94 kW versus 3.2 kW.
  • In depth calculation for liquid-cooled models, include UQD fittings and front levers (900 mm).
  • Compare the SN6600's 35 °C and the -LD models' 40 °C ambient limits with the cold aisle design temperature.
  • For the SN6800-LD, carry the 10.5 kW maximum into supply and cooling capacity separately from the 8.3 kW typical.

Who should read it

Network and facility engineers planning rack power, depth and cooling for AI network spines.

Document contents

  1. SN6600-LD Specifications
  2. SN6600 Specifications
  3. SN6810-LD Specifications
  4. SN6800-LD Specifications

Publication details

Authors
NVIDIA
Publisher
NVIDIA
Year
2026
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

NVIDIA (2026). NVIDIA Spectrum-6 SN6000 Hardware User Manual: Specifications. NVIDIA. https://networking-docs.nvidia.com/sn6000hw/specifications

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.