Data Centers and Water: Frequently Asked Questions
Congressional Research Service · Peter Folger, Elena H. Humphreys et al.
A July 2026 Congressional Research Service report answering questions on data-centre water use, sources, discharges and the federal and state regulatory framework.
On this page
Overview
CRS R49057 was prepared to answer questions from Members of Congress and constituents about how data centres affect the quantity and quality of local water resources. It first describes cooling technologies (air and liquid cooling, hybrid, two-phase, immersion) and their water needs. One study estimates that US data centres directly used about 17 billion gallons of water in 2023, up from 5.6 billion gallons in 2014.
On water efficiency, the report defines WUE (water use effectiveness) as total water consumption divided by IT equipment electricity demand. The metric covers only direct facility use, not indirect water consumed in power generation. Water-cooled chiller systems typically have the highest WUE because of cooling tower evaporation. Economizers and raised setpoints reduce water use, while air-cooled chillers use no water but more energy.
In the water sources section, an estimated 97% of US data centres' on-site water needs were met by public water systems as of 2025. Treated wastewater and direct surface or groundwater withdrawals are the alternatives; they may need pretreatment and longer permitting. Water allocation is mainly a state and local matter, and the federal role is limited to reservoirs, planning support and data collection.
The water quality section groups discharges into wastewater, stormwater and dredged or fill material from site development. In evaporative systems blowdown concentrates dissolved solids and chlorine; corrosion inhibitors, biocides and dispersants, metals, pH and temperature can also count as pollutants. Most data centres send wastewater to publicly owned treatment works. The report closes with a table of related bills in the 119th Congress.
Key points
- US data centres directly used about 17 billion gallons in 2023, versus 5.6 billion gallons in 2014.
- WUE is total water consumption divided by IT electricity demand and excludes indirect water from power generation.
- Water-cooled chiller systems typically have the highest WUE because of cooling tower use.
- Evaporative cooling is generally more energy efficient than air-cooled chillers, which use no water but more energy.
- In 2025 an estimated 97% of US data centres relied on public water systems for on-site water.
- Open-loop water cooling needs more water than closed-loop; demand rises in hot hours and seasons.
- Facilities using raw or reclaimed water may need pretreatment; self-supply can take longer because of permits and infrastructure.
- Discharges include dissolved solids, chlorine, corrosion inhibitors, biocides, copper, nickel and chromium, pH and temperature; commissioning and cleaning raise chemical discharges.
- Facility-specific water-use data are limited; public-supply customers are reported together with other users in the service area.
Using it in design
- Set WUE targets considering both direct and indirect water, and compare cooling architectures on the water-energy balance.
- Treat economizer use and higher setpoints as design decisions that reduce water consumption.
- Compare public supply, reclaimed water and self-supply on permitting time and pretreatment needs.
- Define tower cycles of concentration and blowdown quality and match them to discharge permit and acceptance conditions.
- Plan chemical and metal discharges from commissioning, passivation and cleaning and include them in wastewater management.
- Clarify demand, tariff and data-sharing terms in the water service agreement during design.
Who should read it
Design engineers, developers and policy analysts handling data-centre siting, water supply and discharge permitting.
Document contents
- Introduction
- What Are Data Centers?
- Data Center Water Use
- Water Sources and Authorities
- Water Quality Impacts from Data Center Discharges
- Wastewater, Stormwater and Dredged or Fill Discharges
- Congressional Action
- Table A-1: Selected Bills in the 119th Congress
Publication details
- Authors
- Peter Folger; Elena H. Humphreys; Nicole T. Carter; Corrie E. Clark; Laura Gatz; Anna E. Normand; Charles V. Stern
- Publisher
- Congressional Research Service
- Year
- 2026
- Document number
- R49057
- Document language
- English
- Source type
- Government / public
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Federal publication inspected; third-party material and full-document rights were not comprehensively cleared. Citation-only conservative treatment.
Citation
Peter Folger; Elena H. Humphreys; Nicole T. Carter; Corrie E. Clark; Laura Gatz; Anna E. Normand; Charles V. Stern (2026). Data Centers and Water: Frequently Asked Questions. Congressional Research Service. R49057. https://www.congress.gov/crs_external_products/R/PDF/R49057/R49057.1.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
