EMKO Trans-AMF Automatic Generator Control and Transfer Panel: Product Page and Start-Inhibit FAQ
Original title Trans-AMF: Otomatik Jeneratör Kontrol ve Transfer Paneli: işletme soruları
EMKO Elektronik
The EMKO Trans-AMF page lists four checks for why a generator does not start on mains failure (mains lamp, remote start input, run calendar, fault detection parameter) and gives the unit's input-output specification.
On this page
Overview
The page presents EMKO Elektronik's Trans-AMF automatic generator control and transfer panel. The device offers CanBus J1939 ECU support, a log of the last 500 events and alarms, statistics records, mains and generator phase-sequence checks, selectable resistive input types such as Pt-100, VDO, ABD, GM, Ford and Datcon, and reading of SPN, FMI and OC values over J1939.
The technical specification includes 6 configurable digital inputs, 4 analogue resistive inputs, a cabinet temperature sensor, magnetic pickup and charge-alternator inputs, and 2 relay, 4 transistor, mains and generator contactor outputs. It has a three-phase current transformer input and earth-leakage current measurement; supply is 8-32 VDC and the front panel is IP65. Outputs can be assigned 138 different functions.
The FAQ section addresses field problems. If the generator does not start on mains failure, check that the mains lamp is off, no input is set to remote start, the run calendar is not active and the Mains Failure Detection parameter is active. It also explains failure to crank, oil pressure not read, mains not detected, heater control, fuel filling, motorised breaker control and exercise runs. The page is a product and support document.
Key points
- If the generator does not start on mains failure, four checks apply: the mains lamp must be off, no input may be set to remote start, the run calendar must be inactive and the Mains Failure Detection parameter must be active.
- With a remote start input selected, the unit waits for that input to be active before starting the generator on mains loss.
- The run calendar is defined by daily start and stop times; correct date and time settings are required.
- Exercise runs can be set with 4 time selections per day on all 7 days of the week.
- The outputs can be assigned 138 functions, and their polarity can be normally open or closed.
- Inputs: 6 configurable digital, 4 analogue resistive (0-1300 ohm, 1% FS), cabinet temperature (-50 to +100 degrees C); outputs: 2 relays, 4 transistors, mains and generator contactors.
- Trans-AMF, MidiAMF and MiniAMF give the same function in shrinking sizes with 7, 5 and 3 digital inputs; the AUTO series has no mains measurement or transfer.
- The event memory holds the last 500 events and alarms; SPN, FMI and OC values are read over J1939.
Using it in design
- Add the start-inhibit items to the commissioning checklist: remote start input, run calendar and mains failure detection parameter must be verified by test.
- For facilities needing uninterrupted service such as data centres, keep the run calendar and remote start inputs disabled and mains failure detection active.
- Plan the output count needed for fuel filling, heater and motorised breaker control (2 relays, 4 transistors) in advance; use an expansion module or larger model if short.
- Define the weekly exercise programme with or without load transfer and check the clock setting periodically.
- Specify the AMF series rather than the AUTO series when mains measurement and transfer are needed.
Who should read it
Electrical engineers and service teams who design, commission and operate generator automatic transfer panels.
Document contents
- Product features
- Technical specifications
- Product codes
- Downloads and application notes
- Frequently asked questions
Publication details
- Authors
- EMKO Elektronik
- Publisher
- EMKO Elektronik
- Year
- Year not stated
- Document language
- Turkish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Official publisher material inspected. No document-specific commercial redistribution permission established; retain metadata and original short summaries only.
Citation
EMKO Elektronik Trans-AMF: Otomatik Jeneratör Kontrol ve Transfer Paneli: işletme soruları. EMKO Elektronik. https://www.emkoelektronik.com.tr/tr/urunler/trans-amf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
