Technical guideFree to read2025

ETERNUS AF S3 Series All-Flash Arrays: Site Planning Guide

Fsas Technologies Inc.

Fsas Technologies' site planning guide for ETERNUS AF150/250/650 S3: 750-1340 W controller power, 10-40 °C intake air, 850 mm service areas and a D-curve circuit protector requirement.

On this page

Overview

The document is Fsas Technologies' site planning guide for the ETERNUS AF S3 series of all-flash storage arrays. It has two chapters: the first gives installation specifications, dimensions, packaging, installation area, environment, floor load, outlet and circuit protector requirements for the AF150 S3, AF250 S3 and AF650 S3; the second sets rack installation requirements.

For each model the controller enclosure, drive enclosure and power distribution unit (PDU) are tabulated on separate rows. Maximum controller consumption is 750 W for the AF150 S3, 800 W for the AF250 S3 and 1340 W for the AF650 S3, and a drive enclosure draws up to 430 W. Heat generation and airflow are given in kJ/h and m3/min per controller. A controller figure must therefore not be read as the load of a fully expanded array.

Environmental conditions are 10-40 °C operating temperature, 20-80% relative humidity, a 15 °C/h gradient and 0-3000 m altitude. The cooling section explains that air enters at the front and leaves at the rear, and that at 40 °C intake the exhaust can reach 50 °C or more. At 1800 m or higher a Highland Mode that raises fan speed must be enabled.

On the electrical side, distribution board circuit protectors must have a breaking characteristic equal to or slower than IEC/EN 60898-1 curve D; a faster protector can disconnect other PSUs on the same line after a PSU failure. For floors the guide gives the condition (load capacity) > (weight / installation area including service areas).

Key points

  1. Maximum controller consumption: AF150 S3 750 W, AF250 S3 800 W, AF650 S3 1340 W; drive enclosure 430 W.
  2. AF650 S3 controller measures 482 x 788 x 133 mm (3U), up to 58 kg; AF150/AF250 controllers are 482 x 645 x 88 mm (2U), 35 kg.
  3. AF650 S3 controller airflow is 6.2 m3/min, and 4.0 m3/min for AF150/AF250.
  4. Operating conditions: 10-40 °C, 20-80% RH, maximum wet bulb 29 °C, 15 °C/h gradient, 0-3000 m altitude.
  5. Highland Mode is mandatory at 1800 m and above; fans run fast and the unit must be power-cycled to apply the setting.
  6. 19-inch rack is 700 x 1050 x 2000 mm (1272 mm deep with stabiliser); service area 850 mm front and rear.
  7. Distribution board circuit protectors must be curve D (IEC/EN 60898-1) or slower.
  8. Mobile phones must be used at least 1.0 m from the storage system.

Using it in design

  • In the power budget sum the controller, each drive enclosure and the PDUs separately; do not enter the controller watt figure alone as the array load.
  • Keep cold-aisle temperature within 10-40 °C and humidity within 20-80% RH; at 40 °C intake check hot-aisle capacity for exhaust of 50 °C or more.
  • At sites above 1800 m add the Highland Mode setting to the commissioning checklist and include its fan noise and power effect in the budget.
  • Write the curve D requirement into panel specifications and include the PSU failure case in the selectivity study.
  • Check floor load against the area including service space and leave 850 mm of service clearance at the front and rear of the rack.

Who should read it

Data-centre electrical, mechanical and site planning engineers installing all-flash storage.

Document contents

  1. ETERNUS AF Installation
  2. Installation Specifications
  3. Dimensions and Package Size
  4. Installation Area and Environment
  5. Air Conditioning
  6. Load Bearing Capacity for Floors
  7. Outlet/Socket and Circuit Protector Specifications
  8. Rack Installation Specifications

Publication details

Authors
Fsas Technologies Inc.
Publisher
Fsas Technologies Inc.
Year
2025
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Fsas Technologies Inc. (2025). ETERNUS AF S3 Series All-Flash Arrays: Site Planning Guide. Fsas Technologies Inc.. https://sp.ts.fujitsu.com/dmsp/Publications/public/p3ag-4042-en.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.