ETERNUS AF S3 Series All-Flash Arrays: Site Planning Guide
Fsas Technologies Inc.
Fsas Technologies' site planning guide for ETERNUS AF150/250/650 S3: 750-1340 W controller power, 10-40 °C intake air, 850 mm service areas and a D-curve circuit protector requirement.
On this page
Overview
The document is Fsas Technologies' site planning guide for the ETERNUS AF S3 series of all-flash storage arrays. It has two chapters: the first gives installation specifications, dimensions, packaging, installation area, environment, floor load, outlet and circuit protector requirements for the AF150 S3, AF250 S3 and AF650 S3; the second sets rack installation requirements.
For each model the controller enclosure, drive enclosure and power distribution unit (PDU) are tabulated on separate rows. Maximum controller consumption is 750 W for the AF150 S3, 800 W for the AF250 S3 and 1340 W for the AF650 S3, and a drive enclosure draws up to 430 W. Heat generation and airflow are given in kJ/h and m3/min per controller. A controller figure must therefore not be read as the load of a fully expanded array.
Environmental conditions are 10-40 °C operating temperature, 20-80% relative humidity, a 15 °C/h gradient and 0-3000 m altitude. The cooling section explains that air enters at the front and leaves at the rear, and that at 40 °C intake the exhaust can reach 50 °C or more. At 1800 m or higher a Highland Mode that raises fan speed must be enabled.
On the electrical side, distribution board circuit protectors must have a breaking characteristic equal to or slower than IEC/EN 60898-1 curve D; a faster protector can disconnect other PSUs on the same line after a PSU failure. For floors the guide gives the condition (load capacity) > (weight / installation area including service areas).
Key points
- Maximum controller consumption: AF150 S3 750 W, AF250 S3 800 W, AF650 S3 1340 W; drive enclosure 430 W.
- AF650 S3 controller measures 482 x 788 x 133 mm (3U), up to 58 kg; AF150/AF250 controllers are 482 x 645 x 88 mm (2U), 35 kg.
- AF650 S3 controller airflow is 6.2 m3/min, and 4.0 m3/min for AF150/AF250.
- Operating conditions: 10-40 °C, 20-80% RH, maximum wet bulb 29 °C, 15 °C/h gradient, 0-3000 m altitude.
- Highland Mode is mandatory at 1800 m and above; fans run fast and the unit must be power-cycled to apply the setting.
- 19-inch rack is 700 x 1050 x 2000 mm (1272 mm deep with stabiliser); service area 850 mm front and rear.
- Distribution board circuit protectors must be curve D (IEC/EN 60898-1) or slower.
- Mobile phones must be used at least 1.0 m from the storage system.
Using it in design
- In the power budget sum the controller, each drive enclosure and the PDUs separately; do not enter the controller watt figure alone as the array load.
- Keep cold-aisle temperature within 10-40 °C and humidity within 20-80% RH; at 40 °C intake check hot-aisle capacity for exhaust of 50 °C or more.
- At sites above 1800 m add the Highland Mode setting to the commissioning checklist and include its fan noise and power effect in the budget.
- Write the curve D requirement into panel specifications and include the PSU failure case in the selectivity study.
- Check floor load against the area including service space and leave 850 mm of service clearance at the front and rear of the rack.
Who should read it
Data-centre electrical, mechanical and site planning engineers installing all-flash storage.
Document contents
- ETERNUS AF Installation
- Installation Specifications
- Dimensions and Package Size
- Installation Area and Environment
- Air Conditioning
- Load Bearing Capacity for Floors
- Outlet/Socket and Circuit Protector Specifications
- Rack Installation Specifications
Publication details
- Authors
- Fsas Technologies Inc.
- Publisher
- Fsas Technologies Inc.
- Year
- 2025
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Fsas Technologies Inc. (2025). ETERNUS AF S3 Series All-Flash Arrays: Site Planning Guide. Fsas Technologies Inc.. https://sp.ts.fujitsu.com/dmsp/Publications/public/p3ag-4042-en.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.