IPU-Machine: M2000 Datasheet, Version 1.2 (2020)
Original title Graphcore IPU-Machine M2000 Datasheet v1.2
Graphcore
Graphcore's IPU-M2000 datasheet: 1U, 4 GC200 IPUs, 1 petaFLOPS, 1100 W typical, 2 x 1500 W PSUs, 60 CFM, 10-35 °C inlet air and 16.4 kg weight.
On this page
Overview
The document is Graphcore's version 1.2 IPU-Machine M2000 datasheet, dated December 2020. The M2000 is a 1U AI compute platform with 4 GC200 IPUs, 1 petaFLOPS of AI compute, 5,888 processor cores and 35,328 worker threads. It scales from a direct-attach development system to a 64K-IPU configuration. The datasheet covers product configurations, technical specifications, environmental characteristics, standards compliance and ordering information.
Configurations fall into four groups: a single direct-attach M2000, four direct-attach, four M2000s pre-packaged with a server as a 5U unit, and the scalable IPU-POD reference design. The IPU-POD64 combines 16 M2000s for 16 petaFLOPS at FP16.16 and about 7.2 TB of Exchange Memory, scaling to 64,000 IPUs in a 2D-torus topology. For the IPU-POD64, power, thermal and data-centre requirements are left to a separate installation and integration guide.
Values critical for facility design are: two 1500 W hot-plug PSUs, 1100 W typical power consumption, a user-configurable PowerCap, 100-240 Vac input, air cooling with N+1 hot-plug fans, 60 CFM airflow at nominal fan speed and front-to-rear airflow as standard (rear-to-front optional). The chassis is 440 x 728 mm, 1U, and weighs 16.395 kg.
The operating inlet air range is 10-35 °C at 5-85% relative humidity and the altitude range is 0-3048 m; above 900 m the maximum ambient temperature is derated 1 °C per 300 m. This is a 2020 product datasheet; it gives no rack-level power or heat load for the IPU-POD64.
Key points
- 1U, 440 x 728 mm chassis, 16.395 kg; 4 GC200 IPUs, 5,888 cores, 1 petaFLOPS, 0.25 petaFLOPS FP32.
- 2 x 1500 W hot-plug PSUs (SSI slim), 100-240 Vac input; typical power 1100 W with a configurable PowerCap.
- Air cooled with N+1 hot-plug fans; 60 CFM at nominal speed; front-to-rear (standard) or rear-to-front (optional) airflow.
- Inlet air 10-35 °C, 5-85% RH; altitude 0-3048 m; derate 1 °C per 300 m above 900 m.
- Exchange Memory up to about 450 GB (3.6 GB in-processor and 448 GB Streaming Memory), 180 TB/s bandwidth.
- IPU-Links give 2 Tbps bi-directional bandwidth; up to 8 M2000s in direct-connected stacks and 16 in IPU-POD systems.
- IPU-POD64: 16 M2000s, 16 petaFLOPS FP16.16, ~7.2 TB Exchange Memory; scales to 64,000 IPUs.
- Management: OpenBMC, Redfish, Prometheus/Grafana; Slurm and Kubernetes plug-ins.
Using it in design
- In the rack power budget use the 1100 W typical value while considering the 1500 W PSU capacity and the PowerCap setting; also take the IPU-POD64 power and thermal values from its integration guide.
- In cooling design apply the 60 CFM flow and the 10-35 °C inlet limit; match the airflow direction (front-to-rear or rear-to-front) to cold and hot aisle orientation.
- Add the 728 mm depth and 16.4 kg weight to the rack load and depth checks.
- At sites above 900 m apply the maximum inlet temperature derating.
- Carry the 100 GbE RoCEv2 NIC and OSFP IPU-Link cabling needs into the in-cabinet cable path.
Who should read it
Data-centre engineers planning power, cooling and rack layout for IPU-based AI systems.
Document contents
- Overview
- Product Description
- Product Configurations
- IPU-POD Reference Design for Scale-Out
- Software Support
- Technical Specifications
- Environmental Characteristics
- Standards Compliance
- Ordering Information
Publication details
- Authors
- Graphcore
- Publisher
- Graphcore
- Year
- 2020
- Document number
- Version 1.2, 2 December 2020
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Graphcore (2020). Graphcore IPU-Machine M2000 Datasheet v1.2. Graphcore. Version 1.2, 2 December 2020. https://ocf.co.uk/media/mpwhlcge/ipu-machine-m2000-datasheet.pdf