Graphcore's IPU-M2000 datasheet: 1U, 4 GC200 IPUs, 1 petaFLOPS, 1100 W typical, 2 x 1500 W PSUs, 60 CFM, 10-35 °C inlet air and 16.4 kg weight.

On this page

Overview

The document is Graphcore's version 1.2 IPU-Machine M2000 datasheet, dated December 2020. The M2000 is a 1U AI compute platform with 4 GC200 IPUs, 1 petaFLOPS of AI compute, 5,888 processor cores and 35,328 worker threads. It scales from a direct-attach development system to a 64K-IPU configuration. The datasheet covers product configurations, technical specifications, environmental characteristics, standards compliance and ordering information.

Configurations fall into four groups: a single direct-attach M2000, four direct-attach, four M2000s pre-packaged with a server as a 5U unit, and the scalable IPU-POD reference design. The IPU-POD64 combines 16 M2000s for 16 petaFLOPS at FP16.16 and about 7.2 TB of Exchange Memory, scaling to 64,000 IPUs in a 2D-torus topology. For the IPU-POD64, power, thermal and data-centre requirements are left to a separate installation and integration guide.

Values critical for facility design are: two 1500 W hot-plug PSUs, 1100 W typical power consumption, a user-configurable PowerCap, 100-240 Vac input, air cooling with N+1 hot-plug fans, 60 CFM airflow at nominal fan speed and front-to-rear airflow as standard (rear-to-front optional). The chassis is 440 x 728 mm, 1U, and weighs 16.395 kg.

The operating inlet air range is 10-35 °C at 5-85% relative humidity and the altitude range is 0-3048 m; above 900 m the maximum ambient temperature is derated 1 °C per 300 m. This is a 2020 product datasheet; it gives no rack-level power or heat load for the IPU-POD64.

Key points

  1. 1U, 440 x 728 mm chassis, 16.395 kg; 4 GC200 IPUs, 5,888 cores, 1 petaFLOPS, 0.25 petaFLOPS FP32.
  2. 2 x 1500 W hot-plug PSUs (SSI slim), 100-240 Vac input; typical power 1100 W with a configurable PowerCap.
  3. Air cooled with N+1 hot-plug fans; 60 CFM at nominal speed; front-to-rear (standard) or rear-to-front (optional) airflow.
  4. Inlet air 10-35 °C, 5-85% RH; altitude 0-3048 m; derate 1 °C per 300 m above 900 m.
  5. Exchange Memory up to about 450 GB (3.6 GB in-processor and 448 GB Streaming Memory), 180 TB/s bandwidth.
  6. IPU-Links give 2 Tbps bi-directional bandwidth; up to 8 M2000s in direct-connected stacks and 16 in IPU-POD systems.
  7. IPU-POD64: 16 M2000s, 16 petaFLOPS FP16.16, ~7.2 TB Exchange Memory; scales to 64,000 IPUs.
  8. Management: OpenBMC, Redfish, Prometheus/Grafana; Slurm and Kubernetes plug-ins.

Using it in design

  • In the rack power budget use the 1100 W typical value while considering the 1500 W PSU capacity and the PowerCap setting; also take the IPU-POD64 power and thermal values from its integration guide.
  • In cooling design apply the 60 CFM flow and the 10-35 °C inlet limit; match the airflow direction (front-to-rear or rear-to-front) to cold and hot aisle orientation.
  • Add the 728 mm depth and 16.4 kg weight to the rack load and depth checks.
  • At sites above 900 m apply the maximum inlet temperature derating.
  • Carry the 100 GbE RoCEv2 NIC and OSFP IPU-Link cabling needs into the in-cabinet cable path.

Who should read it

Data-centre engineers planning power, cooling and rack layout for IPU-based AI systems.

Document contents

  1. Overview
  2. Product Description
  3. Product Configurations
  4. IPU-POD Reference Design for Scale-Out
  5. Software Support
  6. Technical Specifications
  7. Environmental Characteristics
  8. Standards Compliance
  9. Ordering Information

Publication details

Authors
Graphcore
Publisher
Graphcore
Year
2020
Document number
Version 1.2, 2 December 2020
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Graphcore (2020). Graphcore IPU-Machine M2000 Datasheet v1.2. Graphcore. Version 1.2, 2 December 2020. https://ocf.co.uk/media/mpwhlcge/ipu-machine-m2000-datasheet.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.