IBM Storage FlashSystem 5300: Hardware Guide (Version 8.7.1)
Original title IBM Storage FlashSystem 5300 Hardware Guide
IBM
IBM's FlashSystem 5300 hardware guide: 1U control enclosure, 1500 W PSUs, 662 W and 2259 BTU/hr in an example 12-FCM configuration, 5-35 °C ambient and rack doors at least 60% perforated.
On this page
Overview
The document is the 2025 hardware guide for IBM Storage FlashSystem 5300, published with version 8.7.1. It covers system overview (node canisters, Fibre Channel, SAS and Ethernet adapters, batteries, power supplies, drives), 2U and 5U expansion enclosures, hardware planning, installation, servicing and troubleshooting. The planning chapter is the most directly useful part for a facility designer.
The control enclosure power supply is an auto-ranging PSU rated 100-127 V (low line) or 200-240 V single-phase AC, with 1500 W maximum output and 10 A maximum input current (IEC C14). Each enclosure has two PSUs for redundancy. In IBM's example measurement a control enclosure with twelve FCM4 9 TB drives and four quad-port 32 Gbps FC adapters draws 662 W and gives 2259 BTU/hr; measurements are illustrations and must be tested in your own environment.
Operating conditions are 5-35 °C ambient temperature, 0-3048 m altitude, 8-80% non-condensing relative humidity and 23 °C maximum wet bulb. Air flows front to rear, and the rack front and rear doors must be at least 60% perforated, otherwise additional cooling mechanisms are needed. The control enclosure is 43 mm high, 446 mm wide and 770 mm deep, and weighs 16.8 kg without drives and 19.5 kg fully configured. Clearance of 50 mm at the sides and at least 100 mm at the back is required.
For expansion enclosures the 2U24 model uses two 764 W PSUs and the 5U92 model two 2400 W PSUs; a 2U enclosure with 24 flash drives measured 151 W and a 5U enclosure with 92 10 TB nearline SAS drives 848 W. The 5U enclosure needs 200-240 V and C19 PDUs. The power and heat values in the document belong to the sample configurations; facility input depends on drive count and ambient temperature.
Key points
- Control enclosure PSU: auto-ranging 100-127 V or 200-240 V, 10 A, 1500 W output, IEC C14; two PSUs per enclosure.
- Example measurement: 662 W and 2259 BTU/hr with twelve FCM4 9 TB drives and four quad-port 32 Gbps FC adapters.
- Operating conditions: 5-35 °C, 0-3048 m, 8-80% RH (non-condensing), maximum wet bulb 23 °C.
- Airflow is front to rear; rack front and rear doors must be at least 60% perforated.
- Control enclosure 43 x 446 x 770 mm; 16.8 kg without drives, 19.5 kg fully configured; 50 mm side and at least 100 mm rear clearance.
- 2U24 expansion: 764 W per PSU; 151 W with 24 flash drives, 234 W with 24 15K SAS.
- 5U92 expansion: 2400 W PSUs, 200-240 V, C19 PDU required; 848 W with 92 10 TB nearline SAS, 748 W with 92 15 TB flash.
- The rack must support the total enclosure weight and heavy devices go at the bottom.
Using it in design
- In the rack power budget scale the 662 W example with the configuration; read the 1500 W PSU rating as capacity rather than load and spread the redundant PSUs across A/B feeds.
- Write the 60% minimum perforation for rack doors into the specification; keep blanking panels and side clearances (50 mm, 100 mm at the rear).
- In heat load calculations keep the BTU/hr example (2259 BTU/hr control enclosure) separate from the PSU-based upper figures such as 8189 BTU/hr for the 5U92.
- For 5U expansion enclosures specify 200-240 V and C19 PDUs in the cabinet; verify floor load with the weight tables.
- Keep the environment below the 35 °C upper limit (40 °C for the 24-drive expansion enclosure); above 2134 m the limit is 30 °C.
Who should read it
Storage engineers installing FlashSystem 5300 and data-centre designers planning power, cooling and rack layout.
Document contents
- FlashSystem 5300
- Notices
- System Overview
- Expansion Enclosures
- Planning for Hardware
- Installing
- Hardware Servicing
Publication details
- Authors
- IBM
- Publisher
- IBM
- Year
- Year not stated
- Document number
- Version 8.7.1 documentation path
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
IBM IBM Storage FlashSystem 5300 Hardware Guide. IBM. Version 8.7.1 documentation path. https://public.dhe.ibm.com/storage/EOS/flash_storwize/version87x/flashsystem5k-v871/hardware-guide/fs5300_pdfguide.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
