Technical guideFree to readYear not stated

IBM Storage FlashSystem 7300: Hardware Guide (Version 8.7.1)

Original title IBM Storage FlashSystem 7300 Hardware Guide

IBM

IBM's FlashSystem 7300 hardware guide: 2U control enclosure, 2000 W PSUs, about 1076-1095 W and 3670-3737 BTU/hr in 24-FCM NVMe examples, 5-35 °C ambient.

On this page

Overview

The document is the 2025 hardware guide for IBM Storage FlashSystem 7300 and states that the product is ENERGY STAR certified. It covers system overview, expansion enclosures, hardware planning, installation and hardware servicing. The planning chapter gives power, environment, dimension and clearance values in tables.

Each control enclosure PSU is rated 2000 W and needs 200-240 V single-phase AC, 50 or 60 Hz, at most 10 A (x2) input (IEC C14); the calorific value is 6824 BTU/hr per PSU. In IBM's example measurements an enclosure with 24 FCM NVMe 4.8 TB drives and six 32 Gbps FC adapters draws 1075.6 W (3670.1 BTU/hr), and one with 24 FCM 4.36 TB drives and six 100 Gbps Ethernet adapters draws 1095.2 W (3737 BTU/hr). Measurements belong to the sample conditions and must be tested in your own environment.

Operating conditions are 5-35 °C ambient, 0-3048 m altitude, 8-80% non-condensing relative humidity and 23 °C maximum wet bulb; above 950 m the maximum ambient temperature is derated 1 °C per 300 m. Air flows front to rear. The control enclosure is 88 mm high, 483 mm wide and 850 mm deep, and weighs 34.8 kg without drives and 40.1 kg fully configured. The minimum rail length is 670 mm and maximum rail depth 870 mm; 50 mm side and at least 100 mm rear clearance are required.

For expansion enclosures the 2U models use two 764 W PSUs and draw 151 W with 24 flash drives. The 5U 92-drive model (4657-92G) needs two 2400 W PSUs, 200-240 V and C19 PDUs; it draws 848 W with 92 10 TB nearline SAS drives and weighs 67 kg without drives and 135 kg fully loaded. A procedure for removing drives is therefore required when transporting the 5U enclosure.

Key points

  1. Control enclosure PSU: 2000 W, 200-240 V single phase, 10 A (x2), IEC C14; 6824 BTU/hr per PSU; two PSUs per enclosure.
  2. Example measurements: 1075.6 W (3670.1 BTU/hr) with 24 FCM 4.8 TB; 1095.2 W (3737 BTU/hr) with 24 FCM 4.36 TB and 100 Gbps Ethernet.
  3. Operating: 5-35 °C, 0-3048 m, 8-80% RH (non-condensing), maximum wet bulb 23 °C; derate 1 °C per 300 m above 950 m.
  4. Control enclosure 88 x 483 x 850 mm; 34.8 kg without drives, 40.1 kg fully configured.
  5. Rail requirement: minimum length 670 mm, maximum depth 870 mm; 50 mm side and 100 mm rear clearance.
  6. 2U expansion (4657-12G/24G): 764 W PSU, 151 W with 24 flash drives; 483 x 556 mm, 25.0 kg fully configured.
  7. 5U92 expansion (4657-92G): 2400 W PSU, C19 PDU; 848 W (92 x 10 TB nearline SAS); 968 mm deep, 135 kg fully loaded.
  8. The product is ENERGY STAR certified.

Using it in design

  • In the rack power budget use the 1076-1095 W examples as typical load of the control enclosure, read the 2000 W PSU rating as capacity and spread redundant PSUs across A/B feeds.
  • Compute heat load from the measured examples (3670-3737 BTU/hr); do not use the 6824 BTU/hr PSU upper value as typical load.
  • Choose the rack for depth (rails 670-870 mm, enclosure 850 mm) and the 50 mm side and 100 mm rear clearances.
  • For 5U92 expansion carry 200-240 V, C19 PDUs and the 135 kg loaded weight into cabinet and floor loading; add the transport procedure to the site plan.
  • At sites above 950 m derate the ambient upper limit by 1 °C per 300 m.

Who should read it

Storage engineers installing FlashSystem 7300 and data-centre designers planning power, cooling and rack layout.

Document contents

  1. FlashSystem 7300
  2. Notices
  3. System Overview
  4. Expansion Enclosures
  5. Planning for Hardware
  6. Installing
  7. Hardware Servicing

Publication details

Authors
IBM
Publisher
IBM
Year
Year not stated
Document number
Version 8.7.1 documentation path
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

IBM IBM Storage FlashSystem 7300 Hardware Guide. IBM. Version 8.7.1 documentation path. https://public.dhe.ibm.com/storage/EOS/flash_storwize/version87x/flashsystem7k-v871/hardware-guide/fs7300_pdfguide.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.