Technical guideFree to read2023

Green Data Centers: Towards a Sustainable Digital Transformation - A Practitioner's Guide

ITU and The World Bank · International Telecommunication Union (ITU), The World Bank et al.

The 2023 ITU and World Bank guide for public bodies that plan, regulate and procure data centres covers climate resilience plus five mitigation areas (design, ICT, energy, cooling, e-waste) and 30 cases.

On this page

Overview

The guide is written for public bodies in low- and middle-income countries that plan, regulate, procure or operate data centres, though its principles apply to any stakeholder. Its starting point is that data centres are energy intensive, consume refrigerants and often large amounts of water, and are exposed to climate hazards such as floods and rising temperatures. Greening is framed as a circular, lifecycle approach from design through to e-waste disposal.

The text is built around six dimensions: climate resilience, and five mitigation areas covering design and buildings, ICT equipment, energy, cooling and e-waste management. The climate section tabulates the effect of physical risks such as flooding and extreme heat. PUE is explained as total facility energy divided by IT energy; in the PUE 3.0 example, 2,700 kWh from the grid is needed to deliver 900 kWh to a server. The guide stresses that PUE should be assessed together with other metrics.

A large part is devoted to public procurement: core needs questions, green levers by data-centre model, lifecycle costs, and a table of standards, labels and certifications. Candidate criteria are listed for specifications, awards and contract performance clauses, for example a design PUE curve, demonstration of PUE at handover and monitoring of PUE input values.

The final section covers the enabling environment: policy framework, public services and utilities, skills, innovation and financing, and measurement, reporting and verification (MRV). Thirty country cases (such as Green Mountain in Norway, waste heat use in Odense and Busan's PUE of 1.39) and three appendices are included: industry standards, resiliency measures and mitigation measures. The guide is a public policy and procurement aid; it does not replace site-specific engineering calculation.

Key points

  1. Six dimensions: climate resilience plus five mitigation areas (design and buildings, ICT, energy, cooling, e-waste).
  2. The climate resilience section tabulates the effect of physical climate risks such as flooding and rising temperatures on data centres.
  3. PUE (ISO/IEC 30134-2) is total energy over IT energy; at PUE 3.0 the grid must supply 2,700 kWh for a server using 900 kWh.
  4. PUE should not be used alone; the IFC EDGE certification includes climate-dependent PUE targets.
  5. About 1 percent of the world's data-centre capacity is located in Africa.
  6. UPS efficiency of 96-97 percent is described as good and available; backup power should be neither oversized nor undersized.
  7. Candidate procurement criteria include design PUE curve, PUE at handover, monitoring of PUE input values, waste heat reuse readiness, renewable energy factor and refrigerant GWP.
  8. Cases: the Busan Global Cloud Data Center has an annual average PUE of 1.39 and a winter low of 1.15; Scala Data Centers reached PUE 1.5 with 100 percent certified renewable energy.
  9. Liquid cooling, closed-loop systems and free cooling are discussed as efficiency options; EN 50600 covers water, carbon and energy reuse metrics.
  10. The guide has 30 cases, 11 figures and 8 tables.

Using it in design

  • In public or corporate specifications, add design PUE curve, demonstration of PUE at handover and monitoring of PUE input values as contract performance clauses.
  • Do not make PUE the sole target; collect WUE, renewable energy factor, waste heat reuse readiness and refrigerant GWP in the same specification table.
  • At site selection, enter climate hazards such as flooding and extreme heat, and adaptation measures, in the risk table.
  • In UPS selection, check for 96-97 percent efficiency and avoid unnecessarily oversized redundant supplies.
  • Compare liquid cooling, closed-loop cooling and free cooling against local climate and water conditions.

Who should read it

Public bodies planning, regulating or procuring data-centre projects, consultants, and designers preparing green requirement sets.

Document contents

  1. Executive summary
  2. Why green data centers (context and dimensions)
  3. Climate resilience
  4. Sustainable design and buildings
  5. Sustainable ICT equipment
  6. Sustainable energy
  7. Sustainable cooling
  8. E-waste management
  9. Greening public procurement of data centers (planning and procuring)
  10. Greening the enabling environment (policy framework, public services and utilities, skills, innovation and financing, MRV)
  11. Appendix A: Standards and certifications
  12. Appendix B: Resiliency measures
  13. Appendix C: Mitigation measures

Related standards

  • ISO/IEC 30134-2
  • ITU-T L.1300

Publication details

Authors
International Telecommunication Union (ITU); The World Bank; Rosie McDonald; Sara Ballan
Publisher
ITU and The World Bank
Year
2023
Document number
ISBN 978-92-61-37491-4
Document language
English
Source type
Expert / community
Access
Free to read
Licence
CC BY-NC-SA 3.0: share with attribution for noncommercial purposes under the same licence
Original licence note

Copyright page: available under Creative Commons Attribution-NonCommercial-ShareAlike 3.0 IGO unless otherwise indicated.

Citation

International Telecommunication Union (ITU); The World Bank; Rosie McDonald; Sara Ballan (2023). Green Data Centers: Towards a Sustainable Digital Transformation - A Practitioner's Guide. ITU and The World Bank. ISBN 978-92-61-37491-4. https://documents1.worldbank.org/curated/en/099112923171023760/pdf/P17859700914e40f60869705b924ae2b4e1.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cost studies in SoSo CAD

Calculate equipment cost, energy cost and total cost of ownership (TCO) from the design’s quantities and your own price assumptions.

CAPEX and TCO estimates in the SoSo CAD cost workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.