NR1-S AI Inference Appliance (Product Brief, 2023)
Original title NeuReality NR1-S AI Inference Appliance Product Brief
NeuReality
NeuReality's 2023 NR1-S product brief: a 4U CPU-less AI inference appliance with 20 PCIe Gen5 x16 slots, 3.2 kW typical power in 2+2 redundancy and 5 fan modules.
On this page
Overview
The document is NeuReality's two-page product brief for the NR1-S AI inference appliance, dated December 2023. The NR1-S is presented as a server appliance without a host CPU, built on network addressable processing units (NR1 NAPU) and deep learning accelerators (DLA). The vendor argues that in conventional CPU-centric platforms data movement and processing run in software, which raises cost, latency and power consumption.
The specifications table gives a 4U, 19-inch rack-mount chassis. Twenty PCIe Gen5 x16 slots hold 10 NR1-M modules and 10 DLAs. Neural network processing is stated as 4-8 POPs, general-purpose processing as 80 Arm Neoverse N1 cores, plus 160 general-purpose DSP cores, 160 audio DSP cores and 40 video engines for 20K FPS at FHD. Networking is 400GbE-2TbE and storage is up to 10 x 3.84 TB E1.S.
For facility design the most useful rows are power and cooling: power is given as typical 3.2 kW in 2+2 redundancy, and cooling is 5 modules each with 2 x 60 x 60 mm dual-rotor fans. The vendor claims a 10x reduction in cost and power consumption and higher density in a 19-inch rack; the brief gives no measurement method or comparison conditions for this claim. It contains no airflow, maximum power, dimension or weight values.
Key points
- 4U, 19-inch rack-mount CPU-less AI inference appliance.
- 20 PCIe Gen5 x16 slots: 10 NR1-M modules and 10 DLAs.
- Typical power 3.2 kW in 2+2 redundancy mode.
- Cooling: 5 modules, each with 2 x 60 x 60 mm dual-rotor fans.
- Neural network processing 4-8 POPs; 80 Arm Neoverse N1 cores; 160 DSP and 160 audio DSP cores; 40 video engines (20K FPS, FHD).
- Networking 400GbE-2TbE; storage up to 10 x 3.84 TB E1.S.
- The vendor claims a 10x reduction in cost and power consumption against conventional platforms.
- Target markets include generative AI, large language models, medical imaging and fraud detection.
Using it in design
- Use the 3.2 kW typical value in the rack power budget together with the 2+2 PSU structure; request the maximum value from the vendor.
- Because the brief gives no airflow rate or inlet temperature limits, take them from the product manual; assess the noise of 5 fan modules in room layout.
- Plan in-cabinet cable management and optical/DAC reach limits for 400GbE-2TbE connections.
- Do not use the 10x density or power claims in rack count or energy savings calculations without validating them against your own workload.
- State in the configuration specification that power may change if the number of the 20 PCIe Gen5 x16 slots populated or the module mix changes.
Who should read it
Data-centre architects and capacity planners evaluating server platforms for AI inference.
Document contents
- Product Introduction
- Key Benefits
- Target Markets and AI Applications
- Specifications
Publication details
- Authors
- NeuReality
- Publisher
- NeuReality
- Year
- 2023
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
NeuReality (2023). NeuReality NR1-S AI Inference Appliance Product Brief. NeuReality. https://www.neureality.ai/wp-content/uploads/2023/12/PB-NR1-S.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.