CFD Modeling of Pressure Drop through an OCP Server for Data Center Applications
Energies (MDPI AG) · Aras Dogan, Sibel Yilmaz et al.
A reduced (compact) server model for room-level CFD: pressure-drop curves of a fully resolved Open Compute Project server in a virtual wind tunnel are fitted with Darcy-Forchheimer coefficients for a porous block that needs only about 0.3% of the cells.
CC BY 4.0: share with attribution
On this page
Overview
The study asks how to calculate quickly and accurately the turbulent pressure drop that internal components cause in servers in air-cooled data-centre simulations. A fully resolved Open Compute Project (OCP) server was run in OpenFOAM in a virtual wind tunnel (5.98 million cells, k-omega SST) over a range of airflows, with fans stationary (inactive) and with fans included (active). The tunnel inlet was 0.5 L upstream and the outlet L downstream of the server (L = server length), with 5% inlet turbulence intensity and slip side walls.
The fully resolved snappyHexMesh model had 5.98 million cells; the porous replacement used a 20,352-cell block mesh, about 0.3% of that. Twenty simulations were run for flow rates of 0.003 to 0.06 m³/s, and steady-state results matched time-averaged transient results. Fitted Darcy-Forchheimer coefficients were: inactive server D = 782,803.905 and F = 37.395; active server D = 715,633.617 and F = 24.788. The main pressure losses occur at the inlet, at the rear heat sink and at the fans/outlet, which gives the highest drop.
A literature approach assuming porosity 0.5 and hydraulic diameter 0.55 departed strongly from the resolved pressure-drop curve, so the choice of porosity coefficients drives accuracy. The porous-versus-complete uncertainty index was largest at low flow, 0.6699 (inactive) and 0.3725 (active) at 0.003 m³/s, and fell to 0.0451 (inactive) and 0.1329 (active) at 0.06 m³/s. The authors publish both the coefficients and the OpenFOAM cases.
Limits: the coefficients are specific to one OCP server design and must be re-derived for another server geometry; uncertainty of the porous model is high at low flow, and the study treats pressure drop only, with thermal modelling out of scope.
Key points
- The virtual wind tunnel inlet was 0.5 L upstream and the outlet L downstream of the server (L = server length), with 5% inlet turbulence intensity and slip side walls.
- The fully resolved snappyHexMesh model had 5.98 million cells; the porous replacement used a 20,352-cell block mesh, about 0.3% of that.
- Twenty simulations were run for flow rates of 0.003 to 0.06 m³/s, and steady-state results matched time-averaged transient results.
- Fitted Darcy-Forchheimer coefficients: inactive server D = 782,803.905 and F = 37.395; active server D = 715,633.617 and F = 24.788.
- A literature approach assuming porosity 0.5 and hydraulic diameter 0.55 departed strongly from the resolved pressure-drop curve, so the choice of porosity coefficients drives accuracy.
- Porous-versus-complete uncertainty index was largest at low flow, 0.6699 (inactive) and 0.3725 (active) at 0.003 m³/s, falling to 0.0451 (inactive) and 0.1329 (active) at 0.06 m³/s.
- The main pressure losses occur at the inlet, at the rear heat sink and at the fans/outlet, which gives the highest drop.
Using it in design
- When modelling a server as a porous block in room-scale CFD, use Darcy-Forchheimer coefficients fitted to a resolved pressure-drop curve rather than generic assumptions such as porosity 0.5.
- Use separate coefficients for servers with fans running (active) and stationary (inactive) (D = 715,633.617 and 782,803.905), and note that uncertainty is high at low flow.
- Cut server cell count to about 0.3% of the full geometry to make solving many servers in a room model practical.
Who should read it
Data-centre thermal engineers and researchers building server models for room-scale CFD.
Document contents
- 1. Introduction
- 2. Methods (2.1 Governing Equations, 2.2 Computational Domain, Boundary Conditions and Mesh, 2.3 Numerical Method)
- 3. Results (validation, time-averaging, inlet conditions)
- 4. Conclusions
Related standards
- OCP Open Rack
Read the document
ocp-server-pressure-drop-cfd-2022.pdf
CC BY 4.0: share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Aras Dogan; Sibel Yilmaz; Mustafa Kuzay; Cagatay Yilmaz; Ender Demirel
- Publisher
- Energies (MDPI AG)
- Year
- 2022
- Volume
- 15
- Issue
- 17
- Pages
- 6438
- Document language
- English
- Source type
- Scientific
- Access
- Open licence (downloadable)
- Licence
- CC BY 4.0: share with attribution
- Licence evidence
- www.mdpi.com
Original licence note
PDF p.1: Licensee MDPI; open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.
Citation
Aras Dogan; Sibel Yilmaz; Mustafa Kuzay; Cagatay Yilmaz; Ender Demirel (2022). CFD Modeling of Pressure Drop through an OCP Server for Data Center Applications. Energies (MDPI AG). 15(17), 6438. https://doi.org/10.3390/en15176438
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.