Research paperPDF2024

Numerical Evaluation of Hot Air Recirculation in Server Rack

Applied Sciences (MDPI AG) · Nelson Bafana Madihlaba, Thokozani Justin Kunene

A detailed Star-CCM+ model of a 2U Dell 2950 server built from a 3D scan studies how hot-aisle containment back pressure drives hot air back through the server, and the effect of adding four fans in series behind the original parallel fan set.

CC BY 4.0: share with attribution

On this page

Overview

In air-cooled data centres, hot-aisle containment prevents hot and cold air mixing but creates a pressure imbalance between cold and hot aisles, with the hot side high. That back pressure pushes against the server fan system, causing hot recirculation and insufficient cooling. The study examines whether series-configured fans can overcome the back pressure and eliminate recirculation. A three-grid GCI study (1.22 to 1.99 million cells) selected a 1,799,871-cell trimmed hexahedral mesh with seven prism layers, giving near-wall y+ of about 5.

Against published experiments, the CFD server inlet temperature under varying back pressure (about 20 °C supply, -0.15 to 0.02 inch w.c.) was within 5%, and chassis static pressure versus airflow was within 15%. Server inlet temperature begins to rise once back pressure reaches the fans' free-delivery point, and from there it rises roughly in proportion to back pressure. Four fans were added in series behind the original parallel fan set, and back pressures from -10 to 20 Pa were tested at a fixed 6800 rpm.

Series fans raised available system pressure against a 10 Pa hot-aisle back pressure but did not improve intake distribution; a dead zone persisted beside the drive bay. With series fans, server inlet temperature was higher than with the original parallel fans: about 5% higher from -20 to -5 Pa back pressure and 19% higher at free delivery (0 Pa), while outlet temperature fell by 1%. Series fans raise system pressure but do not remove recirculation, and inlet temperatures rise.

The authors conclude that fan sizing should follow component temperature needs rather than containment pressure. Limits: a single server model (Dell 2950 2U), a fixed 6800 rpm and a specific back-pressure range. The paper is useful mainly as evidence that pressure differences in a contained hot aisle feed back on server airflow.

Key points

  1. A three-grid GCI study (1.22 to 1.99 million cells) selected a 1,799,871-cell trimmed hexahedral mesh with seven prism layers, near-wall y+ of about 5.
  2. Against published experiments, CFD server inlet temperature under varying back pressure (about 20 °C supply, -0.15 to 0.02 inch w.c.) was within 5%, and chassis static pressure versus airflow within 15%.
  3. Server inlet temperature begins to rise once back pressure reaches the fans' free-delivery point, then rises roughly in proportion to back pressure.
  4. Adding fans in series raised available system pressure against a 10 Pa hot-aisle back pressure but did not improve intake distribution; a dead zone persisted beside the drive bay.
  5. With series fans, server inlet temperature was about 5% higher from -20 to -5 Pa back pressure and 19% higher at free delivery (0 Pa) than with the original parallel fans, while outlet temperature fell by 1%.

Using it in design

  • Make hot-aisle back pressure (hot-aisle pressure above cold aisle) a design input in contained aisles; server inlet temperature rises once back pressure reaches the fans' free-delivery point.
  • Do not assume adding series server fans fixes recirculation; system pressure rose but inlet temperature went up.
  • Size fans and hot-aisle pressure balance by component temperature needs, and consider relief or pressure control to limit hot-aisle pressure.

Who should read it

Cooling engineers and server designers studying hot-aisle containment pressure and server fan interaction.

Document contents

  1. 1. Introduction
  2. 2. Materials and Methods (2.1 Geometrical Configuration, 2.2 Fan)
  3. 3. Numerical Method (3.1 Governing Equations: SGS modeling, virtual; 3.2 Mesh Sensitivity Study; 3.3 Boundary Conditions and Model Validation Results; 3.4 Solver and Numerical Parameters)
  4. 4. Results and Discussion (4.2 Inlet Air Temperature, 4.3 Airflow Distribution: Fan Configuration)
  5. 5. Conclusions

Related standards

  • ASHRAE TC 9.9 Thermal Guidelines for Data Processing Environments

Read the document

server-rack-hot-air-recirculation-2024.pdf

PDF · 9.0 MB · English

CC BY 4.0: share with attribution

The document is provided unaltered because its licence permits redistribution.

Publication details

Authors
Nelson Bafana Madihlaba; Thokozani Justin Kunene
Publisher
Applied Sciences (MDPI AG)
Year
2024
Volume
14
Issue
17
Pages
7904
Document language
English
Source type
Scientific
Access
Open licence (downloadable)
Licence
CC BY 4.0: share with attribution
Licence evidence
www.mdpi.com
Original licence note

PDF p.1: Licensee MDPI; open access article distributed under the terms of the Creative Commons Attribution (CC BY) license. The deposited PDF contains overlapping review-layer text, and the abstract and conclusions report different headline percentages.

Citation

Nelson Bafana Madihlaba; Thokozani Justin Kunene (2024). Numerical Evaluation of Hot Air Recirculation in Server Rack. Applied Sciences (MDPI AG). 14(17), 7904. https://doi.org/10.3390/app14177904

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.