Technical guideFree to read2026

LA-ON33-V.10 Three-Phase Online UPS Datasheet

Original title Lapara LA-ON33-V.10 datasheet Rev.01 2026-08

Lapara

The August 2026 (Rev 01) technical datasheet for Lapara's tower-format, double-conversion three-phase online UPS series of 10, 20 and 30 kVA.

On this page

Overview

The series has three models: LA-ON33-10K, 20K and 30K-V.10 (10,000, 20,000 and 30,000 VA / W). It is a true double-conversion online design with output power factor 1, using silicon carbide diodes and DSP technology to improve efficiency. A dual input voltage system, adjustable charging current and parallel operation of up to 4 units with a common battery are supported; the display is a 5-inch colour touch LCD.

Input is 3 x 400 VAC (3F+N), with a voltage range of 190 to 520 VAC at 50% load and 305 to 478 VAC at 100% load. Input power factor is 0.99 or higher at full load. Output voltage is selectable at 360/380/400/415 VAC, battery-mode regulation is ±1%, and output THD is up to 2% on linear and 5% on non-linear loads. Mains-battery and inverter-bypass transfer times are 0 ms, and crest factor is 3:1 maximum. Efficiency is 96.0% in AC mode, 98.5% in ECO mode and 95.0% in battery mode.

Batteries: (10+10) 12 V 9 Ah units in the 10K model, (16+16) 12 V 9 Ah in the 20K and two strings of (16+16) 12 V 7 Ah in the 30K; recharge to 90% takes 9 hours and charging current is adjustable from 1 to 12 A. Weight is 124, 139 and 225 kg; noise is 55, 58 and 65 dBA at 1 m. Operation is 0 to 40 °C (battery life reduced above 25 °C) with humidity below 95%. Overload is given as 100% to 110% for 60 minutes, 110% to 125% for 10 minutes and above 150% for 1 second.

Key points

  1. Three models: 10, 20 and 30 kVA (kW), output power factor 1, up to 4 units in parallel.
  2. Efficiency: 96.0% in AC mode, 98.5% in ECO mode, 95.0% in battery mode.
  3. Input voltage range 190 to 520 VAC at 50% load, 305 to 478 VAC at 100% load; input power factor 0.99 or higher.
  4. Mains-battery and inverter-bypass transfer 0 ms; crest factor 3:1 max; output THD up to 2% linear and 5% non-linear.
  5. Overload: 100% to 110% for 60 min, 110% to 125% for 10 min, above 150% for 1 s.
  6. Batteries: 12 V 9 Ah (10K and 20K) and 12 V 7 Ah (30K); 9 hours to 90%; charging current 1 to 12 A.
  7. Weight 124, 139 and 225 kg; noise at 1 m 55, 58 and 65 dBA.
  8. Operation 0 to 40 °C, relative humidity below 95% non-condensing.

Using it in design

  • When using the 98.5% ECO mode efficiency, remember the load is fed through bypass in that mode and protection changes.
  • In small server rooms, consider up to 4 units in parallel for capacity growth; design the common battery arrangement separately.
  • Put noise (up to 65 dBA) and weight (up to 225 kg) into the layout and floor-loading assessment.
  • Use the wide input voltage window and 0.99 power factor in generator and input-protection design.
  • Calculate autonomy separately for the selected battery configuration and charging-current setting.

Who should read it

Electrical designers selecting tower UPS for small and mid-sized server rooms, industry and hospitals.

Document contents

  1. Key features
  2. Quick decision summary
  3. Technical specifications (input, output, efficiency, battery, indicators, alarm, physical characteristics, environmental conditions, management)

Publication details

Authors
Lapara
Publisher
Lapara
Year
2026
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Lapara (2026). Lapara LA-ON33-V.10 datasheet Rev.01 2026-08. Lapara. https://www.laparaups.com/en/?pdocs=view&doc=9670&lang=en

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.