LA-ON33-V.10 Three-Phase Online UPS Datasheet
Original title Lapara LA-ON33-V.10 datasheet Rev.01 2026-08
Lapara
The August 2026 (Rev 01) technical datasheet for Lapara's tower-format, double-conversion three-phase online UPS series of 10, 20 and 30 kVA.
On this page
Overview
The series has three models: LA-ON33-10K, 20K and 30K-V.10 (10,000, 20,000 and 30,000 VA / W). It is a true double-conversion online design with output power factor 1, using silicon carbide diodes and DSP technology to improve efficiency. A dual input voltage system, adjustable charging current and parallel operation of up to 4 units with a common battery are supported; the display is a 5-inch colour touch LCD.
Input is 3 x 400 VAC (3F+N), with a voltage range of 190 to 520 VAC at 50% load and 305 to 478 VAC at 100% load. Input power factor is 0.99 or higher at full load. Output voltage is selectable at 360/380/400/415 VAC, battery-mode regulation is ±1%, and output THD is up to 2% on linear and 5% on non-linear loads. Mains-battery and inverter-bypass transfer times are 0 ms, and crest factor is 3:1 maximum. Efficiency is 96.0% in AC mode, 98.5% in ECO mode and 95.0% in battery mode.
Batteries: (10+10) 12 V 9 Ah units in the 10K model, (16+16) 12 V 9 Ah in the 20K and two strings of (16+16) 12 V 7 Ah in the 30K; recharge to 90% takes 9 hours and charging current is adjustable from 1 to 12 A. Weight is 124, 139 and 225 kg; noise is 55, 58 and 65 dBA at 1 m. Operation is 0 to 40 °C (battery life reduced above 25 °C) with humidity below 95%. Overload is given as 100% to 110% for 60 minutes, 110% to 125% for 10 minutes and above 150% for 1 second.
Key points
- Three models: 10, 20 and 30 kVA (kW), output power factor 1, up to 4 units in parallel.
- Efficiency: 96.0% in AC mode, 98.5% in ECO mode, 95.0% in battery mode.
- Input voltage range 190 to 520 VAC at 50% load, 305 to 478 VAC at 100% load; input power factor 0.99 or higher.
- Mains-battery and inverter-bypass transfer 0 ms; crest factor 3:1 max; output THD up to 2% linear and 5% non-linear.
- Overload: 100% to 110% for 60 min, 110% to 125% for 10 min, above 150% for 1 s.
- Batteries: 12 V 9 Ah (10K and 20K) and 12 V 7 Ah (30K); 9 hours to 90%; charging current 1 to 12 A.
- Weight 124, 139 and 225 kg; noise at 1 m 55, 58 and 65 dBA.
- Operation 0 to 40 °C, relative humidity below 95% non-condensing.
Using it in design
- When using the 98.5% ECO mode efficiency, remember the load is fed through bypass in that mode and protection changes.
- In small server rooms, consider up to 4 units in parallel for capacity growth; design the common battery arrangement separately.
- Put noise (up to 65 dBA) and weight (up to 225 kg) into the layout and floor-loading assessment.
- Use the wide input voltage window and 0.99 power factor in generator and input-protection design.
- Calculate autonomy separately for the selected battery configuration and charging-current setting.
Who should read it
Electrical designers selecting tower UPS for small and mid-sized server rooms, industry and hospitals.
Document contents
- Key features
- Quick decision summary
- Technical specifications (input, output, efficiency, battery, indicators, alarm, physical characteristics, environmental conditions, management)
Publication details
- Authors
- Lapara
- Publisher
- Lapara
- Year
- 2026
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Lapara (2026). Lapara LA-ON33-V.10 datasheet Rev.01 2026-08. Lapara. https://www.laparaups.com/en/?pdocs=view&doc=9670&lang=en
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.