Lapara LA-ON3113-V.10 configurable three-phase UPS technical table
Lapara
Lapara's LA-ON3113-V.10 series: 10 kVA/10 kW and 20 kVA/20 kW three-phase double-conversion UPS, configurable 3:3 or 3:1, 98.5% efficient in ECO mode, up to four units in parallel.
On this page
Overview
The page presents LA-ON3113-10K-LCD-V10 (10 kVA / 10 kW) and LA-ON3113-20K-LCD-V10 (20 kVA / 20 kW). The series is a DSP-controlled true double-conversion UPS with three-phase input and output and output power factor 1 for industrial applications. It is configurable 3:3 or 3:1, uses silicon carbide diodes to raise system efficiency, has a dual input voltage system, a 5-inch colour touchscreen LCD and an optional maintenance bypass.
On the input side the low line-loss threshold (phase-neutral) is 110 Vac at 50% load and 176 Vac at full load (+/-3%); the high threshold is 300 Vac at 50% load and 276 Vac at full load (phase-neutral). Frequency range is 46-54 Hz on a 50 Hz system and 56-64 Hz on a 60 Hz system, and input power factor is 0.99 or higher at full load. Output voltage is 360/380/400/415 Vac (phase-phase) or 208/220/230/240 Vac (phase-neutral), regulation +/-1%, harmonic distortion 2% or less on linear and 5% or less on non-linear load.
Overload capability, in both AC and battery mode, is 60 minutes at 100-110%, 10 minutes at 110-125%, 1 minute at 125-150% and immediate above 150%. Efficiency is 95.5% in AC mode, 98.5% in ECO mode and 94.5% in battery mode. Mains-battery transfer is 0 ms; inverter-bypass transfer is 0 ms, but if phase lock fails an interruption under 4 ms occurs. Inverter-ECO transfer is under 10 ms. Crest ratio is at most 3:1.
In the standard model the battery is 12 V 9 Ah, (10+10) pieces for 10K and (20+20) for 20K, with 9 hours to recover 90% capacity. In the long-term model the battery depends on the application, 20 or 32-40 pieces adjustable, with charge current adjustable from 1 to 12 A. The standard model measures 626 x 250 x 826 mm and weighs 126 kg (10K) and 141 kg (20K); the long-term model uses the same case and weighs 30 kg and 45 kg without batteries. Noise is below 58 dB (10K) and 60 dB (20K) at 1 m, and altitude is below 1000 m.
Key points
- Models: LA-ON3113-10K-LCD-V10 (10 kVA / 10 kW) and LA-ON3113-20K-LCD-V10 (20 kVA / 20 kW).
- Configurable 3:3 or 3:1; up to four units in parallel on a common battery.
- Input: low line-loss threshold 110 Vac (50% load) and 176 Vac (full load), phase-neutral; power factor 0.99 or higher.
- Output 360/380/400/415 Vac (phase-phase) or 208-240 Vac (phase-neutral); regulation +/-1%.
- Efficiency: 95.5% in AC mode, 98.5% in ECO mode, 94.5% in battery mode.
- Overload: 60 min at 100-110%, 10 min at 110-125%, 1 min at 125-150%.
- Inverter-bypass transfer 0 ms; under 4 ms interruption if phase lock fails.
- Standard battery 12 V 9 Ah (10+10) and (20+20); 90% recharge in 9 hours.
- Size 626 x 250 x 826 mm; weight 126 kg and 141 kg (standard), 30 kg and 45 kg without batteries (long-term).
- Noise below 58 dB (10K) and 60 dB (20K) at 1 m.
Using it in design
- Define 3:3 or 3:1 configuration from the supply and load phase arrangement and write it into the order specification.
- If load growth is expected, plan up to four parallel units on a common battery and verify parallel redundancy separately.
- On the long-term model set the battery count within 32-40 and the charge current to the battery capacity.
- Assess the under-4 ms bypass interruption when phase lock fails for sensitive loads.
- Carry the 126-141 kg weight of the standard model into floor loading and layout.
Who should read it
Electrical designers choosing 10-20 kW three-phase UPS for industrial and small facility applications.
Document contents
- Features
- Description
- Technical datasheet (input, output, efficiency, battery, physical, environment, management)
- Documentation
Publication details
- Authors
- Lapara
- Publisher
- Lapara
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Lapara Lapara LA-ON3113-V.10 configurable three-phase UPS technical table. Lapara. https://www.laparaups.com/en/la-on3113-v-10-series-three-phase-online-ups/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.