Lapara LA-ON-LCD 6-10 kVA UPS technical specifications

Original title Lapara LA-ON-LCD 6–10 kVA technical specifications

Lapara

The 6 kVA/6 kW and 10 kVA/10 kW models of Lapara's LA-ON-LCD-V.10 series: single-phase, true double-conversion UPS with unity power factor, efficiency above 94% in AC mode and N+X parallel redundancy.

On this page

Overview

Lapara's product page presents two models for critical medium and high power applications: LA-ON-6K-LCD-V10 (6000 VA / 6000 W) and LA-ON-10K-LCD-V10 (10000 VA / 10000 W). They are single-phase, true double-conversion, DSP-controlled UPS units with output power factor 1. The listed features include a 50/60 Hz frequency converter mode, EPO, generator compatibility and N+X parallel redundancy.

On the input side nominal voltage is 208/220/230/240 Vac, with an operating range of 110-300 Vac at 50% load and 176-300 Vac at full load (+/-3%). Input power factor is 0.99 or higher at nominal voltage and full load. Output voltage is programmable at 208/220/230/240 Vac, battery-mode regulation is 1%, THD is 1% or less on linear load and 4% or less on non-linear load, and crest factor is at most 3:1. Mains-battery and inverter-bypass transfers are given as 0 ms.

Efficiency is above 94% in AC mode and above 91% in battery mode. Overload in AC mode is 10 minutes at 100-110%, 1 minute at 110-130% and 1 second above 130%; in battery mode it is 30, 10 and 1 seconds. The standard battery is 20 units of 12 V 7 Ah or 9 Ah; charging current is up to 4 A +/-10%, adjustable from the LCD panel. Battery quantity is adjustable and hot standby is supported.

Physical data give 592 x 250 x 576 mm (D x W x H) and net weight of 66.5 kg (6K) and 83 kg (10K). Operating temperature is 0-40 C and humidity 20-95% non-condensing; battery life shortens above 25 C. Communication is via USB and RS-232, with optional SNMP, ModBus and AS400. The page is a published catalogue for the two models and carries no runtime curve.

Key points

  1. Models: LA-ON-6K-LCD-V10 (6 kVA / 6 kW) and LA-ON-10K-LCD-V10 (10 kVA / 10 kW).
  2. Input range: 110-300 Vac at 50% load, 176-300 Vac at full load; input power factor 0.99 or higher.
  3. Output voltage programmable at 208/220/230/240 Vac; 1% regulation in battery mode.
  4. Output THD: 1% or less on linear load, 4% or less on non-linear load; crest factor 3:1.
  5. Efficiency: above 94% in AC mode, above 91% in battery mode.
  6. Overload in AC mode: 10 min at 100-110%, 1 min at 110-130%, 1 s above 130%.
  7. Battery 20 units of 12 V 7 Ah or 9 Ah; charge current up to 4 A.
  8. Size 592 x 250 x 576 mm; weight 66.5 kg (6K) and 83 kg (10K).
  9. Operation 0-40 C; N+X parallel redundancy and hot standby supported.

Using it in design

  • Compare the load in kW directly with the model kW rating; with output power factor 1, kVA and kW are equal.
  • Where mains voltage can sag, check the load-dependent lower input limit (110 and 176 Vac).
  • If parallel redundancy is required, specify the N+X option and calculate each unit's battery arrangement separately.
  • If ambient may exceed 25 C, reflect the reduced battery life in the maintenance plan.
  • For runtime, use a calculation with your own load and an external battery bank, not the standard 20-battery configuration on this page.

Who should read it

Electrical designers selecting single-phase double-conversion UPS for small and medium critical loads.

Document contents

  1. Features
  2. Technical datasheet (input, output, efficiency, battery, indicators, physical, environment, software)
  3. Documentation

Publication details

Authors
Lapara
Publisher
Lapara
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Lapara Lapara LA-ON-LCD 6–10 kVA technical specifications. Lapara. https://www.laparaups.com/en/online-ups-la-on-lcd-6-10k-lcd-v-10/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.