Lapara's product page presents two models for critical medium and high power applications: LA-ON-6K-LCD-V10 (6000 VA / 6000 W) and LA-ON-10K-LCD-V10 (10000 VA / 10000 W). They are single-phase, true double-conversion, DSP-controlled UPS units with output power factor 1. The listed features include a 50/60 Hz frequency converter mode, EPO, generator compatibility and N+X parallel redundancy.
On the input side nominal voltage is 208/220/230/240 Vac, with an operating range of 110-300 Vac at 50% load and 176-300 Vac at full load (+/-3%). Input power factor is 0.99 or higher at nominal voltage and full load. Output voltage is programmable at 208/220/230/240 Vac, battery-mode regulation is 1%, THD is 1% or less on linear load and 4% or less on non-linear load, and crest factor is at most 3:1. Mains-battery and inverter-bypass transfers are given as 0 ms.
Efficiency is above 94% in AC mode and above 91% in battery mode. Overload in AC mode is 10 minutes at 100-110%, 1 minute at 110-130% and 1 second above 130%; in battery mode it is 30, 10 and 1 seconds. The standard battery is 20 units of 12 V 7 Ah or 9 Ah; charging current is up to 4 A +/-10%, adjustable from the LCD panel. Battery quantity is adjustable and hot standby is supported.
Physical data give 592 x 250 x 576 mm (D x W x H) and net weight of 66.5 kg (6K) and 83 kg (10K). Operating temperature is 0-40 C and humidity 20-95% non-condensing; battery life shortens above 25 C. Communication is via USB and RS-232, with optional SNMP, ModBus and AS400. The page is a published catalogue for the two models and carries no runtime curve.
Key points
- Models: LA-ON-6K-LCD-V10 (6 kVA / 6 kW) and LA-ON-10K-LCD-V10 (10 kVA / 10 kW).
- Input range: 110-300 Vac at 50% load, 176-300 Vac at full load; input power factor 0.99 or higher.
- Output voltage programmable at 208/220/230/240 Vac; 1% regulation in battery mode.
- Output THD: 1% or less on linear load, 4% or less on non-linear load; crest factor 3:1.
- Efficiency: above 94% in AC mode, above 91% in battery mode.
- Overload in AC mode: 10 min at 100-110%, 1 min at 110-130%, 1 s above 130%.
- Battery 20 units of 12 V 7 Ah or 9 Ah; charge current up to 4 A.
- Size 592 x 250 x 576 mm; weight 66.5 kg (6K) and 83 kg (10K).
- Operation 0-40 C; N+X parallel redundancy and hot standby supported.
Using it in design
- Compare the load in kW directly with the model kW rating; with output power factor 1, kVA and kW are equal.
- Where mains voltage can sag, check the load-dependent lower input limit (110 and 176 Vac).
- If parallel redundancy is required, specify the N+X option and calculate each unit's battery arrangement separately.
- If ambient may exceed 25 C, reflect the reduced battery life in the maintenance plan.
- For runtime, use a calculation with your own load and an external battery bank, not the standard 20-battery configuration on this page.
Who should read it
Electrical designers selecting single-phase double-conversion UPS for small and medium critical loads.
Document contents
- Features
- Technical datasheet (input, output, efficiency, battery, indicators, physical, environment, software)
- Documentation
Publication details
- Authors
- Lapara
- Publisher
- Lapara
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Lapara Lapara LA-ON-LCD 6–10 kVA technical specifications. Lapara. https://www.laparaups.com/en/online-ups-la-on-lcd-6-10k-lcd-v-10/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.