Lapara LA-ON-LCD-V.10 UPS technical specifications
Original title Lapara LA-ON-LCD-V.10 technical specifications
Lapara
Lapara's LA-ON-LCD-V.10 series gives 1, 2 and 3 kVA models: single-phase true double-conversion UPS with output power factor 1, a wide 110-300 V input range and an optional 96% efficient ECO mode.
On this page
Overview
The page covers the LA-ON-1K, 2K and 3K-LCD-V.10 models: 1000 VA/1000 W, 2000 VA/2000 W and 3000 VA/3000 W respectively. The series is a microprocessor-controlled true double-conversion on-line UPS with output power factor 1, input power factor correction, a wide 110-300 V input range, optional ECO mode, EPO, built-in surge protection and a charger of up to 1000 W with low ripple.
On the input side the low-mains transfer thresholds vary with load: 160, 140, 120 and 110 Vac (or 80, 70, 60 and 55 Vac) across roughly 100-80%, 80-70%, 70-60% and below 60% load; high-voltage transfer is 300 Vac (or 150 Vac) +/-5%. Frequency range is 40-70 Hz, input power factor 0.99 or higher, and THDi 5% or less at 205-245 Vac. Output voltage is 200/208/220/230/240 Vac or 100/110/115/120/127 Vac, battery-mode regulation 1%, THD 2% on linear and 4% on non-linear load, crest factor 3:1.
Efficiency in AC mode is 89% for 1K and 91% for 2K and 3K; in ECO mode 96%; in battery mode at least 88%, 90% and 90% respectively. Transfer from AC to battery mode is zero and inverter-to-bypass is 4 ms. The battery is 12 V type: 3 x 7 Ah for 1K, 6 x 7 Ah for 2K and 6 x 9 Ah for 3K; typical recharge is 3 hours to 95% at 2 A. On 100-127 V models charge current defaults to 2 A and adjusts up to 8 A; on 200-240 V models up to 12 A.
Outputs are 4 x C13 (1K), 8 x C13 (2K) and 8 x C13 plus 1 x C19 (3K); communication uses USB, RS-232 and an SNMP slot. Dimensions are 397 x 145 x 220 mm and 421 x 190 x 318 mm (D x W x H; the page lists two case sizes), weight with batteries 12.9, 22.8 and 27.0 kg, and without batteries 6.6, 9.9 and 12.3 kg. The page is the datasheet of the three tower models only.
Key points
- Models: LA-ON-1K, 2K, 3K-LCD-V.10; 1, 2 and 3 kVA, kVA = kW in each.
- Input: 40-70 Hz, power factor 0.99 or higher, THDi 5% or less at 205-245 Vac.
- High-mains transfer threshold 300 Vac (or 150 Vac) +/-5%.
- Output voltage 200-240 Vac or 100-127 Vac; battery-mode regulation 1%; crest factor 3:1.
- Efficiency 89% (1K) and 91% (2K, 3K) in AC mode; 96% in ECO mode; at least 88-90% in battery mode.
- Transfer: AC to battery zero, inverter to bypass 4 ms.
- Battery: 1K 3 x 12 V 7 Ah, 2K 6 x 12 V 7 Ah, 3K 6 x 12 V 9 Ah; 3 hours to 95% at 2 A.
- Charge current 2 A default; up to 8 A on 100-127 V models, up to 12 A on 200-240 V models.
- Weight with batteries 12.9 / 22.8 / 27.0 kg; without 6.6 / 9.9 / 12.3 kg.
- Outlets: 4 x C13, 8 x C13, 8 x C13 + 1 x C19.
Using it in design
- Compare the load in kW with the model kW rating; with power factor 1, kVA is not the limiting figure.
- If you enable ECO mode, assess how its protection differs from double conversion and the load's sensitivity.
- Take the 4 ms inverter-to-bypass transfer into account for loads that are very sensitive to interruptions.
- Match the C13 and C19 outlet split to the load connections.
- The standard 3 to 6 battery configuration is for short backup; do the battery calculation separately for long runtime.
Who should read it
Designers and IT managers choosing tower single-phase UPS for small offices, network rooms and edge loads.
Document contents
- Features
- Technical datasheet (input, output, efficiency, battery, connections, physical, environment, software)
- Documentation
Publication details
- Authors
- Lapara
- Publisher
- Lapara
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Lapara Lapara LA-ON-LCD-V.10 technical specifications. Lapara. https://www.laparaups.com/en/online-ups-la-on-lcd-v-10/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.