Lapara LA-ON-RACK 6-10 kVA UPS technical specifications

Original title Lapara LA-ON-RACK 6–10 kVA technical specifications

Lapara

The 6 kVA/6 kW and 10 kVA/10 kW models of Lapara's LA-ON-RACK-V.10 series: 2U rack-mount, true double-conversion, unity power factor single-phase UPS ready for external battery banks.

On this page

Overview

The product page presents two high-capacity, highly protected rack models: LA-ON-6K-RACK-V.10 and LA-ON-10K-RACK-V.10 (6000 VA / 6000 W and 10000 VA / 10000 W). Features include true double conversion, DSP control, output power factor 1, efficiency up to 94%, active input power factor correction (0.99), a 50/60 Hz frequency converter mode, EPO, generator compatibility, programmable ECO mode, optional N+X parallel redundancy and optional OVCD protection.

On the input side the line-loss threshold depends on load: 110-300 Vac (0-60% load), 140-300 Vac (60-80%) and 176-300 Vac (80-100%); recovery thresholds are the low threshold plus 10 V and the high threshold minus 10 V. Input frequency is programmable at 46-54 Hz (50 Hz) or 56-64 Hz (60 Hz) and power factor is 0.99 or higher at nominal voltage and full load. Output voltage is programmable at 208/220/230/240 Vac, battery-mode regulation +/-1%, THD 1% on linear and 4% on non-linear load, crest factor 3:1, and transfer times 0 ms.

Efficiency exceeds 94% in both AC and ECO mode. The battery is 20 units of 12 V 7 Ah or 9 Ah; charging current is up to 1 A +/-10%; typical recharge is 7 hours (7 Ah) and 9 hours (9 Ah) to 90% capacity. The UPS measures 600 x 438 x 88 mm (2U) and weighs 13.5 kg (6K) and 16 kg (10K); the separate battery bank is 600 x 438 x 138 mm (3U) at 55 kg and 63 kg.

Operating environment, indicators, alarm codes and communication (USB, RS-232, optional SNMP) are listed on the page. The document is the product datasheet of the two models and has no runtime curve; runtime must be calculated separately for the external battery bank used.

Key points

  1. Models: LA-ON-6K-RACK-V.10 (6 kVA / 6 kW) and LA-ON-10K-RACK-V.10 (10 kVA / 10 kW).
  2. Line-loss threshold: 110-300 Vac (0-60% load), 140-300 Vac (60-80%), 176-300 Vac (80-100%).
  3. Input power factor 0.99 or higher; output voltage programmable at 208/220/230/240 Vac, regulation +/-1%.
  4. Output THD: 1% on linear, 4% on non-linear load; crest factor 3:1.
  5. Efficiency above 94% in AC and ECO mode; transfer times 0 ms.
  6. Battery 20 units of 12 V 7 Ah or 9 Ah; charge current up to 1 A; 90% recharge in 7 hours (7 Ah) and 9 hours (9 Ah).
  7. UPS 600 x 438 x 88 mm (2U), 13.5 kg and 16 kg; battery bank 600 x 438 x 138 mm (3U), 55 kg and 63 kg.
  8. Optional N+X parallel redundancy and OVCD protection.

Using it in design

  • Reserve 2U for the UPS and 3U for each battery bank in the rack, and compare total weight with the rack's load capacity (13.5-16 kg UPS, 55-63 kg battery bank).
  • In sites with a risk of low mains voltage, check the load-dependent line-loss threshold.
  • Charge current is only 1 A, so plan the recharge time of any long-runtime battery bank.
  • State the N+X and OVCD options separately in the order specification when parallel redundancy is needed.
  • Calculate runtime from the load and the external battery bank, not from the 7 Ah or 9 Ah block capacity.

Who should read it

Electrical and IT infrastructure designers selecting single-phase double-conversion UPS to install in a 19-inch rack.

Document contents

  1. Features
  2. Description
  3. Technical datasheet (input, output, efficiency, battery, indicators, alarms, physical, environment, software)
  4. Documentation

Publication details

Authors
Lapara
Publisher
Lapara
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Lapara Lapara LA-ON-RACK 6–10 kVA technical specifications. Lapara. https://www.laparaups.com/en/la-on-6-10k-rack-series-online-ups/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.