Lapara LA-ON-RACK-V.10 UPS technical specifications
Original title Lapara LA-ON-RACK-V.10 technical specifications
Lapara
Lapara's LA-ON-RACK-V.10 series gives 1, 2 and 3 kVA models: 2U rack-mount, single-phase true double-conversion UPS with output power factor 1, programmable ECO mode (96%) and hot-swappable batteries.
On this page
Overview
The page covers the LA-ON-1K, 2K and 3K-RACK-V.10 models: 1000, 2000 and 3000 VA, at 1000, 2000 and 3000 W. The series is true double conversion with output power factor 1, ready for external battery banks, with charge current set from the LCD panel, output regulation of 1% or better, crest factor 3:1 and programmable output sockets. Batteries are hot-swappable, and EPO, programmable ECO mode and overvoltage cut-off protection are provided.
Input voltage depends on the EU or USA version: 110-300 Vac +/-5% or 55-150 Vac +/-5%. Low-mains return thresholds by load are 175, 155, 135 and 125 Vac (or 87, 77, 67 and 62 Vac), and high-voltage return is 290 Vac (or 145 Vac). Frequency range is 40-70 Hz, power factor 0.99 or higher, THDi 5% or less at 205-245 Vac. Output voltage is 200-240 Vac or 100-127 Vac, with THD of 2% on linear and 4% on non-linear load.
Efficiency in AC mode is 89% for 1K and 91% for 2K and 3K; in ECO mode 96%; in battery mode at least 88%, 90% and 90%. AC-to-battery transfer is zero and inverter-to-bypass is 4 ms. The battery is 12 V 9 Ah: 2 units for 1K, 4 for 2K and 6 for 3K, with charge voltage of 27.4, 54.7 and 82.1 Vdc. On 100-127 V models charge current defaults to 2 A, up to 8 A; on 200-240 V models up to 12 A.
Dimensions are 410, 510 and 630 mm deep, 438 mm wide and 88 mm (2U) high. Weight with batteries is 13.4, 19.8 and 27.5 kg and without batteries 6.6, 9.4 and 12.4 kg. The page is the published datasheet of these three rack models and has no runtime curve.
Key points
- Models: LA-ON-1K, 2K, 3K-RACK-V.10; 1, 2 and 3 kVA, kVA = kW.
- Input voltage 110-300 Vac +/-5% (EU) or 55-150 Vac +/-5% (USA version); frequency 40-70 Hz.
- Input power factor 0.99 or higher; THDi 5% or less at 205-245 Vac.
- Output 200-240 Vac or 100-127 Vac; battery-mode regulation +/-1%; crest factor 3:1.
- Efficiency 89% (1K) and 91% (2K, 3K) in AC mode; 96% in ECO mode; at least 88-90% in battery mode.
- Transfer: AC to battery zero, inverter to bypass 4 ms.
- Battery 12 V 9 Ah: 2, 4 and 6 units; charge voltage 27.4, 54.7 and 82.1 Vdc.
- Size D 410, 510, 630 x W 438 x H 88 mm (2U).
- Weight with batteries 13.4 / 19.8 / 27.5 kg; without 6.6 / 9.4 / 12.4 kg.
Using it in design
- Reserve 2U in the rack and match the model depth (410-630 mm) to rack depth and rails.
- Order the input-voltage version (EU or USA) to suit the mains voltage.
- Use the programmable sockets to shed non-critical loads first in battery mode and extend runtime.
- If you use ECO mode, assess how its protection differs from double conversion against the load's sensitivity.
- Calculate an external battery bank and charge-current setting separately for long backup.
Who should read it
IT infrastructure designers placing small UPS units in network and server racks.
Document contents
- Features
- Technical datasheet (input, output, efficiency, battery, indicators, connections, physical, environment, software)
- Documentation
Publication details
- Authors
- Lapara
- Publisher
- Lapara
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Lapara Lapara LA-ON-RACK-V.10 technical specifications. Lapara. https://www.laparaups.com/en/sai-online-la-on-rack-v-10/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.