Technical guideFree to read2026

LA-ON33-MOD Modular Three-Phase UPS Datasheet

Original title Lapara LA-ON33-MOD datasheet Rev.01 2026-07

Lapara

The technical datasheet (Rev 01, July 2026) for Lapara's modular three-phase double-conversion UPS series of 90 and 120 kVA, built from 30 kW power modules with N+1 redundancy.

On this page

Overview

The series comes in a 19-inch rack format with two models: LA-ON33-90K-MOD (90,000 VA / 90,000 W) and LA-ON33-120K-MOD (120,000 VA / 120,000 W). The power module PM-30HV is 30 kVA / 30 kW; the 90 kVA model takes up to 3 modules and 3 battery modules, and the 120 kVA model up to 4 power modules and 5 battery modules. Output power factor is 1 (kVA = kW). The datasheet states that N+1 and N+X parallel redundancy is provided in the same rack.

Input is 3 x 380/400/415 VAC (3F+N), with a voltage range of 305 to 478 VAC at full load and 208 to 304 VAC below 70% load. Input power factor is above 0.99 at full load and above 0.98 at half load; input current THD is below 3% at full load. Output regulation is typically ±1% on balanced load and ±2% on imbalanced load. Overload capability is 110% for 1 hour, 125% for 10 minutes, 150% for 1 minute and above 150% for 200 ms. Efficiency is above 94.5%.

The battery section uses rack-integrated modules: nominal ±216 V (12 V x 36), strings of 32 to 40 units, charging voltage of 2.25 V per cell (float) and 2.35 V (boost), temperature compensation and up to 8 A charging current per power module. A battery module holds ten 12 V 9 Ah batteries. Cabinets measure 1100 x 600 x 1475 mm (675 kg) and 1100 x 600 x 2010 mm (932 kg); operating temperature is 0 to 40 °C (battery life reduced above 25 °C), IP 20, altitude below 1000 m with 1% derating per 100 m above. Standards are IEC/EN 62040-1 and 62040-2 (C3) and IEC/EN 60950-1.

Key points

  1. Power module is 30 kVA / 30 kW; up to 3 modules in the 90 kVA model and 4 in the 120 kVA model.
  2. Output power factor 1; N+1 / N+X parallel redundancy in the same rack.
  3. Input voltage range 305 to 478 VAC at full load, 208 to 304 VAC below 70% load; input THDi below 3% at full load.
  4. Overload: 110% for 1 hour, 125% for 10 min, 150% for 1 min, above 150% for 200 ms.
  5. Efficiency above 94.5%; output THD up to 2% on linear and 4% on non-linear load.
  6. Battery: rack-integrated modules, nominal ±216 V, strings of 32 to 40, charging current up to 8 A per power module.
  7. Cabinet weight 675 kg (90 kVA) and 932 kg (120 kVA); size 1100 x 600 x 1475 / 2010 mm.
  8. Operation: 0 to 40 °C, relative humidity below 95% non-condensing, 1% derating per 100 m above 1000 m.

Using it in design

  • Choose the module count from the redundancy target: for N+1 the load must be carried with one module missing.
  • Compare cabinet weight (675 and 932 kg) with floor loading and raised-floor or slab load distribution.
  • Keep ambient below 25 °C to protect battery life, and check proximity to the hot aisle.
  • Assess input protection and generator compatibility from the wide voltage window and the THDi below 3% value.
  • Compare the efficiency above 94.5% against higher-efficiency alternatives on annual energy cost.

Who should read it

Electrical designers and specification engineers choosing modular UPS for mid-sized data centres, industry and hospitals.

Document contents

  1. Key features
  2. Quick decision summary
  3. Technical specifications (input, output, battery charger, system modules, physical data, working environment, management software, standards)

Publication details

Authors
Lapara
Publisher
Lapara
Year
2026
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Lapara (2026). Lapara LA-ON33-MOD datasheet Rev.01 2026-07. Lapara. https://www.laparaups.com/en/?pdocs=view&doc=10090&lang=en

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.