Rebellions RebelServer Product Brief v1.8

Rebellions

The Rebellions RebelServer brief describes a 5U, 8-RebelCard inference server for existing air-cooled halls, with 4-6 kW typical and 7 kW theoretical maximum power and six 2700 W PSUs.

On this page

Overview

RebelServer is the AI compute building block of Rebellions' integrated hardware and software inference solution. The brief presents it on four pillars: sovereign AI (deploying in existing air-cooled data centres without additional power or cooling), ease of use, price-performance-per-watt for inference workloads, and production proof. It states that hundreds of racks are deployed with enterprise and government customers.

The spec table gives a 5U form factor (8 RebelCards), 2 AMD EPYC 9355 CPUs, 1.5 TB DDR5 memory (24 x 64 GB), 2 x 1.92 TB NVMe disks and network interfaces (4 x 400G, 1 x 100G, 1 x 10G/25G). Each RebelCard holds one Rebel100 chip and 144 GB HBM3E; the server reports 1 petaFLOPS FP16 and 2 petaFLOPS FP8.

Power is given as 4-6 kW typical and 7 kW theoretical maximum; the footnote says actual consumption will not exceed 7 kW and typically hovers around 4-6 kW under practical workloads. The power supply is six 2700 W units, which is supply capacity, not a consumption value. Operating temperature is 10-35 °C and relative humidity 8-90% non-condensing; gross weight is 45.3 kg and net 29.7 kg; 3-year standard support is included. The document is a manufacturer product brief; for rack placement and supply planning, typical, maximum and PSU capacity should be treated as separate rows.

Key points

  1. The form factor is 5U with 8 RebelCards; each card has one Rebel100 chip and 144 GB HBM3E.
  2. Power is 4-6 kW typical and 7 kW theoretical maximum; actual consumption is stated not to exceed 7 kW.
  3. The six 2700 W power supply capacity cannot be used as a consumption value.
  4. CPU is 2 x AMD EPYC 9355 (32C/64T, 280 W) and memory is 1.5 TB DDR5.
  5. Network: 4 x 400G QSFP112-DD, 1 x 100G 2-port QSFP56, 1 x 10G/25G 2-port SFP28 (OCP 3.0).
  6. Throughput is 1 petaFLOPS FP16 and 2 petaFLOPS FP8.
  7. Operating temperature is 10-35 °C and relative humidity 8-90% non-condensing.
  8. Gross weight is 45.3 kg (100 lb) and net weight is 29.7 kg (65.6 lb).

Using it in design

  • Base the rack power budget on 4-6 kW typical and 7 kW maximum; do not take the 6 x 2700 W PSU capacity as consumption.
  • In existing air-cooled halls, check cabinet inlet temperature against the 10-35 °C operating range.
  • Add the 5U height and 45.3 kg gross weight to the rack loading and installation plan.
  • Include 4 x 400G, 1 x 100G and 1 x 10G/25G interface counts in the network port plan.

Who should read it

Facility and infrastructure engineers planning rack power, cooling and network for inference servers.

Document contents

  1. Four pillars (sovereign AI, ease of use, production tokenomics, production-proven)
  2. Specifications
  3. Performance and efficiency
  4. Ease of use and software stack

Publication details

Authors
Rebellions
Publisher
Rebellions
Year
2026
Document number
v1.8
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Rebellions (2026). Rebellions RebelServer Product Brief v1.8. Rebellions. v1.8. https://rebellions.ai/wp-content/uploads/2026/03/RebelServer_download_EN_v1.8.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.