SambaRack SN40-16 Datasheet: Revision 051426-2

SambaNova

The SambaNova SambaRack SN40-16 datasheet gives the air-cooled inference rack 10 kW typical, 16.4 kW maximum and 520 kg, and the separate Core Services rack 4.8 kW typical and 7 kW maximum.

On this page

Overview

SambaRack SN40-16 is a prebuilt rack system for generative and agentic inference, built on SambaNova SN40L reconfigurable dataflow units (RDUs). The datasheet presents it as deployable in existing data centres at an average power draw of 10 kW with air cooling; the rack ships prebuilt, cabled and ready to deploy. It powers the SambaCloud, SambaStack and SambaManaged platforms.

The inference rack holds 16 SN40 RDUs, each with 520 MB SRAM, 64 GB HBM and 256 GB DDR. In total, 8 GB SRAM, 1 TB HBM and 4 TB attached DDR give 10.2 PFLOPS at BF16. The host side has 2 x 64-core CPUs, 2 TB DDR4 and 6 x 7.6 TB NVMe in RAID 10 (21 TB usable). Networking is a 400/200 GbE data switch and a 1 GbE management switch.

Two separate rack tables support facility planning. Inference rack: 1994 x 600 x 1270 mm, 520 kg, 10 kW typical and 16.4 kW maximum, airflow 2600 CFM front to back, 56000 BTU/hr cooling at maximum utilisation. Core Services rack: the same dimensions, 419 kg, 4.8 kW typical and 7 kW maximum, 1003 CFM, 24000 BTU/hr. For both, operating temperature is 15-30 °C, humidity 20-80% non-condensing, altitude up to 3000 m (derated 1 °C per 300 m above 2952 ft). The document is a manufacturer datasheet. The power, weight and airflow rows of the inference rack and the Core Services rack should be added separately, and typical values should not replace maximums.

Key points

  1. Inference rack: 10 kW typical, 16.4 kW maximum; 1994 x 600 x 1270 mm, 520 kg.
  2. Core Services rack: 4.8 kW typical, 7 kW maximum; same dimensions, 419 kg.
  3. Airflow is 2600 CFM for the inference rack and 1003 CFM for Core Services, front to back.
  4. Cooling at maximum utilisation is 56000 BTU/hr (inference) and 24000 BTU/hr (Core Services).
  5. Operating temperature is 15-30 °C (59-86 °F) and humidity 20-80% non-condensing.
  6. Altitude is up to 3000 m, derated 1 °C per 300 m above 2952 ft.
  7. 16 RDUs give 8 GB SRAM, 1 TB HBM, 4 TB DDR and 10.2 PFLOPS at BF16.
  8. The system ships prebuilt and cabled with a 400/200 GbE data switch.

Using it in design

  • In the rack power budget, add the inference rack (10 kW typical, 16.4 kW maximum) and the Core Services rack (4.8 kW typical, 7 kW maximum) as separate items.
  • Add the 520 kg and 419 kg rack weights to the floor loading and transport route calculation.
  • Verify cooling capacity against maximums (56000 and 24000 BTU/hr) and plan the cold aisle for front-to-back airflow.
  • Set the hall set point to hold the 15-30 °C operating range and apply the derating at high-altitude sites.

Who should read it

Electrical, mechanical and facility engineers and capacity planners placing inference racks.

Document contents

  1. Performance and use in existing data centers
  2. Dataflow architecture
  3. Three-tier memory
  4. Simple to deploy at scale
  5. SambaRack SN40 specifications
  6. Core Services rack specifications

Publication details

Authors
SambaNova
Publisher
SambaNova
Year
2026
Document number
051426-2
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

SambaNova (2026). SambaRack SN40-16 Datasheet: Revision 051426-2. SambaNova. 051426-2. https://sambanova.ai/hubfs/SambaRack%20data%20sheet%20template%2007%2009%2025.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.