H02-V2 User Manual: Pump Controller Settings and Automatic Recognition

Sempa Pompa

Sempa Pompa's two-page H02-V2 duplex pump controller guide: high and low current limits per pump, start and stop delay, maximum starts per hour and a 3.5-second automatic pump recognition test.

On this page

Overview

The guide describes the main menu, settings menu and automatic pump recognition procedure of the H02-V2 controller for two-pump systems. The main menu shows line voltage, pump 1 and 2 current, total runtimes and working type. In the settings menu, parameter changes require a password, which is not requested again for 10 minutes after entry. The software version is 1.0, dated January 2020.

Adjustable parameters: maximum and minimum operating current for each pump (the system protects itself and gives an error at these values), pump start delay (seconds), pump stop delay (seconds), maximum starts per hour, number of current-protection automatic resets and the delay between automatic resets (minutes), language, passive alarm menu and working type (for example booster). Factory settings are for technical service only.

For automatic pump recognition the AUTO/MAN switch on the side of the panel must be in AUTO and the auto mode LED turned off. The controller asks in turn whether the motor direction is correct, whether the pump air is purged and whether the system pressure is empty, then runs the motors for 3.5 seconds and reports detection completed or failed. On success, the low and high current values are assigned automatically.

Important warning: if the AUTO/MAN switch is set to MAN, all protections are disabled and serious damage may occur in case of malfunction; MAN should not be used unless mandatory. The document is not a fire-system certification record.

Key points

  1. Controller for two-pump systems; the main menu shows line voltage, pump currents, total runtimes and working type.
  2. Settings are password protected; the password is not requested again for 10 minutes after entry.
  3. Maximum and minimum operating current are set per pump; the system errors at these values.
  4. Pump start and stop delays are set in seconds.
  5. Maximum starts per hour, number of current-protection automatic resets and delay between resets (minutes) can be set.
  6. Automatic recognition asks about motor direction, pump air and system pressure, then runs the motors for 3.5 seconds.
  7. On successful recognition the low and high current values are assigned automatically.
  8. With the AUTO/MAN switch in MAN all protections are disabled.
  9. Software version 1.0, January 2020.

Using it in design

  • Add per-pump current protection (high and low current) and maximum starts per hour to the pump control panel specification.
  • Write the automatic pump recognition steps into the commissioning procedure: motor direction, pump air and system pressure check, then the 3.5-second test.
  • Set start and stop delays and the number of current-protection automatic resets from hydraulic and electrical conditions and record them in the commissioning report.
  • State in the operating instruction that MAN is used only when mandatory and with the knowledge that the pump runs unprotected.
  • Note in the design that the controller is not a certified fire-system solution; fire pump applications need a panel complying with the relevant standard.

Who should read it

Electrical and mechanical engineers and technicians selecting, commissioning and operating booster and circulation pump panels.

Document contents

  1. Main Menu
  2. Settings Menu
  3. Automatic Pump Recognition Procedure
  4. Notes and Warnings

Publication details

Authors
Sempa Pompa
Publisher
Sempa Pompa
Year
Year not stated
Document number
H02-V2; hosted filename H0275-V2 User Manual V1_0_eng
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Public source opened on the access date. No open redistribution licence established; metadata and original short summaries only. Displayed VER.1.0 01/2020 is controller-screen content; publication year is not inferred from it.

Citation

Sempa Pompa H02-V2 User Manual: Pump Controller Settings and Automatic Recognition. Sempa Pompa. H02-V2; hosted filename H0275-V2 User Manual V1_0_eng. https://sempapompa.com/writable/uploads/medias/files/mf%20resim/pano%20kk/H0275-V2%20User%20Manual%20V1_0_eng.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.