Effectiveness and Implementation of Modular Containment in Existing Data Centers
Upsite Technologies · Lars Strong, Bruce Long
An Upsite white paper introducing modular containment built from rack top baffles, bi-directional doors and gap panels; CFD shows maximum inlet temperature down 10.3 °F, and a bank's site shows 10.2 °F reductions at row ends.
On this page
Overview
The paper explains that physically separating hot and cold air is one of the most effective ways to raise efficiency and utilization, but hard wall and soft curtain containment need engineering plans, cost, and operational disruption and do not accommodate future rack changes. The proposed modular containment adapts to the existing aisle layout without engineering or construction services. Research cited shows the average room has 3X to 4X more cooling capacity than required.
The system has four components: angular rack top baffles (on the top front edge, slightly pressurizing the cold aisle and reducing hot air recirculation over racks), vertical rack top baffles (on the top rear edge, creating a chimney effect toward the ceiling plenum), bi-directional doors at aisle ends, and adjustable rack gap panels sealing spaces between racks. The architecture is deliberately non-sealed: because of IT airflow variation and redundant cooling, excess air entering the cold aisle must be able to escape, avoiding over-pressurized cold aisles, which ASHRAE recommends against.
In the CFD analysis, end-of-row racks show hot air wrapping around the row ends. With bi-directional doors all IT inlet temperatures meet the ASHRAE TC9.9 recommended 80.6 °F; at aisle-end cabinets the maximum inlet reduction is 10.2 °F and the average 6.2 °F. For rack tops the maximum reduction is 10.3 °F and average 3.7 °F. In field results at a global financial institution's raised-floor room, maximum and average inlet temperatures fall across racks, with the most dramatic change at the ends of aisles.
Implementation cautions: angular baffles partially enclose the aisle, so smoke patterns and fire detection may be affected and baffles and doors may impede suppression agent dispersion; the authority having jurisdiction (AHJ) decides. In flooded supply/flooded return environments barriers can raise inlet temperatures and need care. The document is a vendor publication.
Key points
- The average room has 3X to 4X more cooling capacity than required.
- Four modular containment components: angular rack top baffle, vertical rack top baffle, bi-directional door, adjustable rack gap panel.
- The architecture is non-sealed, letting excess air escape and avoiding over-pressurized cold aisles that ASHRAE recommends against.
- Listed benefits: higher supply and return set points, hot spot elimination, more economizer hours, lower dehumidification and humidification cost, and higher rack densities.
- CFD: with bi-directional doors the maximum inlet reduction at row-end racks is 10.2 °F, average 6.2 °F.
- CFD: with rack top baffles the maximum inlet reduction is 10.3 °F, average 3.7 °F.
- Components install without tools and can be reconfigured; installation in an existing room needs no interruption to operations.
- Angular baffles can affect fire detection and suppression agent dispersion; the AHJ makes the final decision.
Using it in design
- Measure inlet temperature at row-end racks in an existing room to find end recirculation; make doors or similar end closure the priority fix.
- After airflow management improvement raise cooling unit set points and recalculate economizer hours.
- In a non-sealed containment architecture monitor cold aisle over-pressure and account for IT airflow variation.
- Evaluate the containment solution together with fire detection and suppression design and obtain AHJ approval.
- In flooded supply or slab-floor rooms, model the effect of barriers on airflow first.
Who should read it
Designers and operations managers looking for fast, low-cost containment in existing data halls.
Document contents
- Executive Summary
- Introduction
- Modular Containment
- Implications on Fire Detection and Suppression Systems
- Modular Containment CFD Analysis
- Field Results at a Global Financial Institution
- Conclusion
Related standards
- ASHRAE TC 9.9 thermal guidelines
- NFPA 75
Publication details
- Authors
- Lars Strong; Bruce Long
- Publisher
- Upsite Technologies
- Year
- 2014
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
© Upsite Technologies, Inc.; no open licence stated
Citation
Lars Strong; Bruce Long (2014). Effectiveness and Implementation of Modular Containment in Existing Data Centers. Upsite Technologies. https://www.upsite.com/wp-content/uploads/2017/08/Effectiveness-and-Implementation-of-Modular-Containment-in-Existing-Data-Centers.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.