Materials Reliability in Direct-to-Chip Cooling: A Systematic Study of Aluminum Corrosion in Next-Generation Data Center Coolants
University of Texas at Arlington / MavMatrix · FNU Harish Gangadhara
A 2025 University of Texas at Arlington master's thesis comparing aluminium corrosion across surface treatments and modern coolants in direct-to-chip systems at 50-100 kW per rack.
On this page
Overview
The thesis starts from the fact that chip and rack power densities, driven by AI and cloud workloads, now approach and sometimes exceed 50-100 kW per rack. Direct-to-chip liquid cooling has become the key enabling technology, yet the durability of materials in contact with the coolant remains a reliability concern over system lifetimes.
Copper is traditionally used for cold plates and loop components. Its cost, mass and supply-chain uncertainty are driving interest in aluminium: low density helps handling and design flexibility, and lower raw-material cost can reduce capital expense, provided corrosion is adequately controlled in contemporary coolant chemistries.
The work systematically evaluates aluminium corrosion across a range of surface treatments and modern data-centre coolant formulations and finds pronounced differences between combinations. The results clarify the conditions under which aluminium can serve as a robust long-term substitute for copper in cold-plate and thermal-control loops, and show the inhibiting capacity of the tested fluids across common treatments. The public abstract is the basis here.
Key points
- Rack power densities approach and sometimes exceed 50-100 kW.
- Aluminium is lighter and cheaper than copper, but its corrosion performance depends on coolant chemistry.
- Susceptibility differs markedly between surface-treatment and coolant combinations.
- The study identifies conditions under which aluminium can replace copper over the long term.
- Keywords include ASTM-based corrosion testing.
Using it in design
- When choosing aluminium cold plates or manifolds, approve surface treatment and coolant formulation as a pair.
- Check galvanic risk and inhibitor compatibility in mixed-metal (copper and aluminium) loops.
- Request an aluminium corrosion test report from the coolant supplier.
- Weigh the cost and weight gain against lifetime corrosion risk.
Who should read it
Engineers selecting cold-plate and manifold materials and designers writing coolant specifications.
Publication details
- Authors
- FNU Harish Gangadhara
- Publisher
- University of Texas at Arlington / MavMatrix
- Year
- 2025
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY 4.0: share with attribution
Original licence note
The thesis-specific repository License section links CC BY 4.0. Preserve attribution and separate third-party rights; only repository metadata/abstract read. Round 5/6 ingestion retains bibliographic metadata only; no local full text is redistributed.
Citation
FNU Harish Gangadhara (2025). Materials Reliability in Direct-to-Chip Cooling: A Systematic Study of Aluminum Corrosion in Next-Generation Data Center Coolants. University of Texas at Arlington / MavMatrix. https://mavmatrix.uta.edu/mechaerospace_theses/1036/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.