Regime-Adaptive Weighted Ensemble Learning for Computing-Driven Dynamic Load Forecasting in AI Data Centers

arXiv preprint (Oklahoma State University / New York University) · Ziying Wang, Ying Zhang et al.

An arXiv preprint proposes a minute-level short-term load forecasting method for AI data centres, whose load is driven by bursty, non-stationary job arrivals.

On this page

Overview

The work is an arXiv preprint by Ziying Wang, Ying Zhang, Lei Wang and Yuzhang Lin (arXiv:2604.27207, 2026; Oklahoma State University / New York University). Its subject is short-term, minute-level load forecasting for AI data centres whose load is driven by bursty, non-stationary job arrivals.

The method combines two submodels, XGBoost and a 1D-CNN, through a small neural network. That network learns time-varying ensemble weights from recent submodel performance and load-increment features, so the forecast adapts across idle, ramp-up, high and ramp-down regimes. The data are cluster-level series built from the MIT Supercloud GPU logs: job-level logs at 0.1 s resolution were resampled to 1-min node-level series, aggregated to cluster level, and idle slots were filled with a 25 W GPU baseline.

The data were split chronologically: 60% for submodel training, 20% for ensemble training and the remainder for testing. Forecast errors (NRMSE/NMAE) are SVR 3.04/2.30%, LSTM 2.66/2.11%, XGBoost 2.46/1.86%, 1D-CNN 2.45/1.85% and the proposed ensemble 0.83/0.37%. Relative to the strongest baseline (1D-CNN), the method improves NRMSE by 66.1% and NMAE by 80.2%. In ramp regimes both submodels lag, and in the high regime both underestimate; the adaptive weights track the ground truth more closely across all four regimes. Limit: the evaluation rests on a single dataset (MIT Supercloud).

Key points

  1. MIT Supercloud job-level GPU logs at 0.1 s resolution were resampled to 1-min node series and aggregated to cluster level; idle slots filled with a 25 W GPU baseline.
  2. Data split chronologically: 60% for submodel training, 20% for ensemble training, remainder for testing.
  3. Forecast errors (NRMSE/NMAE): SVR 3.04/2.30%, LSTM 2.66/2.11%, XGBoost 2.46/1.86%, 1D-CNN 2.45/1.85%, proposed ensemble 0.83/0.37%.
  4. Relative to the strongest baseline (1D-CNN) the method improves NRMSE by 66.1% and NMAE by 80.2%.
  5. In ramp regimes both submodels lag and in the high regime both underestimate; adaptive weights track the ground truth more closely across all four regimes.

Using it in design

  • For operations and grid-interaction features, use regime-aware (idle/ramp/high) minute-resolution IT load forecasting with job-scheduler signals (active jobs) as inputs, rather than only historical kW.
  • Report forecast error by regime, since ramps are where single models fail and where utility ramp limits bite.
  • Use such forecasts to schedule storage or demand-response actions ahead of job starts.
  • Treat the results as findings from a single dataset; validate with your own workload data.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Compare the cost of design decisions

Evaluate equipment costs, energy expenses and total cost of ownership (TCO) using your inputs and assumptions in SoSo CAD.

Request a demo
CAPEX and TCO estimates in the SoSo CAD cost workspace

Who should read it

Engineers and researchers working on grid interaction, storage and energy forecasting for AI data centres.

Publication details

Authors
Ziying Wang; Ying Zhang; Lei Wang; Yuzhang Lin
Publisher
arXiv preprint (Oklahoma State University / New York University)
Year
2026
Document number
arXiv:2604.27207
Document language
English
Source type
Scientific
Access
Free to read
Licence
arXiv distribution permission — reuse conditions remain with the rights holder
Original licence note

arXiv default non-exclusive distribution licence; citation only

Citation

Ziying Wang; Ying Zhang; Lei Wang; Yuzhang Lin (2026). Regime-Adaptive Weighted Ensemble Learning for Computing-Driven Dynamic Load Forecasting in AI Data Centers. arXiv preprint (Oklahoma State University / New York University). arXiv:2604.27207. https://doi.org/10.48550/arXiv.2604.27207

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.