APD 2751 M Diesel Generator Set (Data Center) - Technical Datasheet
Aksa Power Generation
Seven-page datasheet for Aksa's 2,750 kVA standby / 2,500 kVA data-centre-rated 50 Hz diesel generator set with a Mitsubishi S16R2 engine and Stamford alternator.
On this page
Overview
At 400 V, 50 Hz and PF 0.8 the datasheet gives two ratings: Standby (ESP) 2,200 kW / 2,750 kVA and data-centre (DCP) 2,000 kW / 2,500 kVA at 3,969 A. ESP follows ISO 8528-1 with no overload, while DCP is defined as the maximum power for variable or continuous load with unlimited run hours. Data tolerance is +/-5%.
Fuel consumption at 100/75/50% DCC load is 528/390/264 l/h. Exhaust gas flow is 506 m3/min with 1,693 kW of heat rejected to exhaust; radiator fan airflow is 3,480 m3/min with 125 Pa of external restriction allowed. The open set measures 6,720 x 2,410 x 3,250 mm, weighs 15,000 kg dry and has a 2,000 l base tank.
The alternator is a Stamford S7L1D-J4 at 2,500 kVA with class H insulation and temperature rise, IP23. The sheet gathers the data needed for fuel, ventilation and layout calculations in one place. Because the ISO 'Data Centre Power' rating is defined on a reliable-utility assumption, manufacturer confirmation of unlimited hours should be obtained before using it as a Tier III/IV basis.
Key points
- 400 V 50 Hz PF 0.8: Standby (ESP) 2,200 kW / 2,750 kVA; data-centre (DCP) 2,000 kW / 2,500 kVA, 3,969 A.
- ESP per ISO 8528-1 with no overload; DCP is maximum power for variable or continuous load with unlimited run hours.
- Fuel consumption at 100/75/50% DCC load: 528/390/264 l/h.
- Exhaust gas flow 506 m3/min, heat rejection to exhaust 1,693 kW; radiator airflow 3,480 m3/min with 125 Pa external restriction.
- Open set 6,720 x 2,410 x 3,250 mm, dry weight 15,000 kg, 2,000 l base tank.
- Stamford S7L1D-J4 alternator 2,500 kVA, class H, IP23; data tolerance +/-5%.
Using it in design
- Add ESP and DCP kW/kVA, rated current, fuel l/h at 50/75/100%, exhaust flow and heat, radiator airflow and allowable external static, dimensions/weight and base tank as generator catalog fields.
- Use them for automatic fuel autonomy (tank sizing) and plant-room ventilation checks.
- Flag use of the DCP rating as a Tier III/IV basis without manufacturer confirmation of unlimited hours.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Review your power design in SoSo CAD
Inspect supply paths, equipment loads and UPS failure scenarios in one model.
Request a demo
Who should read it
Designers sizing fuel, ventilation and layout for a large data-centre generator.
Related standards
- ISO 8528-1
- ISO 8528-5
- ISO 8528-13
Publication details
- Authors
- Aksa Power Generation
- Publisher
- Aksa Power Generation
- Year
- 2026
- Document number
- APD 2751 M
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only — the publisher’s terms apply to the original document
Citation
Aksa Power Generation (2026). APD 2751 M Diesel Generator Set (Data Center) - Technical Datasheet. Aksa Power Generation. APD 2751 M. https://webcdn.aksa.com.tr/CDN/productPdf/apd-2751-m_2722_english.pdf
Events on this subject
- Electricity Eurasia 2027
- ELECO 2026 Elektrik-Elektronik ve Biyomedikal Mühendisliği Konferansı
- ICCI 2027 – Uluslararası Enerji ve Çevre Fuarı ve Konferansı
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.