Simulation-based assessment of data center waste heat utilization using aquifer thermal energy storage of a university campus
Building Simulation (Springer Science and Business Media LLC) · Vojtech Dvorak, Vojtech Zavrel et al.
CTU Prague, TU/e and Tecnalia researchers use TRNSYS and CONTAM to judge whether a planned mid-sized campus data centre at Eindhoven University of Technology could be cooled from, and reject heat into, the campus's existing district aquifer thermal energy storage (ATES) system.
CC BY 4.0 — share with attribution
On this page
Overview
Practical use of data-centre waste heat is very challenging, and its possible benefits are uncertain and difficult to quantify with common methods. The study is a feasibility study using dynamic simulation tools to predict the campus energy performance resulting from integrating a proposed data centre with an existing ATES. Uncertainty in the data centre's thermal management, chiefly supply-air setpoints and air management, was propagated through the cooling energy results; supply-air temperature setpoints of 13, 17, 21 and 25 °C (within ASHRAE guidelines) were simulated.
The reference data centre has about one hundred racks on a 23 m × 30 m raised floor, averaging 10.7 kW per rack, for a total IT load of 1090 kW. The campus ATES has 32 wells, 20-80 m deep, in three warm and three cold clusters linked by about 2 km warm and cold rings; cold wells hold 6-9 °C water and warm wells 14-17 °C, against a natural subsurface temperature of 10-13 °C. Because the ATES had mainly supplied cooling, imported heat exceeded exported heat; keeping the yearly heat balance is identified as the potential barrier to connecting a continuously cooling data centre.
Three cases were compared with a conventional chiller plant: the isolated data centre without ATES, ATES in the current campus with its import/export balance policy, and ATES in a future campus. Cooperation with ATES improves average PUE from 1.78 to 1.45. Integrated operation cuts data-centre CO2 emissions by 680 tons per year on average under current ATES policy and by 1000 tons per year in the future scenario.
The conclusion is that linking with ATES lowers PUE and CO2, and campus heat export also helps rebalance an aquifer drifting toward net cooling. Limits: a simulation feasibility for a single campus and a planned data centre; results depend on this ATES's heat balance policy.
Key points
- The reference data centre has about one hundred racks on a 23 m × 30 m raised floor, averaging 10.7 kW per rack, for a total IT load of 1090 kW.
- The campus ATES has 32 wells, 20-80 m deep, in three warm and three cold clusters; cold wells hold 6-9 °C water and warm wells 14-17 °C, against a natural subsurface temperature of 10-13 °C.
- Because the ATES had mainly supplied cooling, imported heat exceeded exported heat; keeping the yearly heat balance is the potential barrier to connecting a continuously cooling data centre.
- Supply-air temperature setpoints of 13, 17, 21 and 25 °C (within ASHRAE guidelines) were simulated in the uncertainty analysis.
- Cooperation with ATES improves average PUE from 1.78 to 1.45.
- Integrated operation cuts data-centre CO2 emissions by 680 tons per year on average under current ATES policy, and by 1000 tons per year in the future scenario.
Using it in design
- When considering connecting a data centre to an ATES, make the yearly heat balance (imported versus exported heat) the first feasibility check; a continuously cooling data centre can shift it toward heat rejection.
- Propagate the supply-air setpoint (13-25 °C) uncertainty through waste-heat potential and PUE results.
- Compare the PUE and CO2 gain of ATES integration (1.78 to 1.45, 680-1000 tons per year) against a conventional chiller plant on the same model.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Compare the cost of design decisions
Evaluate equipment costs, energy expenses and total cost of ownership (TCO) using your inputs and assumptions in SoSo CAD.
Request a demo
Who should read it
Planners and energy engineers evaluating data-centre connection to campus and district ATES systems.
Document contents
- 2 DC waste heat utilization system (2.1.1 ATES district system, 2.1.2 DC system, 2.2 Utilization scenarios)
- 3 Modelling (3.1 Modelling method and assumptions)
- 4 Discussion (4.2 Recommendation for ATES management: current utilization scenario, reduction of DC electricity; future utilization scenario, benefits of using DC waste heat)
- 5 Conclusion
Related standards
- ASHRAE TC 9.9 thermal guidelines
Read the document
dc-waste-heat-ates-university-2020.pdf
CC BY 4.0 — share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Vojtech Dvorak; Vojtech Zavrel; J. I. Torrens Galdiz; Jan L. M. Hensen
- Publisher
- Building Simulation (Springer Science and Business Media LLC)
- Year
- 2020
- Volume
- 13
- Issue
- 4
- Pages
- 823-836
- Document language
- English
- Source type
- Scientific
- Access
- Open licence — downloadable
- Licence
- CC BY 4.0 — share with attribution
- Licence evidence
- doi.org
Original licence note
Article states it is open access under a Creative Commons Attribution (CC BY / CC BY 4.0) licence (verified in PDF text).
Citation
Vojtech Dvorak; Vojtech Zavrel; J. I. Torrens Galdiz; Jan L. M. Hensen (2020). Simulation-based assessment of data center waste heat utilization using aquifer thermal energy storage of a university campus. Building Simulation (Springer Science and Business Media LLC). 13(4), 823-836. https://doi.org/10.1007/s12273-020-0629-y
Events on this subject
Browse the events calendarAll content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.