Research paperPDF2026

Smart Reuse of Waste Heat from Data Centres: Energy and Exergy Analysis for a District-Heating Network in Bulgaria

Energies (MDPI AG) · Antonio Verzino, Lorenzo Talluri et al.

Within the EU THUNDER project, the authors run an hourly full-year energy and exergy analysis of a 500 kW air-cooled data centre in Varna, Bulgaria: its condenser heat is upgraded by vapour-compression heat pumps, buffered in thermochemical storage and fed into a real third-generation district heating network with an average demand of 9.3 MW.

CC BY 4.0 — share with attribution

On this page

Overview

The rapid growth of data centres is driving higher electricity consumption and continuous generation of low-grade waste heat; integrating this heat into district-heating networks offers a smart thermal-management strategy in urban areas. The study presents an energy and exergy analysis of an integrated system comprising a data centre, vapour-compression heat pumps, thermochemical energy storage and a third-generation DH network. An integrated scenario was compared with a reference where data-centre cooling and DH generation run separately, under two data-centre air-temperature and free-cooling strategies.

Case A used data-centre inlet/outlet air of 20-35 °C with free cooling up to 15 °C outdoor; Case B used 25-40 °C with free cooling up to 20 °C outdoor, both with hot-aisle/cold-aisle layouts. Moving from Case A to Case B cut data-centre cooling electricity from 240.9 to 132.2 MWh (almost 45.0%) through more free cooling. Recoverable waste heat (condenser heat during active cooling only) in Case B is almost 45.0% of that in Case A (1043.1 vs 1985.1 MWh).

Despite its 500 kW size against an average DH demand of 9.3 MW, the data centre can supply 3.0% of annual DH demand and 22.4% of instantaneous load in favourable periods (Case A). Centralised DH heat pumps are cited as giving COP 3-5 for supply temperatures up to 70-80 °C. Thermochemical storage decouples waste-heat availability from DH demand, enabling seasonal shifting, and the integrated configuration consistently raises overall exergy efficiency.

The conclusion is that warmer data-centre setpoints and more free cooling sharply cut the heat that can be recovered, so data-centre and DH operators need to coordinate. Limits: a single small data centre and one DH network (Varna), so results are for this case.

Key points

  1. Case A used data-centre inlet/outlet air of 20-35 °C with free cooling up to 15 °C outdoor; Case B used 25-40 °C with free cooling up to 20 °C outdoor; both with hot-aisle/cold-aisle layouts.
  2. Moving from Case A to Case B cut data-centre cooling electricity from 240.9 to 132.2 MWh (almost 45.0%) through more free cooling.
  3. Recoverable waste heat (condenser heat during active cooling only) in Case B is almost 45.0% of that in Case A (1043.1 vs 1985.1 MWh).
  4. Despite its 500 kW size against an average DH demand of 9.3 MW, the data centre can supply 3.0% of annual DH demand and 22.4% of instantaneous load in favourable periods (Case A).
  5. Centralised DH heat pumps are cited as giving COP 3-5 for supply temperatures up to 70-80 °C.
  6. Thermochemical storage decouples waste-heat availability from DH demand, enabling seasonal shifting, and the integrated configuration consistently raises overall exergy efficiency.

Using it in design

  • Set data-centre setpoints (air temperature, free-cooling threshold) together with waste-heat sales: warmer setpoints and more free cooling cut cooling electricity by about 45% but also cut recoverable heat to about 45%.
  • Consider seasonal thermochemical or similar storage to decouple waste-heat availability from DH demand.
  • In contract design, note that even a small data centre can contribute meaningfully to DH demand (3.0% annual, up to 22.4% instantaneous) but needs coordination between data-centre and DH operators.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Compare the cost of design decisions

Evaluate equipment costs, energy expenses and total cost of ownership (TCO) using your inputs and assumptions in SoSo CAD.

Request a demo
CAPEX and TCO estimates in the SoSo CAD cost workspace

Who should read it

Operators and planners intending to connect data-centre waste heat to third-generation district heating networks.

Document contents

  1. 1. Introduction (1.1 The Heating Sector: Current Situation and Perspectives of Decarbonisation, 1.2 The District Heating Sector: Evolution and Future Trends, 1.3 Data Centres as Emerging Sources of Waste Heat for District Heating, 1.5 Thermal Energy Storage for Flexible District-Heating Systems)
  2. 2. Materials and Methods (2.1 Scenario S0: No Integration Between DC and DHN, 2.2 DC Integrated Cooling, Thermal Recovery, and Upgrade, TCS Characterisation and Functioning, 2.3 Exergy Analysis)
  3. 3. Results and Discussion (3.1 Energy Analysis Results, 3.2 Exergy Analysis Results, 3.3 Further Possible Strategies for Waste-Heat Use, 3.5 Relevance of This Proposal for Low-Temperature District-Heating Networks)
  4. 4. Conclusions

Related standards

  • EU Energy Efficiency Directive (recast)

Read the document

dc-waste-heat-dh-bulgaria-exergy-2026.pdf

PDF · 1.9 MB · English

CC BY 4.0 — share with attribution

The document is provided unaltered because its licence permits redistribution.

Publication details

Authors
Antonio Verzino; Lorenzo Talluri; Andrea Rocchetti; Luca Socci
Publisher
Energies (MDPI AG)
Year
2026
Volume
19
Issue
3
Pages
800
Document language
English
Source type
Scientific
Access
Open licence — downloadable
Licence
CC BY 4.0 — share with attribution
Licence evidence
www.mdpi.com
Original licence note

PDF p.1 states the article is open access under the Creative Commons Attribution (CC BY 4.0) licence; MDPI publishes all articles under CC BY 4.0.

Citation

Antonio Verzino; Lorenzo Talluri; Andrea Rocchetti; Luca Socci (2026). Smart Reuse of Waste Heat from Data Centres: Energy and Exergy Analysis for a District-Heating Network in Bulgaria. Energies (MDPI AG). 19(3), 800. https://doi.org/10.3390/en19030800

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.