Feasibility Analysis of Indirect Evaporative Cooling System Assisted by Liquid Desiccant for Data Centers in Hot-Humid Regions
Sustainability (MDPI AG) · Wenchao Shi, Xiaochen Ma et al.
Plain IEC loses most of its potential in hot, humid climates because the wet-bulb temperature stays high; the study models a two-stage system that first dehumidifies air in a liquid-desiccant IEC stage (lithium chloride solution) and then uses the drier air as secondary air for a second IEC stage.
CC BY 4.0 — share with attribution
On this page
Overview
In hot, humid regions, energy demand is largely driven by the air conditioning needed to maintain suitable operating temperatures. The study proposes a novel multi-stage IEC system with a liquid desiccant in the primary air channel: the first stage uses a liquid-desiccant IEC (LD-IEC) for dehumidification and the second stage uses the treated air as secondary air to enhance cooling. The model was validated against published data and run through a parametric study of inlet air state, solution concentration and mass flow ratio.
Findings: the first-stage LD-IEC lowers the wet-bulb temperature of the ambient air, enhancing the second-stage IEC. Higher ambient temperature, relative humidity and circulated air velocity reduce the temperature drop, while higher solution concentration and circulated air temperature increase it. Cooling performance improves as the mass flow ratio rises to 0.8 but falls at 0.9, so an optimum exists and must be chosen at design stage. Desiccant solution concentration is limited to 0.20-0.40 to avoid crystallisation, with solution temperature in the 20-50 °C range.
In the Hong Kong case study, the multi-stage LD-IEC improved the air temperature drop by 72.7% compared with a single IEC. With a 25 °C supply-air threshold, supplementary mechanical cooling hours fell from 5092 h to 31 h per year.
Limits: desiccant regeneration energy and economics are left for future work, so the benefit is shown for cooling performance only, not total energy or cost. The model was validated against published data, not site measurements of an installed system.
Key points
- In the Hong Kong case study, the multi-stage LD-IEC improved the air temperature drop by 72.7% compared with a single IEC.
- With a 25 °C supply-air threshold, supplementary mechanical cooling hours fell from 5092 h to 31 h per year.
- Cooling performance improves as the mass flow ratio rises to 0.8 but falls at 0.9, so an optimum exists and must be chosen at design stage.
- Higher ambient temperature, relative humidity and circulated air velocity reduce the temperature drop; higher solution concentration and circulated air temperature increase it.
- Desiccant solution concentration is limited to 0.20-0.40 to avoid crystallisation, with solution temperature in the 20-50 °C range.
Using it in design
- Where plain IEC falls short in a hot-humid climate (high wet-bulb), consider a liquid-desiccant pre-stage; in the Hong Kong example supplementary mechanical cooling fell from 5092 to 31 h.
- Optimise the mass flow ratio at design stage (around 0.8, performance drops at 0.9) and keep solution concentration in the 0.20-0.40 range to avoid crystallisation.
- Calculate desiccant regeneration energy and economics separately; the study did not assess them.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Check cooling capacity alongside your design
Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.
Request a demo
Who should read it
Cooling designers and researchers applying or investigating indirect evaporative cooling in hot-humid regions.
Document contents
- 1. Introduction
- 2. Literature Review
- 3. Methodology (3.1 System Configuration, 3.2 Model Establishment: IEC model, LD-IEC model; 3.3 Model Solution and Grid Independence Monitoring, 3.4 Model Validation)
- 4. Results (effect of mass flow ratio, case study, 4.8 Discussions)
- 5. Limitations and Future Works
- 6. Conclusions
Related standards
- ASHRAE TC9.9 Thermal Guidelines
Read the document
iec-liquid-desiccant-hot-humid-2024.pdf
CC BY 4.0 — share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Wenchao Shi; Xiaochen Ma; Yunran Min; Hongxing Yang
- Publisher
- Sustainability (MDPI AG)
- Year
- 2024
- Volume
- 16
- Issue
- 5
- Pages
- 2011
- Document language
- English
- Source type
- Scientific
- Access
- Open licence — downloadable
- Licence
- CC BY 4.0 — share with attribution
- Licence evidence
- www.mdpi.com
Original licence note
p.1 states the article is open access under the Creative Commons Attribution (CC BY) licence.
Citation
Wenchao Shi; Xiaochen Ma; Yunran Min; Hongxing Yang (2024). Feasibility Analysis of Indirect Evaporative Cooling System Assisted by Liquid Desiccant for Data Centers in Hot-Humid Regions. Sustainability (MDPI AG). 16(5), 2011. https://doi.org/10.3390/su16052011
Events on this subject
Browse the events calendarAll content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.