Techno-Economic Comparison of Data Center Cooling Using Magnetic Bearing Chillers and Aquifer Thermal Energy Storage
Energies (MDPI AG) · Apurva Malpure, Andrew Stumpf et al.
An hourly techno-economic comparison of three chilled-water plants for the same data-centre IT load profile: a water-cooled centrifugal chiller baseline, magnetic-bearing chillers (MBC), and MBC with a screening-level aquifer thermal energy storage (ATES) discharge.
CC BY 4.0 — share with attribution
On this page
Overview
Data centres are large and rapidly growing electricity consumers, and cooling systems account for a substantial share of their energy demand. The study presents a climate-sensitive, hourly techno-economic comparison of three cooling configurations under consistent operating assumptions. All share a waterside economiser and two 4058 kW chillers, and Phoenix and Fairbanks bracket US cooling climates. The plant uses 7 °C chilled-water supply with a 5 K delta-T, and a cooling tower with a 4 K approach and a 2 °C minimum condenser-water temperature.
Phoenix baseline operating modes: 204 h full free cooling, 1748 h partial free cooling and 6808 h mechanical only; Fairbanks: 5350 h, 1297 h and 2113 h. MBC cut annual cooling electricity from 1169.4 to 957.4 MWh in Phoenix (18.1%) and from 361.6 to 319.4 MWh in Fairbanks (11.7%). Cooling-only PUE' was 1.095 (baseline) and 1.078 (MBC) in Phoenix, and 1.029 and 1.026 in Fairbanks.
With a premium capex of USD 123,527, MBC paid back in 5.8 years in Phoenix but 36.6 years in Fairbanks. Peak cooling demand fell by 119.4 kW and 71.6 kW respectively. MBC+ATES gave no extra electricity savings over MBC-only, and its better discounted savings disappear (NPV negative) if its O&M is set equal to MBC-only.
Limits: the authors stress that the ATES case is a simplified screening scenario and that results depend on tariff and O&M assumptions; ATES should not be read as a complete seasonal design or full techno-economic assessment. Only two climates were examined.
Key points
- The plant uses 7 °C chilled-water supply with a 5 K delta-T, and a cooling tower with a 4 K approach and a 2 °C minimum condenser-water temperature; tower water temperature = max(outdoor wet-bulb + approach, minimum).
- Phoenix baseline operating modes: 204 h full free cooling, 1748 h partial free cooling and 6808 h mechanical only; Fairbanks: 5350 h, 1297 h and 2113 h.
- MBC cut annual cooling electricity from 1169.4 to 957.4 MWh in Phoenix (18.1%) and from 361.6 to 319.4 MWh in Fairbanks (11.7%).
- Cooling-only PUE' was 1.095 (baseline) and 1.078 (MBC) in Phoenix, and 1.029 and 1.026 in Fairbanks.
- With a premium capex of USD 123,527, MBC paid back in 5.8 years in Phoenix but 36.6 years in Fairbanks; peak cooling demand fell by 119.4 kW and 71.6 kW.
- MBC+ATES gave no extra electricity savings over MBC-only; its better discounted savings disappear (NPV negative) if its O&M is set equal to MBC-only.
Using it in design
- Evaluate magnetic-bearing chiller investment by climate: payback was 5.8 years in a hot climate relying more on mechanical cooling, 36.6 years in a cold climate dominated by free cooling.
- Model chiller staging and operating modes (full, partial free cooling, mechanical) hourly and report cooling-only PUE and peak demand.
- Show storage-option savings such as ATES with sensitivity to O&M and tariff assumptions; NPV turned negative when O&M was equalised.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Check cooling capacity alongside your design
Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.
Request a demo
Who should read it
Designers and investment decision makers comparing chilled-water plant chiller technology and storage options techno-economically.
Document contents
- 1. Introduction
- 2. Materials and Methods (2.1 Assumptions and Boundary Conditions, 2.2 System Description, 2.3 Data Inputs and Parameters: weather and humidity data, IT load profile, indoor environmental conditions; 2.4 Chiller and Auxiliary Power Model, 2.5 ATES Dispatch and Storage Balance, 2.6 Hourly Simulation Workflow, 2.7 Financial Evaluation, 2.8 Model Verification and Quality Assurance)
- 3. Results (3.1 Energy Performance: operating modes, energy consumption and PUE'; 3.2 Economic Performance)
- 4. Discussion (4.1 Benchmarking Against Previous Studies, 4.2 Limitations and Future Work)
- 5. Conclusions
Related standards
- ASHRAE 90.4
- ASHRAE TC9.9 Thermal Guidelines
Read the document
magnetic-bearing-chiller-ates-dc-cooling-2026.pdf
CC BY 4.0 — share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Apurva Malpure; Andrew Stumpf; Upasana Pandey; Yu-Feng Lin; Craig Bradshaw
- Publisher
- Energies (MDPI AG)
- Year
- 2026
- Volume
- 19
- Issue
- 17
- Pages
- 3947
- Document language
- English
- Source type
- Scientific
- Access
- Open licence — downloadable
- Licence
- CC BY 4.0 — share with attribution
- Licence evidence
- www.mdpi.com
Original licence note
p.1 states the article is open access under the Creative Commons Attribution (CC BY) licence.
Citation
Apurva Malpure; Andrew Stumpf; Upasana Pandey; Yu-Feng Lin; Craig Bradshaw (2026). Techno-Economic Comparison of Data Center Cooling Using Magnetic Bearing Chillers and Aquifer Thermal Energy Storage. Energies (MDPI AG). 19(17), 3947. https://doi.org/10.3390/en19173947
Events on this subject
Browse the events calendarAll content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.