Specifying Air Handling Units to Endure High Wind Events

Nortek Air Solutions · Lee Magill

This Nortek paper explains how to specify outdoor air-handling unit cabinets that survive hurricanes and tornadoes, using Miami-Dade HVHZ product approval as the benchmark.

On this page

Overview

The paper starts with wind categories. On the Saffir-Simpson scale Cat 1 is 74-95 mph, Cat 2 96-110, Cat 3 111-130, Cat 4 131-155 and Cat 5 above 155 mph. Miami-Dade County High Velocity Hurricane Zone (HVHZ) product approval is the certification the paper uses as its benchmark; it covers FBC TAS 201 (impact), TAS 202 (static air pressure) and TAS 203 (cyclic pressure), plus ASTM E8 and E72 material and panel tests.

The second half explains pressure ratings. The roughly 20 HVHZ-certified cabinet designs listed range from 55 psf (146 mph) to 227 psf (301 mph). The psf figure quoted is the design pressure, equal to 67% of the overload pressure. The key caution is that psf does not map directly to mph: the building risk category and equipment elevation from the structural engineer have to be applied.

A table lists HVHZ-rated AHU cabinets from several manufacturers. It helps compare products, but selection depends on site wind speed, risk category and mounting height as well as the rating itself. As a manufacturer publication it does not replace an ASCE 7 calculation; it gives a starting specification for outdoor or rooftop air handlers.

Key points

  1. Saffir-Simpson: Cat 1 74-95 mph, Cat 2 96-110, Cat 3 111-130, Cat 4 131-155, Cat 5 >155 mph.
  2. Miami-Dade HVHZ approval covers FBC TAS 201 (impact), 202 (static pressure), 203 (cyclic pressure) plus ASTM E8 and E72.
  3. About 20 HVHZ-certified designs are rated from 55 psf (146 mph) to 227 psf (301 mph).
  4. Rated psf is design pressure, which is 67% of the overload pressure.
  5. psf does not map directly to mph; risk category and equipment elevation come from the structural engineer.

Using it in design

  • For sites in hurricane or tornado regions, require a wind-pressure rating (psf at design pressure) for outdoor mechanical equipment and derive the required psf from wind speed, risk category and mounting height.
  • Add 'windPressureRating_psf' and 'HVHZ approved' fields to the catalog.
  • Warn when rooftop AHUs or chillers lack an adequate rating.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Check cooling capacity alongside your design

Review zone heat loads, available capacity and the capacity balance after the largest unit is lost in SoSo CAD.

Request a demo
Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Who should read it

Mechanical designers specifying outdoor or rooftop air handlers in hurricane regions.

Related standards

  • Florida Building Code TAS 201/202/203
  • ASCE 7
  • ASTM E72
  • ASTM E8

Publication details

Authors
Lee Magill
Publisher
Nortek Air Solutions
Year
2020
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

Lee Magill (2020). Specifying Air Handling Units to Endure High Wind Events. Nortek Air Solutions. https://www.nortekdatacenter.com/wp-content/uploads/2020/11/NDCC-Miami-Dade-Specifying-Air-Handling-Units-WP-1.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.