FAQs for Using Lithium-ion Batteries with a UPS
Schneider Electric · Patrick Donovan, Martin Zacho
A Schneider Electric question-and-answer primer (WP 231, 2018, Revision 1) comparing Li-ion with VRLA in UPS systems on energy density, life, recharge time, footprint and cost.
On this page
Overview
The paper is a question-and-answer primer on using lithium-ion rather than valve-regulated lead-acid (VRLA) batteries in UPS systems. It compares the technologies on energy density, calendar and cycle life, recharge time, footprint, weight, cost and TCO, and summarises the six common Li-ion chemistries and cell packaging formats. Typical UPS cell ranges are Li-ion 70-260 Wh/kg, 10-15 year calendar life, over 1,000 cycles and 1/2-1 h recharge, against VRLA 15-50 Wh/kg, 4-6 years, 200-400 cycles and 6-12 h recharge.
On cost, an installed Li-ion system is roughly 1.2 to 2 times VRLA for the same power and runtime (as of 2018), down from about 10x a few years earlier. Over 15 years VRLA would likely be replaced 2-3 times versus none or one for Li-ion, and Li-ion UPS TCO is 10-40% lower than VRLA over 10 years (as of 2016). Li-ion systems take 50-80% less floor space and weigh 60-80% less. Charge efficiency is about 90% for Li-ion versus 80-85% for lead-acid, but BMS consumption makes total operating losses similar; the lead recycling rate is 99%.
Safety is addressed through thermal runaway susceptibility and the mandatory cell-level battery management system (BMS). Li-ion cycle life is often specified at 40 C versus 20-25 C for lead-acid, and keeping batteries near 25 C helps realise full runtime. Recommended storage is at 15 C and 20-40% state of charge, and Li-ion is not hot-swappable. Li-ion reaches 100% state of charge in 30 min to 1 h if the UPS charger can supply it, 5-10 hours sooner than lead-acid. The paper also covers UPS compatibility, recyclability, lifecycle carbon and IATA transport classes.
Key points
- Li-ion: 70-260 Wh/kg, 10-15 year calendar life, >1,000 cycles, 1/2-1 h recharge; VRLA: 15-50 Wh/kg, 4-6 years, 200-400 cycles, 6-12 h.
- Installed Li-ion cost is roughly 1.2-2x VRLA (2018), down from about 10x a few years earlier.
- Over 15 years VRLA is replaced 2-3 times versus none or one for Li-ion; Li-ion TCO 10-40% lower over 10 years (2016).
- Li-ion takes 50-80% less floor space and weighs 60-80% less.
- Charge efficiency about 90% versus 80-85%, but BMS consumption makes total losses similar.
- Li-ion cycle life is often specified at 40 C; near 25 C helps full runtime.
- Storage at 15 C and 20-40% state of charge; Li-ion is not hot-swappable.
- Li-ion reaches 100% in 30 min-1 h, 5-10 h sooner than lead-acid; lead recycling rate 99%.
Using it in design
- Battery catalog: chemistry (VRLA, LFP, NMC, LMO, NCA, LTO, LCO), specific energy, design and cycle life, rated temperature, footprint and weight per kWh, recharge time and compatible UPS models.
- Block Li-ion cabinets on a UPS not listed as compatible; warn that Li-ion is not hot-swappable for maintenance planning.
- Flag battery-room ambient above the chemistry's rated temperature and recommend 25 C for full runtime.
- In layout use the 50-80% footprint reduction and lighter floor loading; trigger a fire-protection and thermal-runaway review (NFPA 855, IEC 62619); in the TCO tool use replacement intervals (VRLA 4-6 yr, Li-ion 10-15 yr) and space value.
Monthly newsletter · free
Keep your reading list current
Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.
SoSo CAD
Review your power design in SoSo CAD
Inspect supply paths, equipment loads and UPS failure scenarios in one model.
Request a demo
Who should read it
Design engineers and procurement teams choosing UPS battery technology.
Related standards
- IEC 62619
- UL 1973
- UL 9540A
- NFPA 855
- IEC 62040-1
- IATA Dangerous Goods Regulations
Publication details
- Authors
- Patrick Donovan; Martin Zacho
- Publisher
- Schneider Electric
- Year
- 2018
- Document number
- WP 231
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only — the publisher’s terms apply to the original document
Citation
Patrick Donovan; Martin Zacho (2018). FAQs for Using Lithium-ion Batteries with a UPS. Schneider Electric. WP 231. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_VAVR-A5VTU5_EN
Events on this subject
- Electricity Eurasia 2027
- The smarter E Europe (Intersolar Europe, ees Europe, Power2Drive, EM-Power)
- Data Centre World Paris
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.