White paperFree to read2022

Best Practices to Deploy Sustainable and Resilient Data Centers at Scale at the Network Edge

Schneider Electric · Paul Lin, Steven Carlini et al.

Schneider Electric WP 80 (2022) is a planning guide for small, numerous and mostly unstaffed network-edge data centres. It is a decision framework by site type, not a sizing reference.

On this page

Overview

The paper splits the network edge into three classes: legacy telco rooms, distributed cloud sites and future multi-access edge computing (MEC) sites. Table 1 gives typical rack densities for each: legacy telco below 5 kW/rack, distributed cloud 3-30 kW/rack and MEC 3-20 kW/rack. All three are typically a few racks with no medium voltage, limited low voltage and UPS, and no genset. Power type also varies: -48 V DC for telco, AC for distributed cloud, and AC, -48 V DC or hybrid for MEC.

The authors list seven scaling challenges, among them diverse equipment, limited space, harsh outdoor environments, poor PUE, lack of on-site staff and cyber exposure. Three environments are defined: IT, commercial and office, and industrial and harsh. Harsh sites may need NEMA 4 and IP 65 rated enclosures. On efficiency, today's edge sites run an annual PUE of about 2.0 because of legacy loads near 1 kW per rack, against as low as 1.1 for core cloud.

Recommended practice starts with lithium-ion rather than VRLA batteries behind UPSs and rectifiers: typically 10 years of life, embedded monitoring and tolerance of temperatures above 40 °C. Critical sites should have redundant power and cooling for concurrent maintainability. Air or liquid cooling is chosen by density and environment, prefabricated modules and wall-mount enclosures are paired with physical security, and the paper expects IEC 62443-aligned cybersecurity plus DCIM and sustainability software.

The text also relays Schneider forecasts: 7.5 million new micro data centres by 2025 and, by 2040, a peak-power footprint that could reach 192 GW with energy above 1,679 TWh. Citing integrator data, it adds that pre-configured integrated solutions can cut field engineering cost by 25% to 40%. These are vendor and cited-source projections, and as a vendor white paper the document is best read as guidance rather than neutral evidence.

Key points

  1. Typical rack density: legacy telco below 5 kW/rack, distributed cloud 3-30 kW/rack, MEC 3-20 kW/rack.
  2. Power: telco -48 V DC, distributed cloud AC, MEC AC/-48 V DC/hybrid; distributed cloud may use inverters with 2-4 hours of battery.
  3. Harsh environments may need NEMA 4 and IP 65 enclosures.
  4. Today's network-edge sites run an annual PUE around 2.0, versus as low as 1.1 for core cloud; 5G edge uses three times the energy of 4G on average.
  5. Lithium-ion batteries: typically 10 years life, embedded monitoring, tolerance above 40 °C.
  6. Integrated pre-configured solutions can cut field engineering 25-40% and maintenance 7%, and raise order processing speed 20%.
  7. By 2040 edge peak power could reach 192 GW and energy over 1,679 TWh (Schneider forecast).

Using it in design

  • Add site type (legacy telco, distributed cloud, MEC), environment class and power type (AC, -48 V DC, hybrid) to the project template.
  • Require an IP65/NEMA 4 rated enclosure and self-contained cooling for any harsh-environment site.
  • Warn when rack density falls outside the typical band of the chosen site type.
  • For genset-free sites, make battery runtime an explicit input and default to lithium-ion.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Compare the cost of design decisions

Evaluate equipment costs, energy expenses and total cost of ownership (TCO) using your inputs and assumptions in SoSo CAD.

Request a demo
CAPEX and TCO estimates in the SoSo CAD cost workspace

Who should read it

Design engineers and infrastructure owners planning many small, unstaffed edge or telco sites.

Related standards

  • IEC 62443
  • ANSI/TIA-942
  • IEC 60529
  • NEMA 250
  • NEBS
  • ETSI EN 300 019

Publication details

Authors
Paul Lin; Steven Carlini; Victor Avelar; Andres Vasquez
Publisher
Schneider Electric
Year
2022
Document number
WP 80
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

Paul Lin; Steven Carlini; Victor Avelar; Andres Vasquez (2022). Best Practices to Deploy Sustainable and Resilient Data Centers at Scale at the Network Edge. Schneider Electric. WP 80. https://download.schneider-electric.com/files?p_Doc_Ref=SPD_WP80_EN

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.