Technical guideFree to read2025

Farklı Otomatik Söndürme Sistemlerinin Birbirleriyle Karşılaştırılması

Original title Farklı Otomatik Söndürme Sistemlerinin Birbirleriyle Karşılaştırılması (Comparison of different automatic fire suppression systems)

TMMOB Makina Mühendisleri Odası (MMO) · Gökhan Balık

Gökhan Balık's TESKON 2025 paper compares wet-pipe sprinklers, double-interlock pre-action sprinklers, water mist and clean-agent systems on 12 criteria in a colour-coded matrix.

On this page

Overview

This paper by Gökhan Balık appears in the proceedings of the 16th National Installation Engineering Congress (TESKON 2025), held in Izmir (p. 1324), and was published by the Chamber of Mechanical Engineers of TMMOB. It compares wet-pipe sprinklers, double-interlock pre-action sprinklers, wet-pipe water mist, double-interlock pre-action water mist and clean-agent systems against 12 criteria in a colour-coded matrix, rated on a five-level scale from 'highest' to 'lowest'.

The author bases the assessment on his own experience and expert opinion, which means the method rests on qualitative judgement and not on measurement or testing. The conclusions are that wet-pipe sprinklers and wet-pipe water mist are the most reliable extinguishers. The double-interlock pre-action options drop one level in extinguishing reliability because water release also depends on the detection system.

Clean-agent systems rank lowest for extinguishing reliability: success depends on enclosure integrity and the system is single discharge. Clean agents also carry high first and refill costs, and certain agents face regulatory pressure. Water mist's higher cost mainly reflects tanks and pumps; where this equipment is not otherwise required, its cost can approach that of sprinklers. This distinction shows that, when choosing between water and gaseous suppression in data halls, cost is more than just the first investment.

Costs and maintenance burdens are discussed for each option. TS EN 12845, NFPA 13, TS EN 14972-1 and TS EN 15004-1 are named as related standards. Because the matrix rests on the author's experience, the results give a direction; for a specific facility the decision should be made together with local regulation and the official standards. The paper's value is that it presents the trade-offs in a form that carries directly into data-hall suppression choices.

Key points

  1. Five options are compared on 12 criteria with a five-level ranking from 'highest' to 'lowest'.
  2. Wet-pipe sprinklers and wet-pipe water mist are judged the most reliable extinguishers.
  3. Double-interlock pre-action options drop one level in extinguishing reliability because water release also depends on the detection system.
  4. Clean-agent systems rank lowest for extinguishing reliability: success depends on enclosure integrity and the system is single discharge.
  5. Clean agents carry high first and refill costs and some agents face regulatory pressure.
  6. Water mist's higher cost mainly reflects tanks and pumps; where not otherwise required its cost can approach sprinklers.
  7. The assessment is based on the author's experience and expert opinion.
  8. Related standards: TS EN 12845, NFPA 13, TS EN 14972-1 and TS EN 15004-1.

Using it in design

  • Provide a suppression-option selector for white space, UPS/battery and electrical rooms showing reliability, water-damage risk, enclosure-integrity dependency and cost.
  • If a clean-agent system is chosen, add an enclosure-integrity test as a required entry.
  • Consider recommending a backup sprinkler or water-mist layer where local code requires it.
  • Use the comparison as qualitative guidance and verify the final choice against the relevant standards and regulation.

Monthly newsletter · free

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.

SoSo CAD

Bring standards pre-checks into your project

Review model-based TS EN 50600 and Tier pre-checks, missing inputs and items requiring engineering review in SoSo CAD.

Request a demo
Selected rule packs and findings in the SoSo CAD standards panel

Who should read it

Mechanical and fire-safety engineers and consultants selecting fire suppression for data centres.

Related standards

  • TS EN 12845
  • NFPA 13
  • TS EN 14972-1
  • TS EN 15004-1

Publication details

Authors
Gökhan Balık
Publisher
TMMOB Makina Mühendisleri Odası (MMO)
Year
2025
Document number
TESKON 2025 Bildiriler Kitabı, s. 1324
Event
16. Ulusal Tesisat Mühendisliği Kongresi (TESKON 2025), İzmir
Document language
English
Source type
Industry body
Access
Free to read
Licence
Copyright retained; citation only — the publisher’s terms apply to the original document

Citation

Gökhan Balık (2025). Farklı Otomatik Söndürme Sistemlerinin Birbirleriyle Karşılaştırılması (Comparison of different automatic fire suppression systems). TMMOB Makina Mühendisleri Odası (MMO). TESKON 2025 Bildiriler Kitabı, s. 1324. 16. Ulusal Tesisat Mühendisliği Kongresi (TESKON 2025), İzmir. https://mmoteskon.org/images/dosya/teskon-2025-bildiriler-kitabi-02.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.