Data Center Water Treatment: Why Liquid Cooling Still Relies on Filtration
Original title Data Center Water Treatment for Liquid Cooling
Amiad Water Systems
An August 2026 Amiad article arguing that facility water fouls CDU plate heat exchangers in direct-to-chip cooling, and recommending disc filtration of 5-15% of cooling-tower flow in a side stream down to 55 μm.
On this page
Overview
The article argues that direct-to-chip liquid cooling protects processors at the rack but does not remove the need for facility water treatment. Heat passes from the technology cooling system (TCS) through the CDU plate heat exchangers into the external facility cooling system (FCS). The FCS loop is exposed to dust, sand, silt and pollen pulled in by cooling towers, and evaporation concentrates these solids.
Accumulation creates three risks: an insulating layer that cuts heat-transfer efficiency, under-deposit corrosion and flow restriction in narrow exchanger channels. The article gives the PUE and WUE definitions and links these risks to PUE degradation and overheating.
The solution presented is the vendor's DATA Klin system: diagonally grooved Spin Klin NOVA discs form a three-dimensional depth-filtration matrix that captures particles down to 55 μm, runs on a live side-stream loop treating 5-15% of the main circulating flow and backwashes pods in sequence. The construction is fully polymeric.
It is vendor content and illustrates cooling-tower side-stream filtration with a Texas gas turbine plant (25-micron screen, 700 GPM skid; two skids and 1,400 GPM at the new plant). Cyclonic separators are said to be less effective on light organic particles, and sand filters to need space and backwash water.
Key points
- In liquid cooling, heat passes from the TCS through CDU plate heat exchangers to the FCS, which is exposed to tower-borne contamination.
- Three risks: insulating layer (efficiency loss), under-deposit corrosion and CDU flow restriction.
- PUE = total annual facility energy / IT annual energy; WUE = annual site water use (litres) / IT annual energy (kWh).
- DATA Klin works on a live side-stream loop treating 5-15% of the main flow.
- The disc filter captures particles down to 55 μm by 3D depth filtration.
- Backwash cleans pods in sequence, so cooling water flow to the CDU is maintained.
- Fully polymeric construction resists biocides and scale inhibitors.
- The example project used a 25-micron screen at 700 GPM, and two skids at 1,400 GPM at the new plant.
Using it in design
- Put a tower side-stream filter on the facility side of the CDU; a closed TCS does not remove the need for FCS filtration.
- Start sizing side-stream flow at 5-15% of main flow and plan for backwash water to join the tower blowdown.
- Select filter fineness against the CDU plate heat exchanger channel gap and the manufacturer's requirement.
- If a cyclonic separator or sand filter is considered, compare organic load, footprint and backwash water.
- Choose a low pressure-drop filter and carry the pump energy into the PUE calculation.
Who should read it
Mechanical and water-treatment engineers designing tower water and CDU facility loops for liquid-cooled sites.
Document contents
- The Thermodynamics of the Primary Boundary: TCS to FCS
- The Fouling Threat to Boundary Heat Exchangers
- Amiad's Solution: DATA Klin Polymeric Disc Filtration
- Key Operational Advantages of DATA Klin
- Parallel Industrial Validation: Cooling Tower Sidestream Filtration
- Achieving Long-Term Operational Resilience
- FAQ About Data Center Water Treatment and Liquid Cooling
Publication details
- Authors
- Amiad Water Systems
- Publisher
- Amiad Water Systems
- Year
- 2026
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Amiad Water Systems (2026). Data Center Water Treatment for Liquid Cooling. Amiad Water Systems. https://amiad.com/blog/data-center-water-treatment-liquid-cooling/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.