Antifrogen PG 25 technical data
Original title Antifrogen PG 25: Technical Data
Clariant
Clariant's Antifrogen PG 25 product page gives a 25% v/v propylene glycol, H-OAT-inhibited mix for direct-to-chip cooling with a -11 °C freezing point, 0.471 W/(m K) thermal conductivity and 2.88 mm²/s viscosity.
On this page
Overview
The page presents the technical table for Antifrogen PG 25, a physiologically harmless monopropylene glycol (MPG) based fluid prepared for data centre direct-to-chip cooling. The product is a clear blue liquid of 25% v/v propylene glycol with corrosion inhibitors, protected by Hybrid-OAT (H-OAT).
The table gives density of 1.024 g/cm³ at 20 °C, kinematic viscosity of 2.88 mm²/s, thermal conductivity of 0.471 W/(m K) and specific heat of 3.92 kJ/(kg K). Freezing point is -11 °C by ASTM D1177 and boiling point 103 °C by ASTM D1120. The pH is about 8.8 (33% v/v in deionised water).
The page positions the product for enhanced safety requirements with a low toxicity profile and highlights an optimised glycol concentration giving -10 °C antifreeze protection. Concentrates and custom concentrations are available on request.
Key points
- Composition: 25% v/v propylene glycol with corrosion inhibitors; clear blue liquid.
- Density 1.024 g/cm³ at 20 °C (DIN 51757).
- Freezing point -11 °C (ASTM D1177); boiling point 103 °C (ASTM D1120).
- Kinematic viscosity 2.88 mm²/s at 20 °C.
- Thermal conductivity 0.471 W/(m K) and specific heat 3.92 kJ/(kg K) at 20 °C.
- pH about 8.8 (33% v/v in deionised water); reserve alkalinity 1.4 mL 0.1 M HCl (ASTM D1121).
- Corrosion protection by Hybrid-OAT (H-OAT); low toxicity profile.
Using it in design
- When choosing propylene glycol for safety or environmental reasons, balance it against the higher viscosity (2.88 vs 1.75 mm²/s) and lower thermal conductivity (0.471 vs 0.514 W/(m K)) than EG 20.
- Use the 2.88 mm²/s viscosity in pump and cold plate pressure drop calculations.
- With a -11 °C freezing point, ask for a higher concentration at sites with low outdoor temperatures.
- Check H-OAT inhibitor chemistry for compatibility with loop materials and do not mix it with other inhibitor classes.
Who should read it
Mechanical designers and operations engineers selecting propylene-glycol-based coolant for direct-to-chip loops.
Document contents
- Features
- Technical Data
- Documentation
Publication details
- Authors
- Clariant
- Publisher
- Clariant
- Year
- 2026
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Clariant (2026). Antifrogen PG 25: Technical Data. Clariant. https://www.clariant.com/en/Solutions/Products/2026/04/09/10/13/ANTIFROGEN-PG-25
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.