Antifrogen EG 20 technical data
Original title Antifrogen EG: Technical Data
Clariant
Clariant's Antifrogen EG 20 product page gives a 20% v/v ethylene glycol, OAT-inhibited mix for direct-to-chip cooling with a -10 °C freezing point, 0.514 W/(m K) thermal conductivity and 3.91 kJ/(kg K) specific heat.
On this page
Overview
The page presents the technical table for Antifrogen EG, a monoethylene glycol (MEG) based fluid prepared for data centre direct-to-chip cooling. The product is a clear yellow liquid of 20% v/v ethylene glycol with corrosion inhibitors, protected by Organic Acid Technology (OAT).
The table gives density of 1.030 g/cm³ at 20 °C, kinematic viscosity of 1.75 mm²/s, thermal conductivity of 0.514 W/(m K) and specific heat of 3.91 kJ/(kg K). Freezing point is -10 °C by ASTM D1177 and boiling point 103 °C by ASTM D1120. The pH is about 8 (33% v/v in deionised water).
The page highlights an optimised glycol concentration giving -10 °C antifreeze protection for direct-to-chip applications with rising processor heat loads. Concentrates and custom glycol concentrations are available on request. Full product documentation requires registration.
Key points
- Composition: 20% v/v ethylene glycol with corrosion inhibitors; clear yellow liquid.
- Density 1.030 g/cm³ at 20 °C (DIN 51757).
- Freezing point -10 °C (ASTM D1177); boiling point 103 °C (ASTM D1120).
- Kinematic viscosity 1.75 mm²/s at 20 °C.
- Thermal conductivity 0.514 W/(m K) and specific heat 3.91 kJ/(kg K) at 20 °C.
- pH about 8 (33% v/v in deionised water); reserve alkalinity 1.0 mL 0.1 M HCl (ASTM D1121).
- Corrosion protection by Organic Acid Technology (OAT).
Using it in design
- Size flow against ΔT in the coolant calculation with the 20 °C values (specific heat 3.91 kJ/(kg K), density 1.030 g/cm³).
- Compare the -10 °C freezing point with outdoor and transport conditions; ask for a higher concentration for lower temperatures.
- Use viscosity and thermal conductivity as inputs to cold plate pressure drop calculations.
- Check OAT inhibitor chemistry for compatibility with cold plate and loop materials (copper, aluminium, seals) and do not mix it with other glycol or inhibitor classes.
Who should read it
Mechanical designers and operations engineers selecting coolant for direct-to-chip loops.
Document contents
- Features
- Technical Data
- Documentation
Publication details
- Authors
- Clariant
- Publisher
- Clariant
- Year
- 2026
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Clariant (2026). Antifrogen EG: Technical Data. Clariant. https://www.clariant.com/en/Solutions/Products/2026/04/09/12/14/Antifrogen-EG-20
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.