Technical guideFree to read2026

The role of polymer piping in direct liquid cooling (GF Piping Systems white paper)

Original title The role of polymer piping in direct liquid cooling

GF Piping Systems · Charles Freda, Eveliina Juntunen

A Georg Fischer white paper explaining that polymer (beta-nucleated polypropylene) piping in direct liquid cooling releases less corrosion particulate than stainless steel, that infrared welds reach 96% of base-material strength and that embodied carbon falls 51%.

On this page

Overview

The white paper states that liquid has about 3,500 times the volumetric thermal capacity of air, that present-day air cooling handles up to 90 kW per rack (with diminishing efficiency) while liquid cooling reliably supports well above 100 kW. The common coolant is a 25% propylene glycol mix (PG25); a table compares thermal conductivity (air 0.025, water 0.598, PG25 0.478 W/(m K)), specific heat (1.01, 4.18, 3.98 kJ/(kg K)) and viscosity (0.0182, 1.00, 2.86 cP) at 20 °C.

The piping materials section says DLC operating conditions stay within the boundary parameters for polymers and that stainless steel SS304/SS316 replaced copper for corrosion and liquid purity reasons. For a 70 m d160 loop at ΔT 10 °C, deionised water gives about 13% lower pressure loss and about 16% lower pumping power than PG25. In a ten-year example, one metre of stainless pipe can release 35 to 1,500 mm³ of particles depending on corrosion rate while polymer releases none; today's filtration norm is 25-50 µm and is expected to tighten to 10 µm.

A surface smoothness section notes that laminar flow is proportional to the fourth power of diameter; in a DN50 stainless pipe, if roughness grows from 0.015 mm to 0.03 mm over 10 years, flow area drops 4% and flow 8% (240 to 222 l/min). Polypropylene is presented for chemical resistance, mechanical robustness and resilience to chlorine, copper and salt.

Infrared (IR) welding is contactless and uses no filler or shielding gas, so no contamination enters the liquid path; the weld retains up to 96% of base-material strength (DVS 2203-5; minimum required 60%). On sustainability, replacing SCH10 stainless steel (4 inch) with PP-H d160/SDR17.6 in the Schneider EcoStruxure reference design cuts embodied carbon by 51% at system level and makes the system 64% lighter. It is a manufacturer white paper and the results rest on the manufacturer's example calculations.

Key points

  1. Liquid has about 3,500 times the volumetric thermal capacity of air; air cooling handles up to 90 kW per rack, liquid cooling above 100 kW.
  2. PG25 properties at 20 °C: conductivity 0.478 W/(m K), specific heat 3.98 kJ/(kg K), viscosity 2.86 cP.
  3. 70 m, d160 loop, ΔT 10 °C: deionised water gives about 13% less pressure loss and about 16% less pumping power than PG25.
  4. Over ten years one metre of stainless pipe can release 35 to 1,500 mm³ of corrosion particles; corrosion rates 0.02-0.57 µm/year (water) and 0.87 µm/year (SS304, humid).
  5. The filtration norm is 25-50 µm today and expected to tighten to 10 µm.
  6. In a DN50 stainless pipe, roughness growth from 0.015 to 0.03 mm over 10 years cuts flow 8% (240 to 222 l/min).
  7. IR welds reach 96% of base-material strength (minimum 60%, DVS 2203-5) with no filler or gas.
  8. The polymer system cuts embodied carbon by 51% and weight by 64% (PP-H d160/SDR17.6 vs SS SCH10 4 inch, stage A1).

Using it in design

  • Weigh DLC supply and return pipe material against corrosion particle release and cold plate channel clogging risk; design filter fineness for 25-50 µm now and 10 µm later.
  • Use coolant viscosity in pump power calculations: where deionised water can replace PG25, pressure loss can fall about 13% and pump power about 16%.
  • Size pipe diameter with an allowance for 10 years of roughness growth and bore narrowing; in laminar flow, flow scales with D^4.
  • Specify IR welding (or an equivalent contactless method), weld bead inspection and non-destructive testing for welded joints.
  • If embodied carbon and weight targets exist, compare polymer and stainless steel at system level; check prefabricated module weight limits.
  • When using polymer pipe, verify that operating temperature and pressure stay within manufacturer limits.

Who should read it

Mechanical engineers, contractors and sustainability leads designing DLC facility water (FWS) and technology cooling (TCS) piping.

Document contents

  1. Liquid cooling: an efficient answer to rising thermal loads
  2. Types of liquid cooling
  3. Empowering sustainable cooling with reliable liquid conveyance in DLC
  4. Polypropylene: piping material tailored for critical industrial applications
  5. Precision welding: the key to reliable, leak-proof systems
  6. Growing emphasis on sustainability
  7. From potential to practice
  8. Conclusion: future-proof your cooling infrastructure

Publication details

Authors
Charles Freda; Eveliina Juntunen
Publisher
GF Piping Systems
Year
2026
Document number
GFDO_WP_00001a_EN (07.26)
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Charles Freda; Eveliina Juntunen (2026). The role of polymer piping in direct liquid cooling. GF Piping Systems. GFDO_WP_00001a_EN (07.26). https://www.gfps.com/content/dam/gfps/com/whitepapers/en/gfps-whitepaper-direct-liquid-cooling-en.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.