UltraRack SR and NSR Series IT Server Racks (Austin Hughes Brochure)
Original title Austin Hughes UltraRack SR rack brochure
Austin Hughes
Austin Hughes' UltraRack brochure: SR series 1500 kg and NSR series 1000 kg static load; 42U-52U, 600 and 800 mm widths, 80% perforated doors, and blanking and sealing kits for one-way airflow.
On this page
Overview
The brochure presents the SR and NSR series of Austin Hughes' UltraRack family of 19-inch IT server racks. The series target data centre, banking, retail, healthcare, telecom, government and academic environments. The product is stated as RoHS3 and REACH compliant, the design and manufacturing process meets BSi ISO 9001 and ISO 14001, and the racks are built to the EIA-310 standard.
The SR series has a 1500 kg static load capacity and the NSR series 1000 kg. Up to 4 rack PDUs in the SR and 2 in the NSR mount without tools. Both series have 80% perforated front and split rear doors, tool-less 19-inch rail adjustment, quick-release doors and easy adaptation to aisle containment. The SR standard configuration includes split side panels, brush cable entries, a cable management tray, heavy-duty casters and adjustable feet, a dynamic earthing kit and a standard RAL 9005 black finish.
The size table gives 42U, 45U, 47U and 52U heights in 600 and 800 mm widths with overall depths of 972, 1072 and 1200 mm (effective depths 900, 1000 and 1128 mm respectively). Overall height of the 42U rack with casters is 2035 mm; for 52U it is 2480 mm. The airflow section describes air blanking panels (1U plastic, 1-8U steel) and gap sealing kits for creating one-way airflow in the rack and within aisle containment systems.
The document is a vendor brochure; it gives no thermal performance, airflow or power density measurements. Capacity claims are vendor values.
Key points
- SR series 1500 kg, NSR series 1000 kg static load capacity.
- Tool-less mounting of up to 4 rack PDUs in the SR and 2 in the NSR.
- 42U, 45U, 47U, 52U heights; 600 and 800 mm widths; overall depth 972, 1072 or 1200 mm (effective 900, 1000, 1128 mm).
- Overall height with casters is 2035 mm for 42U and 2480 mm for 52U.
- Front and split rear doors have a honeycomb pattern with up to 80% perforation.
- Airflow accessories: 1U plastic and 1-8U steel blanking panels, rack-to-floor seal kit and gap sealing kits.
- EIA-310 compliant; RoHS3 and REACH compliance stated by an SGS accredited laboratory; ISO 9001 and ISO 14001.
- Standard colour RAL 9005 black, optional RAL 9016 white; keyed-lock upgrade for up to 500 individual keys.
Using it in design
- Compare the rack load class (1000 or 1500 kg) with the loaded rack weight and verify floor loading separately for racks on casters.
- Choose depth from server and cable requirements; do not confuse effective depth (900-1128 mm) with overall depth.
- In airflow design put blanking panels and gap sealing kits in the specification; use the rack-to-floor seal to cut bypass air.
- Check the number of rack PDUs (2 or 4) against A/B feed and cabinet power.
- Assess 80% perforated doors against server intake airflow; verify heat load per cabinet separately at high density.
Who should read it
Designers and procurement engineers selecting and specifying racks for server rooms and data centres.
Document contents
- UltraRack Overview
- SR Rack
- NSR Rack
- Door and Cladding Options
- Airflow
Publication details
- Authors
- Austin Hughes
- Publisher
- Austin Hughes
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Austin Hughes Austin Hughes UltraRack SR rack brochure. Austin Hughes. https://www.austin-hughes.com/wp-content/uploads/2020/05/CA-UR.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.