Technical guideFree to read2026

Datwyler Rack Solutions Catalogue 2026

Datwyler

Datwyler's 2026 catalogue lists server, network and wall-mount rack families (DSRP, DSRS, DNRP, DNRS, DNRF, DWMR) with maximum loads: Standard 800 kg, Premium 2000 kg, wall-mount 30-40 kg.

On this page

Overview

The catalogue presents Datwyler IT Infra's server racks, network racks and wall-mount racks with accessories. Its contents cover server racks, network racks, wall mount racks, and accessories for cable management, structure, ventilation and lighting, and PDU and rack monitoring, plus Smart Modular Data Centres (SMDCs) and bespoke solutions. The opening table compares families by type: Standard and Premium server racks come in 42U or 48U, and Premium network racks in 21, 27, 42 and 48U.

Load capacity differs markedly between families: 800 kg for Standard racks, 2000 kg for Premium racks and 30-40 kg for wall-mount racks. For example, the Premium DSRP server rack is 19-inch, 42U and 47U, 800 mm wide with 800, 1000 and 1200 mm depth options, built on a welded galvanised steel frame with perforated front and rear doors and 3-point locks; it is IP00 but can reach IP54 with the appropriate expansion and can be stacked up to 108U. Empty weights are listed as 122-152 kg for 42U and 144-160 kg for 47U.

The Standard DSRS family is 42U at 1978 mm high, 600 and 800 mm wide, 1000 and 1200 mm deep, with weights of 100-139 kg. The tables must be read by order code; different door and size combinations within one family carry separate order codes.

The catalogue also includes the single-rack SMDC (a self-contained mini data centre that combines cooling, power, monitoring and security in one solution and can be commissioned within a few hours) and PDU and monitoring accessories. The document is a manufacturer catalogue; load and dimension data should be confirmed against the order code.

Key points

  1. Maximum load capacity: Standard racks 800 kg, Premium racks 2000 kg, wall-mount 30-40 kg.
  2. Server racks are 42U or 48U; Premium network racks are 21, 27, 42 and 48U; wall-mount racks are 6, 9, 12, 15 or 18U.
  3. Premium DSRP: 42U (2005 mm) and 47U (2205 mm), 800 mm wide, 800, 1000 or 1200 mm deep; 42U empty weight 122-152 kg.
  4. DSRP is IP00, can reach IP54 with the appropriate expansion and is stackable up to 108U.
  5. Standard DSRS: 42U (1978 mm), 600 or 800 mm wide, 1000 or 1200 mm deep, 100-139 kg.
  6. Premium DNRP network rack 42U 2000 x 800 x 800 mm weighs 134-136 kg, and 800 x 1000 weighs 150 kg.
  7. Racks offer 1-point or 3-point locks and perforated or glass front doors.
  8. The DSRP has two brush-covered lateral cable entries (88 mm) and a ventilation opening for fans.
  9. The single-rack SMDC combines cooling, power, monitoring and security in one solution and can be commissioned in a few hours.

Using it in design

  • In rack selection, compare load capacity (800 or 2000 kg) with planned equipment weight; consider the Premium class for high-density AI racks.
  • Record the order code together with the size, door and colour combination; do not equate different sizes in one family under a single code.
  • Choose depth (800, 1000, 1200 mm) from the deepest equipment and cable bend allowance.
  • If IP54 or stacking is required, write the expansion kit and the 108U limit into the specification.
  • Add the rack weight (100-160 kg) to equipment weight in the floor load calculation.

Who should read it

Data-centre designers, procurement and infrastructure engineers planning rack, network and server layouts.

Document contents

  1. Rack solutions for every requirement
  2. Server racks
  3. Network racks
  4. Wall mount racks
  5. Accessories: cable management
  6. Accessories: structure
  7. Accessories: ventilation and lighting
  8. Accessories: PDU and rack monitoring system
  9. IT Solutions: Smart Modular Data Centres (SMDCs)
  10. Bespoke solutions

Publication details

Authors
Datwyler
Publisher
Datwyler
Year
2026
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Datwyler (2026). Datwyler Rack Solutions Catalogue 2026. Datwyler. https://static.datwyler-itinfra.com/assets/Downloads/DATWYLER_Rack_Solutions_Catalogue_2026.pdf?v=1779968014

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Redundancy scenarios in SoSo CAD

Compare normal operation with equipment failures and see served loads and capacity shortfalls in the same view.

Normal operation and failure scenario comparison in SoSo CAD

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.