UPCOM SoundProof Cabinets: Turkish Technical Catalogue

Original title UPCOM SoundProof Kabinetler Türkçe Teknik Katalog

UPCOM

UPCOM's catalogue of 19-inch soundproof SoundProof cabinets: 12U-42U, 650/700/750 mm widths, up to 400 kg distributed load, 1 or 2 thermostat-controlled fan modules, indoor use only.

On this page

Overview

The document is UPCOM Telekomünikasyon's 16-page Turkish technical catalogue for SoundProof cabinets. The family is 19-inch rack cabinets for indoor spaces where people are present, such as offices, clinics, bank branches, shop back offices and shared technical areas, with acoustic lining, locking and ventilation by thermostat-controlled fans. The catalogue names noise control, physical security and airflow as the three main needs the product addresses.

Common specifications are heights of 12U, 15U, 19U, 26U, 32U, 36U and 42U, widths of 650, 700 and 750 mm, depths of 650, 800 and 1000 mm, up to 400 kg of distributed load, a DKP sheet steel body with acoustic inner insulation, galvanised 19-inch rails, electrostatic powder paint, RAL 9005 black and 1 or 2 fan modules with a digital thermostat. Ten model codes fall into three families: compact (12-19U, 650x650 and 700x800 mm base), mid (26-32U) and full height (36-42U), the last two on a 750x1000 mm base.

The model table gives outer dimensions, fan groups and maximum inner depth. The 12-19U models have 1 module and 2 fans, with inner depth of 510 mm on the 650x650 mm base and 660 mm on the 700x800 mm base. The 26-42U models have 2 modules and 6 fans, with a maximum inner depth reference of 860 mm. The catalogue stresses that the inner depth reference does not guarantee usable space for the device chassis and rear cable connections, and that service and bend clearances must be checked separately.

On acoustics the catalogue gives no verified numeric dB reduction valid for all configurations and states explicitly that this value must be confirmed before quotation. Its selection checklist names filled U, deepest device, total heat load of continuously running devices (W/kW), noise sensitivity and installation and access conditions. SoundProof models do not replace IP-rated cabinets for outdoor use.

Key points

  1. Heights 12U, 15U, 19U, 26U, 32U, 36U, 42U; widths 650, 700, 750 mm; depths 650, 800, 1000 mm.
  2. Capacity up to 400 kg distributed load; DKP sheet steel body, acoustic inner insulation, RAL 9005 black.
  3. 12U-19U models have 1 fan module (2 fans); 26U-42U models have 2 fan modules (6 fans); digital thermostat.
  4. Maximum inner depth: 510 mm on 650x650 mm base, 660 mm on 700x800 mm base, 860 mm reference on 750x1000 mm base.
  5. Outer dimension examples: 12U 650 x 650 x 618 mm; 42U 750 x 1000 x 1950 mm.
  6. The catalogue gives no verified dB reduction valid for all configurations and asks for confirmation before quotation.
  7. Selection order: depth first, then heat load, then U capacity.
  8. Indoor use only; choose an IP-rated product family for outdoor sites.

Using it in design

  • In cabinet selection add spare U for future devices to the filled U count; compare the deepest device plus rear cable bend and service clearance with the maximum inner depth.
  • Heat builds up in a closed acoustic body: compute the total W/kW of continuously running devices and confirm with the manufacturer that the fan module and thermostat arrangement can reject it.
  • For the acoustic target (office, clinic, branch) request a numeric dB reduction in writing at quotation; do not take the catalogue wording as a guarantee.
  • Check the 400 kg distributed load limit for UPS and heavy devices; place heavy devices low.
  • Before installation check air movement around the cabinet, door swing, cable entry and delivery route.

Who should read it

IT designers and procurement specialists housing small-scale server and network equipment in shared spaces such as offices, branches and clinics.

Document contents

  1. Product Family
  2. Application Areas
  3. Acoustic Design: Noise Reduction and Airflow
  4. General Technical Specifications
  5. Comparison of 10 Models
  6. 12U, 15U, 19U Model Sheets
  7. 26U, 32U, 36U, 42U Model Sheets
  8. Selection Guide
  9. Technical Request Checklist

Publication details

Authors
UPCOM
Publisher
UPCOM
Year
Year not stated
Document language
Turkish
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

UPCOM UPCOM SoundProof Kabinetler Türkçe Teknik Katalog. UPCOM. https://www.upcom.com.tr/wp-content/uploads/2026/10/UPCOM_SoundProof_Kabinetler_Turkce_Teknik_Katalog-1.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Redundancy scenarios in SoSo CAD

Compare normal operation with equipment failures and see served loads and capacity shortfalls in the same view.

Normal operation and failure scenario comparison in SoSo CAD

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.