Triton Cabinet Catalogue 2023 (RMA and Data Centre Cabinet Series)
Original title Triton Catalogue 2023: RMA free-standing cabinets
Triton
Triton Pardubice's 2023 cabinet catalogue: 19-inch cabinets rated 400 to 1800 kg and a data centre section (1.2 m aisle, 80% perforated doors, floor feed with plenum return up to 30 kW per cabinet).
On this page
Overview
The catalogue is a multi-section product catalogue, dated December 2022, from the Czech manufacturer Tritón Pardubice, which has almost 30 years of history. Its sections include high-tech, free-standing, wall-mounted and special cabinets, data centres, cable trays and accessories. Free-standing series are split by load capacity: RMA and RZA 400 kg, RTA and RYA 1200/1500 kg, RDA server cabinet 1800 kg; RIE and RDE have IP54 dust and humidity protection, and RSX is a 19-inch open frame.
The RMA series has a welded construction, a door opening almost 180 degrees with reversible direction, and an optional swing frame with a 150 kg load capacity on 800 mm width. The recommended maximum load is 400 kg, protection is IP 20 and it is designed for office environments; it is not suited to outdoor use, explosion risk or humid surroundings. It has breakout-type cable openings in the top and bottom plates and an M8 central earthing point.
The data centre section covers cabinet arrangement and cooling principles. Cabinets are placed in two rows, usually 1,200 mm apart (two standard raised floor tiles); ANSI/TIA/EIA-942-A recommends a 1.2 m cold aisle width. Door perforation is 80% and other openings in the floor must be covered to keep static pressure. A contained cold aisle is built at 1.2 or 1.8 m width with glass sliding doors at the ends.
The catalogue also presents floor-feed cabinets, floor feed with plenum return, a closed modular solution with side cooling units, in-row cooling and intelligent PDU panels (16-64 A, single and three-phase). For the plenum-return solution, cooling of up to 30 kW per cabinet is stated. It is a product selection document: it holds product specifications and ordering tables rather than airflow, thermal test or independent performance data.
Key points
- Free-standing cabinet series by load capacity: RMA/RZA 400 kg, RTA/RYA 1200/1500 kg, RDA 1800 kg; RIE/RDE IP54.
- RMA recommended maximum load 400 kg, IP 20, office environment; optional 150 kg swing frame on 800 mm width.
- RMA doors open almost 180 degrees with changeable opening direction; M8 central earthing point.
- Cabinets are placed in two rows 1200 mm apart (two raised floor tiles); ANSI/TIA/EIA-942-A recommends a 1.2 m cold aisle.
- Doors are 80% perforated; cable entries and other openings in the raised floor must be covered to keep static pressure.
- A contained cold aisle is 1.2 m (two tiles) or 1.8 m (three tiles) wide with glass sliding doors at the ends.
- Floor feed with plenum return is stated to cool up to 30 kW per cabinet.
- Humidity under 30% risks static discharge and high humidity risks condensation; PDU panels are 16-64 A, single or three-phase.
Using it in design
- Select the cabinet load class (400, 1200/1500 or 1800 kg) against the loaded server and storage weight; consider RMA only for office conditions and loads under 400 kg.
- Plan a 1.2 m cold aisle (two tiles), consider a 1.8 m contained aisle at higher density, and seal tiles and cable entries.
- To keep hot air out of the room, compare the ceiling plenum return solution and its 30 kW per cabinet limit in cooling design.
- Choose cabinet and door perforation (80%) to match server intake airflow, and fit blanking panels in unused U spaces.
- Write a humidity control specification that keeps relative humidity from falling below 30%, and size PDU and environmental monitoring capacity with the cabinet count.
Who should read it
Designers and procurement engineers selecting cabinets, aisle containment and in-cabinet cooling for server rooms and data centres.
Document contents
- About Tritón
- Free-Standing Cabinets (RMA, RZA, RTA, RYA, RDA, RIE, RDE, RSX)
- Data Centers: Introduction
- Data Center Cooling Principles
- Power Distribution
- Accessories for Data Centers
- Hot/Cold Aisle
- Wall-Mounted Cabinets
- Special Cabinets
- Active Cooling
- Cable Management Systems
- Part Numbering System and Configurator
Publication details
- Authors
- Triton
- Publisher
- Triton
- Year
- 2023
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Triton (2023). Triton Catalogue 2023: RMA free-standing cabinets. Triton. https://triton-racks.com/wp-content/uploads/2023/01/Catalog-Triton-2023-EN.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.