SZB IT Server Cabinets (Product Data Sheet, 2025)
Original title SZB IT Server Cabinets: W-IT-42X010-4XAA-2-XXX
ZPAS
ZPAS data sheet for the SZB server cabinet: bolted frame, externally tested 1500 kg static load, 42U/1963 mm, 80% perforated doors, IP 20 and 105-128 kg weight.
On this page
Overview
The document is ZPAS S.A.'s two-page data sheet for SZB IT server cabinets, dated February 2025. It describes an ICT cabinet with a bolted frame (bottom plate, top plate, four posts) whose static load capacity is verified at 1500 kg by external testing. The frame, side panels, doors and mounting profiles are sheet steel, outriggers are zamak casting, and the protection degree is IP 20 per EN 60529.
The cabinet offers 42U of usable height (frame height 1963 mm), 600 or 800 mm width and 1000 mm depth. The front door is single-leaf and the rear door single or double-leaf, in RAL 7035 light grey or RAL 9005 black. Weight is 105 kg at 600 mm width (112 kg with a double-leaf rear door) and 125 kg at 800 mm (128 kg).
Functional features include 71 mm wide cable openings in the top and bottom plates that pass power cords with three-phase plugs, a ventilation perforation in the top plate, knock-out blanking plates, 15 mm deep 19-inch mounting profiles, an earthing bar, a 270 degree door opening angle, three-point locking and doors with 80% perforation. The cabinets suit row installation and cold/hot aisle (Data Box) creation. It is a product data sheet and contains no thermal performance or airflow figures.
Key points
- Bolted frame; static load capacity verified at 1500 kg by external testing.
- 42U usable height, frame height 1963 mm; width 600 or 800 mm, depth 1000 mm.
- Weight: 105 kg at 600 mm width (112 kg with double-leaf rear door), 125 kg at 800 mm (128 kg).
- Protection degree IP 20 (EN 60529); RAL 7035 or RAL 9005 powder paint.
- Doors are 80% perforated; front and rear doors open 270 degrees and the opening direction can be changed.
- 71 mm wide cable openings in the top and bottom plates pass cords with three-phase plugs.
- The cabinet is adapted to row installation and to cold/hot aisle (Data Box) creation.
- Four levelling feet and the option to stand directly on the floor; the standard set includes an earthing bar and door/panel earthing conductors.
Using it in design
- Compare rack load against the 1500 kg static capacity and the floor load capacity; add the cabinet's own 105-128 kg to the floor load.
- Compare the 80% perforated doors with the server intake airflow requirement; verify the full cabinet density separately if extra cooling is needed at high density.
- If aisle containment is planned, select cabinets arranged in rows suited to aisle enclosure; close unused openings with the knock-out blanking plates.
- Check on site that three-phase PDU cords pass through the 71 mm cable openings.
- Note that IP 20 protection suits only indoor halls without dust or water risk.
Who should read it
Data-centre and structured cabling designers selecting and specifying server room cabinets.
Document contents
- Product Description
- Technical Data
- Configuration
- Reference Chart
- Design and Sections
Publication details
- Authors
- ZPAS
- Publisher
- ZPAS
- Year
- 2025
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
ZPAS (2025). SZB IT Server Cabinets: W-IT-42X010-4XAA-2-XXX. ZPAS. https://doc.zpas.pl/2_EN/DATA_SHEETS/SZB_IT_Network_and_Server_Cabinets/W-IT-42X010-4XAA-2-XXX.2025-02.EN.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.