Belimo & Direct-to-Chip Cooling Technologies: Differential Pressure Control for Liquid Cold Plates
Belimo · Jason Tables
Belimo's 2025 article contrasts constant total flow with constant differential pressure control when servers are added or removed, and states the external sensor requirement of Energy Valve 4.2.
On this page
Overview
This manufacturer article addresses the choice of control strategy in the loop that feeds liquid cold plates in direct-to-chip racks. The question is how the loop behaves when a server is added or removed, and two approaches are compared: holding total flow constant and holding differential pressure constant.
The constant differential pressure option is described with Energy Valve 4.2 and needs a differential pressure sensor that connects to the valve and is not included with the product. In the example, when a server is removed the valve reduces flow to restore the set pressure difference, so total rack flow is not held at one fixed value.
The article stands apart from Belimo's existing Energy Valve brochure by covering the software version and the external sensor requirement. It is useful for designers who need to understand flow response in racks whose server count changes.
Key points
- The comparison is between constant total flow and constant differential pressure control.
- The constant pressure difference option is described with Energy Valve 4.2.
- It needs a differential pressure sensor connected to the valve and not included in the product.
- When a server is removed the valve reduces flow to restore the set pressure difference.
- Total rack flow is not held at a single fixed value in this mode.
Using it in design
- For racks with changing server counts, choose the control mode (constant flow or constant ΔP) and verify it in acceptance testing with add and remove scenarios.
- List the differential pressure sensor and its location separately; it is not part of the valve package.
- Design pump control and CDU for the lower total flow that results when a server is removed in constant ΔP mode.
- State the valve software version (4.2) in the specification.
Who should read it
Mechanical engineers designing D2C rack hydraulics and CDUs, and BMS or controls integrators.
Publication details
- Authors
- Jason Tables
- Publisher
- Belimo
- Year
- 2025
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Jason Tables (2025). Belimo & Direct-to-Chip Cooling Technologies: Differential Pressure Control for Liquid Cold Plates. Belimo. https://www.belimo.com/br/en_US/blog/belimo-direct-to-chip-cooling-technologies-differential-pressure-control-for-liquid-cold-plates
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
