Direct-to-Chip Liquid Cooling Treatment Helps DOE National Laboratory Improve System Performance (ChemTreat case study)

Original title Direct-to-Chip Liquid Cooling Treatment Helps DOE National Laboratory Improve System Performance

ChemTreat

ChemTreat case study: at a DOE national laboratory, cooling towers stayed deposit-free for over 10 years, aluminium corrosion fell from >10 mpy to <0.1 mpy, and a closed-loop conversion saved 34 million gallons of water a year.

On this page

Overview

The case study explains that US Department of Energy (DOE) national laboratories run extensive direct-to-chip liquid cooling and HPC systems that need customised water treatment to run at peak efficiency. One laboratory had performance problems in its open recirculating, closed-loop and HPC cooling systems; ChemTreat addressed four items with technical and analytical support.

In the open tower systems, mineral deposits reduced heat transfer and raised corrosion and microbiological activity; a polymeric dispersant and corrosion-inhibitor programme removed them and the systems have stayed deposit-free with good corrosion and microbiological control for over 10 years. A newly built HPC failed speed testing because its cooling loops were fouled with biological growth, mineral scale and additives; after the CL2001 programme, designed for CPU applications and avoiding film inhibitors such as silicates, it passed.

A closed loop with aluminium equipment suffered fouling events causing under-deposit corrosion; with the neutral-pH multi-metal FlexPro inhibitor the water became free of suspended solids and aluminium corrosion fell from >10 mpy to <0.1 mpy. A once-through to closed-loop conversion saved 34 million gallons of water a year. The document is a supplier case example; the text notes results are not guaranteed and may vary.

Key points

  1. Open tower systems have stayed free of mineral deposits for over 10 years with good corrosion and microbiological control.
  2. A new HPC failed speed testing because of fouled cooling loops and passed after the CL2001 programme.
  3. For direct-to-chip systems a holistic approach avoided film inhibitors such as silicates.
  4. Aluminium corrosion fell from >10 mpy to <0.1 mpy (neutral-pH FlexPro multi-metal inhibitor).
  5. A once-through to closed-loop conversion saves 34 million gallons of water a year.
  6. Results are examples only, not guaranteed, and actual results may vary.

Using it in design

  • For direct-to-chip loops select the chemical programme (inhibitor, biocide) against the clogging risk of cold plate microchannels, and consider avoiding film-forming inhibitors.
  • For loops containing aluminium, specify a neutral-pH aluminium-compatible inhibitor and a corrosion rate target such as <0.1 mpy.
  • Tie pre-start loop cleaning and the water treatment plan to server speed and performance acceptance tests.
  • Where water saving is a goal, evaluate converting once-through systems to closed loop.

Who should read it

Engineers designing and operating direct-to-chip liquid cooling and cooling-tower water treatment programmes.

Document contents

  1. Introduction
  2. Improving cooling system performance (open recirculating towers, HPC cooling, aluminium closed loop, water conservation)
  3. Conclusion

Publication details

Authors
ChemTreat
Publisher
ChemTreat
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

ChemTreat Direct-to-Chip Liquid Cooling Treatment Helps DOE National Laboratory Improve System Performance. ChemTreat. https://cloud.kapostcontent.net/pub/70c368ef-39af-4006-87a3-416c87a5a462/direct-to-chip-liquid-cooling-treatment-helps-doe-national-laboratory-improve-system-performance

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.