Direct-to-Chip Liquid Cooling Treatment Helps DOE National Laboratory Improve System Performance (ChemTreat case study)
Original title Direct-to-Chip Liquid Cooling Treatment Helps DOE National Laboratory Improve System Performance
ChemTreat
ChemTreat case study: at a DOE national laboratory, cooling towers stayed deposit-free for over 10 years, aluminium corrosion fell from >10 mpy to <0.1 mpy, and a closed-loop conversion saved 34 million gallons of water a year.
On this page
Overview
The case study explains that US Department of Energy (DOE) national laboratories run extensive direct-to-chip liquid cooling and HPC systems that need customised water treatment to run at peak efficiency. One laboratory had performance problems in its open recirculating, closed-loop and HPC cooling systems; ChemTreat addressed four items with technical and analytical support.
In the open tower systems, mineral deposits reduced heat transfer and raised corrosion and microbiological activity; a polymeric dispersant and corrosion-inhibitor programme removed them and the systems have stayed deposit-free with good corrosion and microbiological control for over 10 years. A newly built HPC failed speed testing because its cooling loops were fouled with biological growth, mineral scale and additives; after the CL2001 programme, designed for CPU applications and avoiding film inhibitors such as silicates, it passed.
A closed loop with aluminium equipment suffered fouling events causing under-deposit corrosion; with the neutral-pH multi-metal FlexPro inhibitor the water became free of suspended solids and aluminium corrosion fell from >10 mpy to <0.1 mpy. A once-through to closed-loop conversion saved 34 million gallons of water a year. The document is a supplier case example; the text notes results are not guaranteed and may vary.
Key points
- Open tower systems have stayed free of mineral deposits for over 10 years with good corrosion and microbiological control.
- A new HPC failed speed testing because of fouled cooling loops and passed after the CL2001 programme.
- For direct-to-chip systems a holistic approach avoided film inhibitors such as silicates.
- Aluminium corrosion fell from >10 mpy to <0.1 mpy (neutral-pH FlexPro multi-metal inhibitor).
- A once-through to closed-loop conversion saves 34 million gallons of water a year.
- Results are examples only, not guaranteed, and actual results may vary.
Using it in design
- For direct-to-chip loops select the chemical programme (inhibitor, biocide) against the clogging risk of cold plate microchannels, and consider avoiding film-forming inhibitors.
- For loops containing aluminium, specify a neutral-pH aluminium-compatible inhibitor and a corrosion rate target such as <0.1 mpy.
- Tie pre-start loop cleaning and the water treatment plan to server speed and performance acceptance tests.
- Where water saving is a goal, evaluate converting once-through systems to closed loop.
Who should read it
Engineers designing and operating direct-to-chip liquid cooling and cooling-tower water treatment programmes.
Document contents
- Introduction
- Improving cooling system performance (open recirculating towers, HPC cooling, aluminium closed loop, water conservation)
- Conclusion
Publication details
- Authors
- ChemTreat
- Publisher
- ChemTreat
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
ChemTreat Direct-to-Chip Liquid Cooling Treatment Helps DOE National Laboratory Improve System Performance. ChemTreat. https://cloud.kapostcontent.net/pub/70c368ef-39af-4006-87a3-416c87a5a462/direct-to-chip-liquid-cooling-treatment-helps-doe-national-laboratory-improve-system-performance
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.