Technical guideFree to read2025

Risks and Benefits of using Peroxide-Cured EPDM (EPDM-P) vs. Sulfur-Cured Chloroprene (CR) in Data Center Water-Glycol Hose Applications

Danfoss · Danfoss Power Solutions

An April 2025 Danfoss white paper recommends peroxide-cured EPDM-P over sulfur-cured chloroprene (CR) for water-glycol data centre cooling hoses and reports 20-25% better heat stability.

On this page

Overview

The document is a four-page manufacturer white paper on hose material choice in data centres cooled with water-glycol mixtures. Chloroprene (CR) is often chosen for flame resistance, but sulfur curing brings corrosion and ozone degradation risks that can undermine reliability in water-glycol systems.

In sulfur-cured CR, elemental sulfur in contact with ferrous metals can oxidise to sulfur dioxide, which reacts with water vapour to form sulfuric acid and causes sulfidation corrosion. Carbon-black-filled CR has low electrical resistivity and can act as the cathode in a galvanic cell with dissimilar metals. CR ozone resistance relies on additives whose effect can fade over time.

Peroxide-cured EPDM-P contains no sulfur, has inherent ozone resistance from its saturated structure, and its higher electrical resistivity does not promote galvanic corrosion. Heat stability is reported as 20-25% better than sulfur-cured CR, with broader chemical compatibility, no staining of metal or PVC, and better compression set and fatigue resistance. The paper recommends EPDM-P for both tube and cover. It is a manufacturer view without measurement tables.

Key points

  1. The comparison is between peroxide-cured EPDM-P and sulfur-cured chloroprene (CR).
  2. CR's strength is flame resistance; its risks are sulfidation corrosion, galvanic corrosion and ozone degradation.
  3. Elemental sulfur can corrode ferrous metal fittings through sulfuric acid formation in the presence of moisture.
  4. Carbon-black-filled CR can act as the cathode in a galvanic cell with dissimilar metals.
  5. EPDM-P's saturated structure gives inherent ozone resistance and it contains no sulfur.
  6. EPDM-P heat stability is reported as 20-25% better than CR.
  7. EPDM-P does not stain metal or PVC and has better compression set and fatigue resistance.
  8. Recommendation: EPDM-P for both tube and cover in data centre water-glycol hoses.

Using it in design

  • Write the cure system (peroxide) and a no-sulfur requirement into the water-glycol hose specification.
  • Weigh UL94 rating against corrosion and ozone risk where flame resistance is required.
  • Avoid sulfur-bearing elastomers in circuits with ferrous metal fittings.
  • Include hose electrical resistivity in galvanic risk checks for mixed-metal circuits.
  • Plan hose life and maintenance interval according to material choice.

Who should read it

Mechanical engineers and procurement teams selecting hose and fitting materials for water-glycol cooling loops.

Document contents

  1. Executive summary
  2. Introduction
  3. Sulfur-cured chloroprene (CR)
  4. Peroxide-cured EPDM-P
  5. Additional benefits of EPDM-P in data center cooling
  6. Conclusion
  7. Recommendation

Publication details

Authors
Danfoss Power Solutions
Publisher
Danfoss
Year
2025
Document number
BE512954036134en-000101
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Danfoss Power Solutions (2025). Risks and Benefits of using Peroxide-Cured EPDM (EPDM-P) vs. Sulfur-Cured Chloroprene (CR) in Data Center Water-Glycol Hose Applications. Danfoss. BE512954036134en-000101. https://assets.danfoss.com/documents/latest/474562/BE512954036134en-000101.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.