Technical guideFree to readYear not stated

Supporting Cold Plate Performance: Why Filter Flow Direction Matters in Liquid Cooling Systems

Donaldson

A Donaldson technical article explaining how an inside-to-outside filter element reduces re-entry of captured particles into the loop during service, to protect cold plate microchannels as narrow as 100 microns.

On this page

Overview

The article explains that as liquid cooling spreads, coolant cleanliness matters more for long-term performance and filter design affects it. Cold plates remove CPU and GPU heat through dense microchannels that can be as small as 100 microns; particles entering these can affect flow distribution, pressure drop and thermal performance over time, and because cold plates are integrated into server hardware, fixing contamination afterwards is hard.

Two flow directions are compared. In outside-to-inside flow, contaminants are held on the element's outer surface; during service, when flow stops and the element is removed, accumulated particles can be disturbed and partly re-enter the stream. In inside-to-outside flow, fluid enters through the core and passes outward through the media, contaminants stay on the interior surface, and they leave the system with the element when it is replaced. Both designs filter effectively in normal operation; the difference arises during maintenance.

The article also gives an illustrative cost table: cold plate replacement at about USD 2,000-5,000 per server and server replacement after thermal-management-related failure at potentially USD 150,000-300,000 or more. These are examples and can vary widely with hardware, labour and operating conditions. It is a manufacturer article promoting the Donaldson PP-100-I HF element and contains no independent test data.

Key points

  1. Cold plate microchannels can be as small as 100 microns and are sensitive to particulate contamination.
  2. With outside-to-inside filtration, contaminants sit on the outer surface and some may re-enter the stream during service.
  3. With inside-to-outside filtration, contaminants stay on the inner surface and are removed with the element at replacement.
  4. Both directions filter effectively in normal operation; the difference appears during maintenance and service.
  5. Illustrative costs: cold plate replacement about USD 2,000-5,000 per server; server replacement potentially USD 150,000-300,000 or more.
  6. The filter is a small part of total infrastructure cost but affects the cleanliness of the whole circuit.

Using it in design

  • Link filter fineness and CDU filter placement in the specification to cold plate channel width (100 micron class).
  • Design the filter housing with a flow direction, isolation valves and drain path that limit contaminant escape during service.
  • Add steps to the filter maintenance procedure that limit particle return during element change, followed by a sample check.
  • In filter selection consider not only efficiency but also how contaminants are contained during maintenance and removed with the element.

Who should read it

Designers and maintenance teams choosing CDU filtration and cleanliness strategy for direct-to-chip liquid cooling.

Publication details

Authors
Donaldson
Publisher
Donaldson
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Donaldson Supporting Cold Plate Performance: Why Filter Flow Direction Matters in Liquid Cooling Systems. Donaldson. https://www.donaldson.com/en/resources/technical-articles/supporting-cold-plate-performance/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.