DOWFROST LC Inhibited Propylene Glycol-Based Heat Transfer Fluid: Engineering and Operating Guide
Dow · The Dow Chemical Company
Dow's guide for data-centre liquid cooling loops gives the properties, material compatibility, system preparation and maintenance limits of DOWFROST LC fluids at 25% and 55% propylene glycol.
On this page
Overview
The guide collects engineering and operating principles for DOWFROST LC fluids used in closed loops of datacom equipment cooling systems (DECS). Two ready-to-use blends are defined: LC 25 at 25% propylene glycol by volume (freezing point -10°C) and LC 55 at 55% (freezing point -40°C). Both use USP/EP grade glycol above 99.8% purity with corrosion inhibitors, pH buffers and stabilizers, and are dyed fluorescent yellow-green to reveal leak locations.
Property tables are detailed: at 50°C, LC 25 has thermal conductivity of 0.485 W/mK, specific heat of 3.94 kJ/kg-K and viscosity of 1.3 mPa s, against 0.336 W/mK, 3.43 kJ/kg-K and 2.9 mPa s for LC 55. Further tables give density, specific heat, conductivity, viscosity and vapour pressure from -5 to 80°C (-40 to 80°C for LC 55), plus the refractive index to glycol concentration relation. Because heat transfer and pressure drop worsen as glycol content rises, concentration should be held at the level freeze protection requires and no higher.
The design section covers protection of wetted metals (carbon steel, stainless steel, copper and copper alloys) up to 90°C and lists temperature limits for elastomers and plastics. EPDM, PE and PP are acceptable to at least 75°C, PTFE and FEP to at least 90°C; most NBR, FKM, PA, silicone and CR compositions are not recommended above 40°C, and POM is not recommended above 30°C. Final compatibility is left to confirmation by the component material supplier.
Preparation and maintenance sections set the fluid's service life: flushing, hydrostatic testing, vents, bypass filters and spill handling, then a representative sample after first circulation and a comprehensive annual analysis. Acceptance values are tabulated. The document is a manufacturer guide; the figures are typical values, not specifications, and they do not extend to fluids outside this product family.
Key points
- Ready-to-use blends: LC 25 (25% PG by volume, freezing point -10°C) and LC 55 (55% PG, -40°C); neither should be diluted further.
- Diluting glycol below 25% allows biodegradation and bacterial growth; at 25% and above, osmotic pressure suppresses bacteria and fungi.
- Operating range: 24-27% PG by volume for LC 25 and 53-57% for LC 55; the freezing point should sit at least 3°C below the lowest expected temperature.
- Maximum recommended bulk fluid temperature is 90°C; the normal lower operating limit is -20°C, with freeze protection to -40°C using LC 55.
- Electrical conductivity exceeds 2,000 micromho/cm, higher than water because of the inhibitor package.
- If dilution is unavoidable, purified water is required: chloride <25 mg/L, sulfate <25 mg/L, hardness <50 mg/L, iron <1 mg/L, conductivity <50 micromho/cm.
- In-service acceptance values: pH 8.0-10.5, reserve alkalinity >4 mL (0.1N HCl), copper and iron <2 ppm, hardness <100 ppm, chloride and sulfate <25 ppm.
- In ASTM D1384 testing (88°C, 2 weeks) LC 25 shows copper loss of 0.6 mg and aluminium loss of 2 mg; rates above 0.5 mpy (2.5 mpy for aluminium) indicate inadequate protection.
- The fluid ages through oxidation products; when pH falls below 8.0 it has reached end of life and must be drained and replaced.
Using it in design
- Check the loop's wetted-materials list (pipe, seals, pump mechanical seals, valves) against the fluid's minimum and maximum temperatures; watch the 30-40°C limits of NBR, FKM, silicone, PA and POM.
- Choose the lowest glycol concentration that gives freeze protection, and size CDU pumps for the viscosity penalty (8.8 mPa s against 2.8 mPa s at 20°C) in pressure drop.
- Put complete drainage of flush water, vents, a bypass filter and a post-circulation sampling point (not on a dead leg) into the commissioning plan.
- Write an annual sampling routine (pH, reserve alkalinity, glycol concentration, metal and ion limits) and replacement criteria into the operating procedure.
- Avoid turbulence and air contact in the expansion tank, and size it for volume expansion (5.2% for LC 25 and 7.7% for LC 55 between -40 and 90°C).
Who should read it
Mechanical designers who specify and operate direct-to-chip liquid cooling loops, plus commissioning and maintenance engineers.
Document contents
- Introduction
- Properties of DOWFROST LC Heat Transfer Fluids
- System design considerations
- System preparation
- Fluid testing and maintenance
- Conditions to avoid
Publication details
- Authors
- The Dow Chemical Company
- Publisher
- Dow
- Year
- 2023
- Document number
- 176-01641-01-0623 S2D
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
The Dow Chemical Company (2023). DOWFROST LC Inhibited Propylene Glycol-Based Heat Transfer Fluid: Engineering and Operating Guide. Dow. 176-01641-01-0623 S2D. https://www.glycolsales.com.au/wp-content/uploads/2025/07/176-01641-01-dowfrost-lc-engineering-and-operating-guide.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.