Technical guideFree to readYear not stated

Single Phase Immersion Cooling Fluids: FUCHS RENOLIN FECC Brochure

Original title Single Phase Immersion Cooling Fluids: For Today’s Digital Computing Revolution

FUCHS

FUCHS brochure comparing its RENOLIN FECC 7 and FECC 5 SYNTH single-phase immersion fluids with OCP specification values: thermal conductivity 0.126-0.133 W/mK at 50°C, flash point above 150°C, breakdown voltage above 40 kV.

On this page

Overview

The brochure states that computing demand from AI, 5G and crypto-mining exceeds what air cooling can supply in space, energy and water, and that single-phase immersion fluids offer zero ozone depletion and global warming potential with a simpler design. For existing air-cooled sites it lists lower operating expenses and CO2 footprint, and for new builds the absence of chillers, air handlers and server fans.

The product line is RENOLIN FECC (Fluids for Electronic Component Cooling), made from selected synthetic base oils and additives. RENOLIN FECC 5 SYNTH was recognised as the first OCP Inspired single-phase immersion coolant meeting the Immersion Requirements Rev. 2.1; FECC 5 SYNTH and FECC 7 are also approved by Iceotope. Values are tabulated beside the OCP requirements.

The tables give, for FECC 7 and FECC 5 SYNTH respectively: pour point -45 and -66°C, kinematic viscosity at 40°C of 7.6 and 5.1 mm2/s, density at 50°C of 809 and 775 kg/m3, specific heat of 1920 and 2080 J/(kg K), thermal conductivity of 0.126 and 0.133 W/(m K), natural-convection FOM1 of 50.6 and 60.2 and forced-convection FOM2 of 29.1 and 30.5. Electrical values include breakdown voltage >40 kV, volume resistivity >2.0e11 ohm-cm and dielectric constant of 2.11 and 2.07. It is a manufacturer brochure with manufacturer test data, and also promotes fluid management and recycling services.

Key points

  1. RENOLIN FECC 5 SYNTH is the first OCP Inspired single-phase immersion coolant meeting Immersion Requirements Rev. 2.1.
  2. Pour point is -45°C for FECC 7 and -66°C for FECC 5 SYNTH (OCP requirement < -30°C).
  3. Kinematic viscosity at 40°C is 7.6 and 5.1 mm2/s; density at 50°C is 809 and 775 kg/m3.
  4. At 50°C specific heat is 1920 and 2080 J/(kg K) and thermal conductivity 0.126 and 0.133 W/(m K).
  5. Natural-convection FOM1 values are 50.6 and 60.2; OCP asks > 35 for current processors and > 45 for next-generation ones.
  6. Forced-convection FOM2 values are 29.1 and 30.5 (OCP requirement > 19).
  7. Breakdown voltage > 40 kV; dielectric constant 2.11 and 2.07 (limit ≤ 2.3); loss tangent 0.0011 (limit ≤ 0.05).
  8. Closed-cup flash point is 165 and 153°C (OCP > 150°C); GWP 0, no ozone depletion potential, low toxicity.

Using it in design

  • Compare immersion fluids on one table of OCP properties (FOM1 and FOM2, viscosity, density, specific heat, conductivity) at 50°C and across 20-70°C.
  • For high-speed signal integrity compare dielectric constant and loss tangent with the hardware maker's limits.
  • In fire safety review record flash point (153-165°C closed cup) and auto-ignition temperature (>239°C for FECC 7).
  • Before a fluid change arrange supplier engineering consultation and a fluid quality monitoring plan.

Who should read it

Designers and procurement engineers evaluating single-phase immersion fluids and OCP compliance.

Publication details

Authors
FUCHS
Publisher
FUCHS
Year
Year not stated
Document number
930093929
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

FUCHS Single Phase Immersion Cooling Fluids: For Today’s Digital Computing Revolution. FUCHS. 930093929. https://www.fuchs.com/fileadmin/us/product-data/Single-Phase-Immersion-Cooling-Fluids_Brochure_US.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.